Article number

6ES7212-1AF40-0XB0

6ES7212-1HF40-0XB0

6ES7214-1AF40-0XB0

6ES7214-1HF40-0XB0

6ES7215-1AF40-0XB0

6ES7215-1HF40-0XB0

CPU 1212FC ,DC/DC/DC, 8DI/6DO/2AI

CPU 1212FC, DC/DC/RELAY, 8DI/6DO/2AI

CPU 1214 FC, DC/DC/DC, 14DI/10DO/2AI

CPU 1214 FC, DC/DC/RELAY, 14DI/10DO/2AI

CPU 1215 FC, DC/DC/DC, 14DI/10DO/2AI/2AO

CPU 1215 FC, DC/DC/RLY,14DI/10DO/2AI/2AO

General information

Product type designation

CPU 1212FC DC/DC/DC

CPU 1212FC DC/DC/relay

CPU 1214FC DC/DC

CPU 1214FC DC/DC/Relay

CPU 1215FC DC/DC/DC

CPU 1215C DC/DC/relay

Firmware version

V4.2

V4.2

V4.2

V4.2

V4.2

V4.2

Engineering with

  • Programming package

STEP 7 V14 or higher

STEP 7 V14 or higher

STEP 7 V14 or higher

STEP 7 V14 or higher

STEP 7 V14 or higher

STEP 7 V14 or higher

Supply voltage

Rated value (DC)

  • 24 V DC

Yes

Yes

Yes

Yes

Yes

Yes

permissible range, lower limit (DC)

20.4V

20.4V

20.4V

20.4V

20.4V

20.4V

permissible range, upper limit (DC)

28.8V

28.8V

28.8V

28.8V

28.8V

28.8V

Reverse polarity protection

Yes

Yes

Load voltage L+

  • Rated value (DC)

24V

24V

24V

24V

24V

  • permissible range, lower limit (DC)

20.4V

20.4V

20.4V

20.4V

20.4V

  • permissible range, upper limit (DC)

28.8V

28.8V

28.8V

28.8V

28.8V

Input current

Current consumption (rated value)

375mA; Typical

500mA; CPU only

500mA; CPU only

Current consumption, max.

1500mA; max. with all expansion accessories

1500mA; max. with all expansion accessories

1500mA; CPU with all expansion modules

1500mA; CPU with all expansion modules

Inrush current, max.

12A; at 28.8 V DC

12A; at 28.8 V DC

12A; at 28.8 V DC

12A; at 28.8 V DC

12A; at 28.8 V DC

It

0.5As

0.5As

0.5As

0.5As

0.5As

0.5As

Output current

for backplane bus (5 V DC), max.

1000mA; Max. 5 V DC for SM and CM

1000mA; Max. 5 V DC for SM and CM

1600mA; Max. 5 V DC for SM and CM

1600mA; Max. 5 V DC for SM and CM

1600mA; Max. 5 V DC for SM and CM

1600mA; Max. 5 V DC for SM and CM

Encoder supply

24 V encoder supply

  • 24 V

Permissible range: 20.4V to 28.8V

Permissible range: 20.4V to 28.8V

L+ minus 4 V DC min.

L+ minus 4 V DC min.

L+ minus 4 V DC min.

L+ minus 4 V DC min.

Power loss

Power loss, typ.

9W

9W

12W

12W

12W

12W

Memory

Work memory

  • integrated

100kbyte

100kbyte

125kbyte

125kbyte

150kbyte

150kbyte

  • expandable

No

No

No

No

No

No

Load memory

  • integrated

2Mbyte

2Mbyte

4Mbyte

4Mbyte

4Mbyte

4Mbyte

  • Plug-in (SIMATIC Memory Card), max.

with SIMATIC memory card

with SIMATIC memory card

with SIMATIC memory card

with SIMATIC memory card

with SIMATIC memory card

with SIMATIC memory card

Backup

  • present

Yes

Yes

Yes

Yes

Yes

Yes

  • maintenance-free

Yes

Yes

Yes

Yes

Yes

Yes

  • without battery

Yes

Yes

Yes

Yes

Yes

Yes

CPU processing times

for bit operations, typ.

0.08s; / instruction

0.08s; / instruction

0.08s; / instruction

0.08s; / instruction

0.08s; / instruction

0.08s; / instruction

for word operations, typ.

1.7s; / instruction

1.7s; / instruction

1.7s; / instruction

1.7s; / instruction

1.7s; / instruction

1.7s; / instruction

for floating point arithmetic, typ.

2.5s; / instruction

2.5s; / instruction

2.3s; / instruction

2.3s; / instruction

2.3s; / instruction

2.3s; / instruction

CPU-blocks

Number of blocks (total)

DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used

DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used

DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used

DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used

DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used

DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used

OB

  • Number, max.

Limited only by RAM for code

Limited only by RAM for code

Limited only by RAM for code

Limited only by RAM for code

Limited only by RAM for code

Limited only by RAM for code

Data areas and their retentivity

Retentive data area (incl. timers, counters, flags), max.

10kbyte

10kbyte

10kbyte

10kbyte

10kbyte

10kbyte

Flag

  • Number, max.

4kbyte; Size of bit memory address area

4kbyte; Size of bit memory address area

8kbyte; Size of bit memory address area

8kbyte; Size of bit memory address area

8kbyte; Size of bit memory address area

8kbyte; Size of bit memory address area

Local data

  • per priority class, max.

16kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB

16kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB

16kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB

16kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB

16kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB

16kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB

Address area

I/O address area

  • Inputs

1024byte

1024byte

1024byte

  • Outputs

1024byte

1024byte

1024byte

Process image

  • Inputs, adjustable

1kbyte

1kbyte

1kbyte

1kbyte

1kbyte

1kbyte

  • Outputs, adjustable

1kbyte

1kbyte

1kbyte

1kbyte

1kbyte

1kbyte

Hardware configuration

Number of modules per system, max.

3 comm. modules, 1 signal board, 2 signal modules

3 comm. modules, 1 signal board, 2 signal modules

3 comm. modules, 1 signal board, 8 signal modules

3 comm. modules, 1 signal board, 8 signal modules

3 comm. modules, 1 signal board, 8 signal modules

3 comm. modules, 1 signal board, 8 signal modules

Time of day

Clock

  • Hardware clock (real-time)

Yes

Yes

Yes

Yes

Yes

  • Backup time

480h; Typical

480h; Typical

480h; typical; 12 days min. at 40 C

480h; Typical

480h; Typical

  • Deviation per day, max.

60 s/month at 25 C

60 s/month at 25 C

60 s per month

60 s/month at 25 C

60 s/month at 25 C

Digital inputs

Number of digital inputs

8; Integrated

8; Integrated

14

14

14; Integrated

14; Integrated

  • of which inputs usable for technological functions

4; HSC (High Speed Counting)

4; HSC (High Speed Counting)

6; HSC (High Speed Counting)

6; HSC (High Speed Counting)

6; HSC (High Speed Counting)

Source/sink input

Yes

Yes

Yes

Yes

Yes

Number of simultaneously controllable inputs

all mounting positions

  • up to 40 C, max.

8

8

14; 14 inputs at 55 C horizontal or 45 C vertical

14

14

Input voltage

  • Rated value (DC)

24V

24V

24V; DC at 4 mA nominal

24V

24V

  • for signal "0"

5 V DC at 1 mA

5 V DC at 1 mA

5 V DC at 1 mA

5 V DC at 1 mA

5 V DC at 1 mA

  • for signal "1"

15 V DC at 2.5 mA

15 V DC at 2.5 mA

15 V DC at 2.5 mA

15 V DC at 2.5 mA

15 V DC at 2.5 mA

Input current

  • for signal "1", typ.

1mA

1mA

4mA; nominal

Input delay (for rated value of input voltage)

for standard inputs

  • parameterizable

0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four

0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four

0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 μs; 0.05 / 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 ms

Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four

Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four

  • at "0" to "1", min.

0.2ms

0.2ms

0.1s

0.2ms

0.2ms

  • at "0" to "1", max.

12.8ms

12.8ms

20ms

12.8ms

12.8ms

for interrupt inputs

  • parameterizable

Yes

Yes

Yes

Yes

Yes

for counter/technological functions

  • parameterizable

Single phase: 3 @ 100 kHz & 1 @ 30 kHz, differential: 3 @ 80 kHz & 1 @ 30 kHz

Yes; Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80 kHz & 3 @ 30 kHz

Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80 kHz & 3 @ 30 kHz

Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80 kHz & 3 @ 30 kHz

Cable length

  • shielded, max.

500m; 50 m for technological functions

500m; 50 m for technological functions

500m; 50 m for technological functions

500m; 50 m for technological functions

  • unshielded, max.

300m; For technological functions: No

150m; For technological functions: No

300m; For technological functions: No

300m; For technological functions: No

Digital outputs

Number of digital outputs

6

6

10

10

10

10; Relays

  • of which high-speed outputs

4; 100 kHz Pulse Train Output

4; 100 kHz Pulse Train Output

4; 100 kHz Pulse Train Output

Short-circuit protection

No; to be provided externally

No; to be provided externally

Limitation of inductive shutdown voltage to

L+ (-48 V)

L+ (-48 V)

Switching capacity of the outputs

  • with resistive load, max.

0.5A

2A

0.5A

0.5A

2A

  • on lamp load, max.

5W

30 W with DC, 200 W with AC

5W

5W

30 W with DC, 200 W with AC

Output voltage

  • for signal "0", max.

0.1V; with 10 kOhm load

0.1V; with 10 kOhm load

0.1V; with 10 kOhm load

  • for signal "1", min.

20 V

20 V

20 V

Output current

  • for signal "1" rated value

0.5A

0.5A

0.5A

  • for signal "0" residual current, max.

0.1mA

0.1mA

0.1mA

Output delay with resistive load

  • "0" to "1", max.

1s

10ms; max.

1s

1s

10ms; max.

  • "1" to "0", max.

5s

10ms; max.

3s

5s

10ms; max.

Switching frequency

  • of the pulse outputs, with resistive load, max.

100kHz

1Hz

100kHz

100kHz

Relay outputs

  • Number of operating cycles, max.

mechanically 10 million, at rated load voltage 100 000

Cable length

  • shielded, max.

500m

500m

500m

500m

500m

  • unshielded, max.

150m

150m

150m

150m

150m

Analog inputs

Number of analog inputs

2

2

2

2

2

2

Input ranges

  • Voltage

Yes

Yes

Yes

Yes

Yes

Yes

Input ranges (rated values), voltages

  • 0 to +10 V

Yes

Yes

Yes

Yes

Yes

Yes

  • Input resistance (0 to 10 V)

≥100k ohms

≥100k ohms

≥100k ohms

≥100k ohms

≥100k ohms

≥100k ohms

Cable length

  • shielded, max.

100m; twisted and shielded

100m; twisted and shielded

100m; twisted and shielded

100m; twisted and shielded

100m; twisted and shielded

100m; twisted and shielded

Analog outputs

Number of analog outputs

0

0

0

0

2

2

Output ranges, current

  • 0 to 20 mA

Yes

Yes

Yes

Analog value generation for the inputs

Integration and conversion time/resolution per channel

  • Resolution with overrange (bit including sign), max.

10bit

10bit

10bit

10bit

10bit

10bit

  • Integration time, parameterizable

Yes

Yes

Yes

Yes

Yes

Yes

  • Conversion time (per channel)

625s

625s

625s

625s

625s

625s

Analog value generation for the outputs

Integration and conversion time/resolution per channel

  • Resolution with overrange (bit including sign), max.

10bit

10bit

Encoder

Connectable encoders

  • 2-wire sensor

Yes

Yes

Yes

Yes

Yes

Yes

1. Interface

Interface type

PROFINET

PROFINET

PROFINET

PROFINET

PROFINET

PROFINET

Physics

Ethernet

Ethernet

Ethernet

Ethernet

Ethernet

Ethernet

Isolated

Yes

Yes

Yes

Yes

Yes

Yes

automatic detection of transmission rate

Yes

Yes

Yes

Yes

Yes

Yes

Autonegotiation

Yes

Yes

Yes

Yes

Yes

Yes

Autocrossing

Yes

Yes

Yes

Yes

Yes

Yes

Interface types

  • Number of ports

1

1

1

1

2

2

  • integrated switch

Yes

Yes

Yes

Yes

Yes

Yes

Functionality

  • PROFINET IO Controller

Yes

Yes

Yes

Yes

Yes

Yes

  • PROFINET IO Device

Yes

Yes

Yes

Yes

Yes

Yes

  • SIMATIC communication

Yes

Yes

Yes

Yes

Yes

Yes

  • Open IE communication

Yes

Yes

Yes

Yes

Yes

Yes

  • Web server

Yes

Yes

Yes

Yes

Yes

Yes

  • Media redundancy

Yes; as MRP client

Yes; as MRP client

Yes; as MRP client

Yes; as MRP client

PROFINET IO Controller

  • Transmission rate, max.

100Mbit/s

100Mbit/s

100Mbit/s

100Mbit/s

100Mbit/s

100Mbit/s

Services

  • PG/OP communication

Yes

Yes

Yes

Yes

Yes

Yes

  • S7 routing

Yes

Yes

Yes

Yes

Yes

Yes

  • Isochronous mode

No

No

No

No

No

No

  • Open IE communication

Yes

Yes

Yes

Yes

Yes

Yes

  • IRT

No

No

No

No

No

No

  • MRP

No

No

No

No

Yes; as MRP client

Yes; as MRP client

  • MRPD

No

No

No

No

No

No

  • PROFIenergy

No

No

No

No

No

No

  • Prioritized startup

Yes

Yes

Yes

Yes

Yes

Yes

  • Number of IO devices with prioritized startup, max.

16

16

16

16

16

16

  • Number of connectable IO Devices, max.

16

16

16

16

16

16

  • Number of connectable IO Devices for RT, max.

16

16

16

16

16

16

  • of which in line, max.

16

16

16

16

16

16

  • Activation/deactivation of IO Devices

Yes

Yes

Yes

Yes

Yes

Yes

  • Number of IO Devices that can be simultaneously activated/deactivated, max.

8

8

8

8

8

8

  • Updating time

The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data.

The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data.

The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data.

The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data.

The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data.

The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data.

PROFINET IO Device

Services

  • PG/OP communication

Yes

Yes

Yes

Yes

Yes

Yes

  • S7 routing

Yes

Yes

Yes

Yes

Yes

Yes

  • Isochronous mode

No

No

No

No

No

No

  • Open IE communication

Yes

Yes

Yes

Yes

Yes

Yes

  • IRT

No

No

No

No

No

No

  • MRP

No

No

No

No

Yes; as MRP client

Yes; as MRP client

  • MRPD

No

No

No

No

No

No

  • PROFIenergy

Yes

Yes

Yes

Yes

Yes

Yes

  • Shared device

Yes

Yes

Yes

Yes

Yes

Yes

  • Number of IO Controllers with shared device, max.

2

2

2

2

2

2

Protocols

Supports protocol for PROFINET IO

Yes

Yes

Yes

Yes

Yes

Yes

PROFIBUS

Yes; CM 1243-5 required

Yes; CM 1243-5 required

Yes; CM 1243-5 required

Yes; CM 1243-5 required

Yes; CM 1243-5 required

Yes; CM 1243-5 required

AS-Interface

Yes; CM 1243-2 required

Yes; CM 1243-2 required

Yes; CM 1243-2 required

Yes; CM 1243-2 required

Yes; CM 1243-2 required

Yes; CM 1243-2 required

Protocols (Ethernet)

  • TCP/IP

Yes

Yes

Yes

Yes

Yes

Yes

  • DHCP

No

No

No

No

No

No

  • SNMP

Yes

Yes

Yes

Yes

Yes

Yes

  • DCP

Yes

Yes

Yes

Yes

Yes

Yes

  • LLDP

Yes

Yes

Yes

Yes

Yes

Yes

Open IE communication

  • TCP/IP

Yes

Yes

Yes

Yes

Yes

Yes

  • Data length, max.

8kbyte

8kbyte

8kbyte

8kbyte

8kbyte

8kbyte

  • ISO-on-TCP (RFC1006)

Yes

Yes

Yes

Yes

Yes

Yes

  • Data length, max.

8kbyte

8kbyte

8kbyte

8kbyte

8kbyte

8kbyte

  • UDP

Yes

Yes

Yes

Yes

Yes

Yes

  • Data length, max.

1472byte

1472byte

1472byte

1472byte

1472byte

1472byte

Web server

  • User-defined websites

Yes

Yes

Yes

Yes

Yes

Yes

Further protocols

  • MODBUS

Yes

Yes

Yes

Yes

Yes

Yes

Communication functions

S7 communication

  • supported

Yes

Yes

Yes

Yes

Yes

Yes

  • as server

Yes

Yes

Yes

Yes

Yes

Yes

  • as client

Yes

Yes

Yes

Yes

Yes

Yes

  • User data per job, max.

See online help (S7 communication, user data size)

See online help (S7 communication, user data size)

See online help (S7 communication, user data size)

See online help (S7 communication, user data size)

See online help (S7 communication, user data size)

See online help (S7 communication, user data size)

Web server

  • supported

Yes

Yes

Yes

Yes

Yes

Yes

Number of connections

  • overall

16; dynamically

16; dynamically

16; dynamically

16; dynamically

Test commissioning functions

Status/control

  • Status/control variable

Yes

Yes

Yes

Yes

Yes

Yes

  • Variables

Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters

Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters

Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters

Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters

Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters

Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters

Forcing

  • Forcing

Yes

Yes

Yes

Yes

Yes

Yes

Diagnostic buffer

  • present

Yes

Yes

Yes

Yes

Yes

Yes

Traces

  • Number of configurable Traces

2

2

2

2

2

2

  • Memory size per trace, max.

512kbyte

512kbyte

512kbyte

512kbyte

512kbyte

512kbyte

Interrupts/diagnostics/status information

Diagnostics indication LED

  • RUN/STOP LED

Yes

Yes

  • ERROR LED

Yes

Yes

  • MAINT LED

Yes

Yes

Integrated Functions

Number of counters

4

4

6

6

6

6

Counting frequency (counter) max.

100kHz

100kHz

100kHz

100kHz

100kHz

100kHz

Frequency measurement

Yes

Yes

Yes

Yes

Yes

Yes

controlled positioning

Yes

Yes

Yes

Yes

Yes

Yes

Number of position-controlled positioning axes, max.

8

8

8

8

8

8

Number of positioning axes via pulse-direction interface

Up to 4 with SB 1222

Up to 4 with SB 1222

Up to 4 with SB 1222

Up to 4 with SB 1222

4; With integrated outputs

Up to 4 with SB 1222

PID controller

Yes

Yes

Yes

Yes

Yes

Yes

Number of alarm inputs

4

4

4

4

4

Number of pulse outputs

4

4

4

Limit frequency (pulse)

100kHz

100kHz

Potential separation

Potential separation digital inputs

  • Potential separation digital inputs

500V AC for 1 minute

500V AC for 1 minute

Functional isolation (Optocoupler)

No

500V AC for 1 minute

  • between the channels, in groups of

1

1

1

1

Potential separation digital outputs

  • Potential separation digital outputs

Yes

Relays

Yes

Relays

  • between the channels

No

No

No

No

  • between the channels, in groups of

1

1

1

2

Permissible potential difference

between different circuits

500 V DC between 24 V DC and 5 V DC

500 V DC between 24 V DC and 5 V DC

EMC

Interference immunity against discharge of static electricity

  • Interference immunity against discharge of static electricity acc. to IEC 61000-4-2

Yes

Yes

Yes

Yes

Yes

Yes

  • Test voltage at air discharge

8kV

8kV

8kV

8kV

8kV

8kV

  • Test voltage at contact discharge

6kV

6kV

6kV

6kV

6kV

6kV

Interference immunity to cable-borne interference

  • Interference immunity on supply lines acc. to IEC 61000-4-4

Yes

Yes

Yes

Yes

Yes

Yes

  • Interference immunity on signal cables acc. to IEC 61000-4-4

Yes

Yes

Yes

Yes

Yes

Yes

Interference immunity against voltage surge

  • on the supply lines acc. to IEC 61000-4-5

Yes

Yes

Yes

Yes

Yes

Yes

Interference immunity against conducted variable disturbance induced by high-frequency fields

  • Interference immunity against high-frequency radiation acc. to IEC 61000-4-6

Yes

Yes

Yes

Yes

Yes

Yes

Emission of radio interference acc. to EN 55 011

  • Limit class A, for use in industrial areas

Yes; Group 1

Yes; Group 1

Yes; Group 1

Yes; Group 1

Yes; Group 1

Yes; Group 1

  • Limit class B, for use in residential areas

Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011

Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011

Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011

Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011

Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011

Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011

Degree and class of protection

Degree of protection acc. to EN 60529

  • IP20

Yes

Yes

Yes

Yes

Yes

Standards, approvals, certificates

CE mark

Yes

Yes

Yes

Yes

Yes

Yes

UL approval

Yes

Yes

Yes

Yes

Yes

Yes

cULus

Yes

Yes

Yes

Yes

Yes

Yes

FM approval

Yes

Yes

Yes

Yes

Yes

Yes

RCM (formerly C-TICK)

Yes

Yes

Yes

Yes

Yes

Yes

KC approval

Yes

Yes

Yes

Yes

Yes

Yes

Marine approval

Yes

Yes

Yes

Yes

Yes

Yes

Highest safety class achievable in safety mode

  • Performance level according to ISO 13849-1

PLe

PLe

PLe

PLe

PLe

PLe

  • SIL acc. to IEC 61508

SIL 3

SIL 3

SIL 3

SIL 3

SIL 3

SIL 3

Ambient conditions

Free fall

  • Fall height, max.

0.3m; five times, in product package

0.3m; five times, in product package

0.3m; five times, in product package

0.3m; five times, in product package

0.3m; five times, in product package

Ambient temperature during operation

  • min.

0C

0C

0C

0C

0C

0C

  • max.

55C

55C

55C

55C

55C

55C

  • horizontal installation, min.

0C

0C

0C

0C

0C

0C

  • horizontal installation, max.

55C

55C

55C

55C

55C

55C

  • vertical installation, min.

0C

0C

0C

0C

0C

0C

  • vertical installation, max.

45C

45C

45C

45C

45C

45C

Ambient temperature during storage/transportation

  • min.

-40C

-40C

-40C

-40C

-40C

-40C

  • max.

70C

70C

70C

70C

70C

70C

Air pressure acc. to IEC 60068-2-13

  • Operation, min.

795hPa

795hPa

  • Operation, max.

1080hPa

1080hPa

  • Storage/transport, min.

660hPa

660hPa

660hPa

660hPa

660hPa

660hPa

  • Storage/transport, max.

1139hPa

1139hPa

1139hPa

1139hPa

1080hPa

1080hPa

  • Installation altitude, min.

-1000m

-1000m

  • Installation altitude, max.

2000m

2000m

Relative humidity

  • Operation, max.

95%; no condensation

95%; no condensation

95%; no condensation

95%; no condensation

95%; no condensation

95%; no condensation

Vibrations

  • Vibration resistance during operation acc. to IEC 60068-2-6

2 g (m/s) wall mounting, 1 g (m/s) DIN rail

2 g (m/s) wall mounting, 1 g (m/s) DIN rail

2 g (m/s) wall mounting, 1 g (m/s) DIN rail

2 g (m/s) wall mounting, 1 g (m/s) DIN rail

2 g (m/s) wall mounting, 1 g (m/s) DIN rail

2 g (m/s) wall mounting, 1 g (m/s) DIN rail

  • Operation, tested according to IEC 60068-2-6

Yes

Yes

Yes

Yes

Yes

Yes

Shock testing

  • tested according to IEC 60068-2-27

Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms

Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms

Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms

Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms

Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms

Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms

Pollutant concentrations

  • SO2 at RH < 60% without condensation

S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free

S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free

S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free

S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free

S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free

S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free

Programming

Programming language

  • LAD

Yes; incl. failsafe

Yes; incl. failsafe

Yes; incl. failsafe

Yes; incl. failsafe

Yes; incl. failsafe

Yes; incl. failsafe

  • FBD

Yes; incl. failsafe

Yes; incl. failsafe

Yes; incl. failsafe

Yes; incl. failsafe

Yes; incl. failsafe

Yes; incl. failsafe

  • SCL

Yes

Yes

Yes

Yes

Yes

Yes

Know-how protection

  • User program protection/password protection

Yes

Yes

Yes

Yes

Yes

Yes

  • Copy protection

Yes

Yes

Yes

Yes

Yes

Yes

  • Block protection

Yes

Yes

Yes

Yes

Yes

Yes

Access protection

  • Protection level: Write protection

Yes

Yes

  • Protection level: Read/write protection

Yes

Yes

  • Protection level: Complete protection

Yes

Yes

Cycle time monitoring

  • adjustable

Yes

Yes

Yes

Yes

Yes

Yes

Dimensions

Width

90mm

90mm

110mm

110mm

130mm

130mm

Height

100mm

100mm

100mm

100mm

100mm

100mm

Depth

75mm

75mm

75mm

75mm

75mm

75mm

Weights

Weight, approx.

370g

385g

435g

435g

585g

585g


















skener.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
DENDOR

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS -

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK -

  © " " 2007-2022
  (4872) 700-366  skenergo@mail.ru
.