Product type designation | F-DQ 4x24 V DC/2 A PM HF | F-DQ 8x24 V DC/0.5 A PP HF |
Firmware version | | |
| | Yes |
usable BaseUnits | | BU type A0 |
Color code for module-specific color identification plate | | CC02 |
Product function | | |
| Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 |
Engineering with | | |
| V12 | V14 SP1 with HSP 202 |
| V5.5 SP3 / - | Still being prepared |
| V2.31 | |
Supply voltage | | |
Rated value (DC) | 24 V | 24 V |
permissible range, lower limit (DC) | 20.4 V | 20.4 V |
permissible range, upper limit (DC) | 28.8 V | 28.8 V |
Reverse polarity protection | Yes | Yes |
Input current | | |
Current consumption (rated value) | 75 mA; without load | 75 mA; without load |
Current consumption, max. | 21 mA; From the backplane bus | 21 mA; From the backplane bus |
Output voltage | | |
Rated value (DC) | 24 V | 24 V |
Power | | |
Power available from the backplane bus | 70 mW | 70 mW |
Power loss | | |
Power loss, typ. | 4 W | 3 W |
Address area | | |
Address space per module | | |
| 5 byte | 6 byte; 5 bytes non-RIOforFA; 6 bytes RIOforFA |
| 5 byte | 6 byte; 5 bytes non-RIOforFA; 6 bytes RIOforFA |
Hardware configuration | | |
Automatic encoding | | |
| | Yes |
Digital outputs | | |
Number of digital outputs | 4 | 8 |
Short-circuit protection | Yes | Yes |
| > 3.3 A | Min. 0.7 A |
Open-circuit detection | Yes | No |
| 8 mA | |
Overload protection | Yes | |
| 2.9 A | |
Limitation of inductive shutdown voltage to | Typ. -2x 47 V | Typ. -39 V |
Controlling a digital input | | Yes |
Switching capacity of the outputs | | |
| 2 A | 0.5 A |
| 10 W | 2 W |
Load resistance range | | |
| 12 Ω | 48 Ω |
| 2 000 Ω | 12 000 Ω |
Output voltage | | |
| 24 V; L+ (-0.5 V) | 24 V; L+ (-0.5 V) |
Output current | | |
| 2 A | 0.5 A |
| 0.5 mA | 0.5 mA |
Switching frequency | | |
| 30 Hz; Symmetrical | 30 Hz; Symmetrical |
| 0.1 Hz; according to IEC 60947-5-1, DC-13, symmetrical | 0.1 Hz; according to IEC 60947-5-1, DC-13, symmetrical |
| | 2 Hz; Symmetrical |
| 10 Hz; Symmetrical | 10 Hz; Symmetrical |
Total current of the outputs | | |
| 2 A; Note derating data in the manual | 0.5 A; Note derating data in the manual |
| 6 A; Note derating data in the manual | 3 A; Note derating data in the manual |
Total current of the outputs (per module) | | |
horizontal installation | | |
| | 3 A |
| | 2.5 A |
| | 2 A |
vertical installation | | |
| | 2 A |
Cable length | | |
| 1 000 m | 100 m |
| 500 m | 100 m |
Interrupts/diagnostics/status information | | |
Diagnostics function | Yes, "Alarms/diagnostic messages" section in the manual | Yes, "Alarms/diagnostic messages" section in the manual |
Substitute values connectable | No | No |
Alarms | | |
| Yes | Yes |
Diagnostics indication LED | | |
| Yes; Green LED | Yes; Green LED |
| Yes; Red LED | Yes; Red LED |
| Yes; green PWR LED | Yes; green PWR LED |
| Yes; Green LED | Yes; Green LED |
| Yes; Red LED | Yes; Red LED |
| Yes; green/red DIAG LED | Yes; green/red DIAG LED |
Potential separation | | |
Potential separation channels | | |
| No | No |
| Yes | Yes |
| No | No |
Permissible potential difference | | |
between different circuits | 75 V DC/60 V AC | |
Isolation | | |
Isolation tested with | 707 V DC (type test) | 707 V DC (type test) |
Ambient conditions | | |
Ambient temperature during operation | | |
| 0 °C | 0 °C |
| 60 °C | 60 °C |
| 0 °C | 0 °C |
| 50 °C | 50 °C |
Dimensions | | |
Width | 15 mm | 15 mm |
Height | 73 mm | |
Depth | 58 mm | |
Weights | | |
Weight, approx. | 57 g | 48 g |