General information | |
Product type designation | DI 16x24 V DC/DQ 16x24 V DC/0.5 A BA |
HW functional status | FS01 |
Firmware version | V1.0.0 |
| Yes |
Product function | |
| Yes; I&M0 to I&M3 |
Engineering with | |
| V13 / V13 |
| V5.5 SP3 / - |
| V1.0 / V5.1 |
| V2.3 / - |
Operating mode | |
| Yes |
| No |
| Yes |
| No |
| No |
| No |
| Yes |
| Yes |
Supply voltage | |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes; through internal protection with 7 A per group |
Input current | |
Current consumption, max. | 30 mA |
Output voltage | |
Rated value (DC) | 24 V |
Power | |
Power available from the backplane bus | 1.1 W |
Power loss | |
Power loss, typ. | 3.45 W |
Digital inputs | |
Number of digital inputs | 16 |
Digital inputs, parameterizable | No |
Source/sink input | P-reading |
Input characteristic curve in accordance with IEC 61131, type 3 | Yes |
Input voltage | |
| DC |
| 24 V |
| -30 to +5V |
| +11 to +30V |
Input current | |
| 2.7 mA |
Input delay (for rated value of input voltage) | |
for standard inputs | |
| No |
| 3 ms |
| 4 ms |
| 3 ms |
| 4 ms |
for interrupt inputs | |
| No |
Cable length | |
| 1 000 m |
| 600 m |
Digital outputs | |
Type of digital output | Transistor |
Number of digital outputs | 16 |
Current-sourcing | Yes |
Short-circuit protection | Yes |
| 1 A |
Limitation of inductive shutdown voltage to | L+ (-53 V) |
Controlling a digital input | Yes |
Switching capacity of the outputs | |
| 0.5 A |
| 5 W |
Load resistance range | |
| 48 Ω |
| 12 kΩ |
Output voltage | |
| L+ (-0.8 V) |
Output current | |
| 0.5 A |
| 0.5 A |
| 0.5 mA |
Output delay with resistive load | |
| 100 µs |
| 500 µs |
Parallel switching of two outputs | |
| Yes |
| No |
| Yes |
Switching frequency | |
| 100 Hz |
| 0.5 Hz |
| 10 Hz |
Total current of the outputs | |
| 0.5 A; see additional description in the manual |
| 4 A; see additional description in the manual |
| 8 A; see additional description in the manual |
Cable length | |
| 1 000 m |
| 600 m |
Encoder | |
Connectable encoders | |
| Yes |
| 1.5 mA |
Isochronous mode | |
Isochronous operation (application synchronized up to terminal) | No |
Interrupts/diagnostics/status information | |
Diagnostics function | No |
Substitute values connectable | No |
Alarms | |
| No |
| No |
Diagnostic messages | |
| No |
| No |
| No |
| No |
Diagnostics indication LED | |
| Yes; Green LED |
| Yes; Red LED |
| Yes; Green LED |
| Yes; Green LED |
| No |
| No |
Potential separation | |
Potential separation channels | |
| No |
| 8 |
| Yes |
Isolation | |
Isolation tested with | 707 V DC (type test) |
Ambient conditions | |
Ambient temperature during operation | |
| 0 °C |
| 60 °C |
| 0 °C |
| 40 °C |
Decentralized operation | |
Prioritized startup | Yes |
Dimensions | |
Width | 25 mm |
Height | 147 mm |
Depth | 129 mm |
Weights | |
Weight, approx. | 280 g |
Other | |
Note: | Supplied incl. 40-pole push-in front connectors |