Ex i input | |
Input signal | 0/4 ... 20 mA with HART |
Functional range | 0 ... 24 mA |
Max. input current for mA sources | 50 mA |
Transmitter supply voltage | ≥ 16 V at 20 mA (for 2-, 3-wire) |
Supply voltage residual ripple | ≤ 25 mVeff |
No-load voltage | ≤ 26 V |
Short-circuit current | ≤ 35 mA |
Input resistance (AC impedance HART) | ≈ 500 Ω |
Input resistance for mA sources | 30 О© |
Communication signal (for 2-wire transmitters) | Bidirectional HART transmission, 0.5 kHz ... 30 kHz |
Output | |
Output signal | 0/4 ... 20 mA with HART |
Load resistance RL | 0 ... 600 О© (terminal 1+/2-) 0 ... 379 О© (terminal 3+/2) (with internal 221 О© resistance for HART) |
Residual ripple | ≤ 40 μAeff |
No-load voltage | ≤ 15.5 V |
Communication signal | Bidirectional HART transmission, 0.5 kHz ... 30 kHz |
Settling time (10% ... 90%) | ≤ 25 ms |
Transmission characteristics Input/output | 1:1 0 ... 20 mA в†’ 0 ... 20 mA, 4 ... 20 mA в†’ 4 ... 20 mA |
Measuring accuracy Accuracy, typical data expressed as % of calibrated span at UN, 23 °C | |
Linearity error | ≤ 0.1% |
Offset error | ≤ 0.1% |
Temperature influence | ≤ 0.1%/10 K |
Power supply effect within voltage range | ≤ 0.01% |
Load resistance effect | ≤ 0.02% |
Rated conditions | |
Degree of protection of enclosure | IP30 |
Degree of protection of terminals | IP20 |
Ambient conditions | |
| -20 °C ... +60 °C/+70 °C (‑4 ... +140/+158 °F) (refer to Operating Instructions) |
| -40 °C ... +80 °C (‑40 ... +176 °F) |
- Relative humidity (no condensation)
| ≤ 95% |
Electromagnetic compatibility | Checked according to following standards and regulations: EN 61326-1 Use in the industrial environment |
Design | |
Screw terminals | |
| |
| 0.2 ... 2.5 mm2 (0.00031 ... 0.0039 in2) |
| 0.2 ... 2.5 mm2 (0.00031 ... 0.0039 in2) |
- Flexible with end ferrules (without/with plastic ferrule)
| 0.25 ... 2.5 mm2 (0.00039 ... 0.0039 in2) |
| |
| 0.2 ... 1 mm2 (0.00031 ... 0.00155 in2) |
| 0.2 ... 1.5 mm2 (0.00031 ... 0.0023 in2) |
- Flexible with end ferrules
| 0.25 ... 1 mm2 (0.00039 ... 0.00155 in2) |
Weight | Approx. 160 g (0.35 lb) |
Type of installation | On DIN rail according to EN 50022 (NS35/15; NS35/7.5) |
Mounting position | Vertical or horizontal |
Enclosure material | PA 6.6 |
Fire protecting class (UL-94) | V0 |
Auxiliary power | |
Rated voltage UN | 24 V DC |
Voltage range | 18 ... 31.2 V |
Residual ripple within voltage range | ≤ 3.6 VSS |
Rated current (UN, 20 mA) | 70 mA |
Power consumption (UN, 20 mA) | 1.7 W |
Power loss (at UN, RL = 250 О©) | 1.3 W |
Operation indicator | Green "PWR" LED |
Reverse polarity protection | Yes |
Undervoltage monitoring | Yes (no faulty module/output states) |
Electrical isolation | |
- Test voltage according to EN 60079-11
| |
- Ex intrinsic safety input to output
| 1.5 kV AC |
- Ex intrinsic safety input to auxiliary power
| 1.5 kV AC |
- Ex intrinsic safety input to fault signaling contact
| 1.5 kV AC |
- Test voltage according to EN 50178
| |
- Output to auxiliary power
| 350 V AC |
- Error contact to auxiliary power and output
| 350 V AC |
Error detection Ex i input | |
| < 2 mA |
| > 22 mA |
| = Input signal |
| IA = 0 mA |
Error detection output | |
| < 2 mA |
Error messaging Ex i input/output | |
| Activated/deactivated |
| Red "LF" LED |
Error messaging and power supply failure | - Contact (30 V/100 mA), closed to ground in event of fault
- pac-Bus, floating contact (30 V/100 mA)
|
Certificates and approvals | |
Explosion protection ATEX | |
- EC type-examination certificate
| DMT 03 ATEX E 010 X |
| II 3 (1) G Ex nA nC [ia] IIC T4 II (1) D [Ex iaD] |
Installation | In Zone 2, Div. 2 and in the safe area |
Other approvals | USA (FM) Canada (CSA) Marine (DNV) |
Safety specifications (CENELEC) | |
| 27 V |
| 88 mA |
| 576 mW |
- Max. connectable capacitance Co for IIC/IIB
| 90 nF/705 nF |
- Max. connectable inductance Lo for IIC/IIB
| 2.3 mH/14 mH |
- Internal capacitance Ci and inductance Li
| Negligible |
| 253 V |
- When connecting mA sources:
| |
| 4.1 V |
- Max. connectable voltage Ui
| 30 V |
- Max. connectable current Ii
| 100 mA |
- Internal capacitance Ci and inductance Li
| Negligible |
- Additional information and value combinations
| See Certifications |