General information | |
Product type designation | IM 155-5 PN ST |
HW functional status | E01 |
Firmware version | V1.0.0 |
Vendor identification (VendorID) | 0x002A |
Device identifier (DeviceID) | 0X0312 |
Product function | |
| Yes; I&M0 to I&M3 |
Engineering with | |
| V12 / V12 |
| V5.5 SP3 / - |
| V1.0 / V2.23 |
Supply voltage | |
Type of supply voltage | DC |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Short-circuit protection | Yes |
Mains buffering | |
| 5 ms |
Input current | |
Current consumption (rated value) | 0.2 A |
Current consumption, max. | 1.2 A |
Inrush current, max. | 9 A |
IІt | 0.09 AІ·s |
Power | |
Infeed power to the backplane bus | 14 W |
Power available from the backplane bus | 2.3 W |
Power loss | |
Power loss, typ. | 4.5 W; Typical |
Address area | |
Address space per module | |
| 256 byte; per input / output |
Address space per station | |
| 512 byte; per input / output |
Hardware configuration | |
System power supply can be plugged in to left of IM | Yes |
Number of permissible power segments | 3 |
Rack | |
| 30; I/O modules |
Interfaces | |
Number of PROFINET interfaces | 1 |
1. Interface | |
Interface types | |
| 2 |
| Yes |
| Yes |
Functionality | |
| Yes |
| Yes |
Interface types | |
RJ 45 (Ethernet) | |
| PROFINET with 100 Mbit/s full duplex (100BASE-TX) |
| Yes |
| Yes |
| Yes |
PROFINET IO Device | |
Services | |
| Yes |
| Yes |
| Yes; 500 ms |
| Yes |
| 2 |
Open IE communication | |
| Yes |
| Yes |
| Yes |
Isochronous mode | |
Isochronous operation (application synchronized up to terminal) | Yes |
Equidistance | Yes |
shortest clock pulse | 250 µs |
max. cycle | 4 ms |
Interrupts/diagnostics/status information | |
Status indicator | Yes |
Alarms | Yes |
Diagnostic functions | Yes |
Diagnostics indication LED | |
| Yes; Green LED |
| Yes; Red LED |
| Yes; yellow LED |
| Yes; yellow LED |
Potential separation | |
between backplane bus and electronics | No |
between PROFINET and all other circuits | Yes |
between supply and all other circuits | No |
Permissible potential difference | |
between different circuits | 75 V DC/60 V AC (base isolation) |
Isolation | |
Isolation tested with | 707 V DC (type test) |
Ambient conditions | |
Ambient temperature during operation | |
| -40 °C; = Tmin; Startup @ -25 °C |
| 70 °C; = Tmax; ab > +60 °C no module permissible left of the IM |
| -40 °C; = Tmin |
| 40 °C; = Tmax |
Altitude during operation relating to sea level | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Relative humidity | |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Use in stationary industrial systems | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Dimensions | |
Width | 35 mm |
Height | 147 mm |
Depth | 129 mm |
Weights | |
Weight, approx. | 310 g |