Article number

6AG1132-6BD20-7BA0

6AG1132-6BF00-7BA0

6AG1132-6BH00-7BA0

SIPLUS ET200SP DQ 4x24VDC/2A ST

SIPLUS ET 200SP DQ 8x24VDC/0,5A ST

SIPLUS ET 200SP DQ 16x24VDC/0,5A ST

General information

 

 

 

Product type designation

DQ 4x24VDC/2A ST

DQ 8x24VDC/0.5A ST

DQ 16x24VDC/0.5A ST

Redundancy

 

 

 

  • в—Џ Redundancy capability

Yes

Supply voltage

 

 

 

Rated value (DC)

24 V

24 V

24 V

permissible range, lower limit (DC)

19.2 V

19.2 V

19.2 V

permissible range, upper limit (DC)

28.8 V

28.8 V

28.8 V

Power loss

 

 

 

Power loss, typ.

1 W

1 W

1 W

Address area

 

 

 

Address space per module

 

 

 

  • в—Џ Address space per module, max.

32 byte

32 byte

32 byte

Digital outputs

 

 

 

Number of digital outputs

4; > +60 °C number of simultaneously controllable outputs max. 2 x 0.25 A or max. 4 x 0.125 A, max. total current 0.5 A

8; > +60 °C max. total current 1.0 A

16; > +60 °C max. total current 1.0 A

Current-sourcing

Yes

Short-circuit protection

Yes

  • в—Џ Response threshold, typ.

2.8 to 5.2 A

0.7 to 1.3 A

0.7 to 1.3 A

Limitation of inductive shutdown voltage to

Typ. L+ (-50 V)

Typ. L+ (-50 V)

Typ. L+ (-50 V)

Controlling a digital input

Yes

Yes

Yes

Switching capacity of the outputs

 

 

 

  • в—Џ with resistive load, max.

2 A

0.5 A

0.5 A

  • в—Џ on lamp load, max.

10 W

5 W

5 W

Load resistance range

 

 

 

  • в—Џ lower limit

12 в„¦

48 в„¦

48 в„¦

  • в—Џ upper limit

3 400 в„¦

12 kΩ

12 kΩ

Output current

 

 

 

  • в—Џ for signal "1" rated value

2 A

0.5 A

0.5 A

Output delay with resistive load

 

 

 

  • в—Џ "0" to "1", max.

50 µs

50 µs

50 µs

  • в—Џ "1" to "0", max.

100 µs

100 µs

100 µs

Parallel switching of two outputs

 

 

 

  • в—Џ for uprating

No

No

No

  • в—Џ for redundant control of a load

Yes

Yes

Yes

Switching frequency

 

 

 

  • в—Џ with resistive load, max.

100 Hz

100 Hz

100 Hz

  • в—Џ with inductive load, max.

2 Hz

2 Hz

2 Hz

  • в—Џ on lamp load, max.

10 Hz

10 Hz

10 Hz

Cable length

 

 

 

  • в—Џ shielded, max.

1 000 m

1 000 m

1 000 m

  • в—Џ unshielded, max.

200 m

200 m

200 m

Diagnostic messages

 

 

 

  • в—Џ Monitoring the supply voltage

Yes

Yes

Yes

  • в—Џ Wire-break

Yes

Yes

Yes

  • в—Џ Short-circuit

Yes

Yes

Yes

  • в—Џ Group error

Yes

Yes

Yes

Permissible potential difference

 

 

 

between different circuits

75 V DC/60 V AC

75 V DC/60 V AC

75 V DC/60 V AC

Isolation

 

 

 

Isolation tested with

707 V DC

707 V DC

707 V DC

Ambient conditions

 

 

 

Ambient temperature during operation

 

 

 

  • в—Џ horizontal installation, min.

-40 °C; = Tmin

-40 °C; = Tmin; Startup @ -25 °C

-40 °C; = Tmin

  • в—Џ horizontal installation, max.

70 °C; = Tmax; > +60 °C number of simultaneously controllable outputs max. 2 x 0.25 A or max. 4 x 0.125 A, max. total current 0.5 A

70 °C; = Tmax; > +60 °C max. total current 1.0 A

70 °C; = Tmax; > +60 °C max. total current 1.0 A

  • в—Џ vertical installation, min.

-40 °C; = Tmin

-40 °C; = Tmin; Startup @ -25 °C

-40 °C; = Tmin

  • в—Џ vertical installation, max.

50 °C; = Tmax

50 °C; = Tmax

50 °C; = Tmax

Altitude during operation relating to sea level

 

 

 

  • в—Џ Ambient air temperature-barometric pressure-altitude

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Relative humidity

 

 

 

  • в—Џ With condensation, tested in accordance with IEC 60068-2-38, max.

100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation

100 %; RH incl. condensation/frost (no commissioning under condensation conditions)

100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation

Use in stationary industrial systems

 

 

 

  • — to biologically active substances according to EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

  • — to chemically active substances according to EN 60721-3-3

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

  • — to mechanically active substances according to EN 60721-3-3

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Dimensions

 

 

 

Width

15 mm

15 mm

15 mm

Height

73 mm

73 mm

73 mm

Depth

58 mm

58 mm

58 mm

Weights

 

 

 

Weight, approx.

30 g

28 g

28 g


Article number

6AG1132-6BF00-7CA0

6AG1132-6GD50-2BA0

6AG1132-6HD00-7BB1

SIPLUS ET 200SP DQ 8X24VDC/0,5A HF

SIPLUS ET 200SP RQ 4X24VDC/2A CO ST

SIPLUS ET 200SP RQ 4x120VDC/230VAC/5A

General information

 

 

 

Product type designation

DQ 8x24VDC/0.5A HF

RQ 4x24VUC/2A CO ST

RQ 4x120 VDC … 230 VAC/5 A NO ST

Firmware version

V1.2

V1.0

  • в—Џ FW update possible

Yes

Yes

Yes

usable BaseUnits

BU type A0

BU type A0

BU type B0, B1

Color code for module-specific color identification plate

CC02

CC00

CC00

Product function

 

 

 

  • в—Џ I&M data

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Engineering with

 

 

 

  • в—Џ PROFIBUS as of GSD version/GSD revision

GSD Revision 5

GSD Revision 5

GSD Revision 5

  • в—Џ PROFINET as of GSD version/GSD revision

GSDML V2.3

GSDML V2.3

GSDML V2.3

Operating mode

 

 

 

  • в—Џ DQ

Yes

Yes

Yes

  • в—Џ DQ with energy-saving function

No

No

No

  • в—Џ PWM

No

No

No

  • в—Џ Oversampling

No

No

No

  • в—Џ MSO

Yes

No

No

Supply voltage

 

 

 

Rated value (DC)

24 V

24 V

24 V

permissible range, lower limit (DC)

19.2 V

19.2 V

19.2 V

permissible range, upper limit (DC)

28.8 V

28.8 V

28.8 V

Reverse polarity protection

Yes

Yes

Input current

 

 

 

Current consumption (rated value)

50 mA

Current consumption, max.

45 mA; without load

100 mA; without load

Output voltage

 

 

 

Rated value (DC)

24 V

Power loss

 

 

 

Power loss, typ.

1 W

1.2 W

1.5 W

Address area

 

 

 

Address space per module

 

 

 

  • в—Џ Address space per module, max.

1 byte; + 1 byte for QI information

1 byte; + 1 byte for QI information

1 byte; + 1 byte for QI information

  • в—Џ Inputs

1 byte; With QI

1 byte; With QI

  • в—Џ Outputs

1 byte

1 byte

Digital outputs

 

 

 

Type of digital output

Relays

Relays

Number of digital outputs

8

4

4

Current-sinking

No

Current-sourcing

Yes

Short-circuit protection

No

No

  • в—Џ Response threshold, typ.

0.7 to 1.3 A

Limitation of inductive shutdown voltage to

Typ. L+ (-50 V)

Controlling a digital input

Yes

Switching capacity of the outputs

 

 

 

  • в—Џ with resistive load, max.

0.5 A

  • в—Џ on lamp load, max.

5 W

Load resistance range

 

 

 

  • в—Џ lower limit

48 в„¦

  • в—Џ upper limit

12 kΩ

Output current

 

 

 

  • в—Џ for signal "1" rated value

0.5 A

  • в—Џ for signal "0" residual current, max.

0.1 mA

Output delay with resistive load

 

 

 

  • в—Џ "0" to "1", typ.

50 µs

  • в—Џ "1" to "0", typ.

100 µs

Parallel switching of two outputs

 

 

 

  • в—Џ for uprating

No

  • в—Џ for redundant control of a load

Yes

Switching frequency

 

 

 

  • в—Џ with resistive load, max.

100 Hz

2 Hz

2 Hz

  • в—Џ with inductive load, max.

2 Hz

0.5 Hz

  • в—Џ on lamp load, max.

10 Hz

2 Hz

Total current of the outputs

 

 

 

  • в—Џ Current per channel, max.

0.5 A

2 A

5 A

  • в—Џ Current per module, max.

4 A

8 A

20 A

Total current of the outputs (per module)

 

 

 

horizontal installation

 

 

 

  • — up to 60 °C, max.

4 A

8 A

20 A

vertical installation

 

 

 

  • — up to 60 °C, max.

4 A

8 A

20 A

Relay outputs

 

 

 

  • в—Џ Number of relay outputs

4

4

  • в—Џ Rated supply voltage of relay coil L+ (DC)

24 V

24 V

  • в—Џ Current consumption of relays (coil current of all relays), max.

40 mA

40 mA

  • в—Џ external protection for relay outputs

Yes, with 6A

  • в—Џ Number of operating cycles, max.

7 000 000; see additional description in the manual

Switching capacity of contacts

 

 

 

  • — with inductive load, max.

2 A; see additional description in the manual

  • — with resistive load, max.

2 A

5 A; see additional description in the manual

  • — Thermal continuous current, max.

2 A

5 A; Max. 1 385 VA, 150 W

  • — Switching current, min.

1 mA; 5 V DC

100 mA; 5 V DC

  • — Rated switching voltage (DC)

24 V

24 V DC to 120 V DC

  • — Rated switching voltage (AC)

24 V

24V AC to 230V AC

Cable length

 

 

 

  • в—Џ shielded, max.

1 000 m

1 000 m

1 000 m

  • в—Џ unshielded, max.

600 m

200 m

200 m

Isochronous mode

 

 

 

Isochronous operation (application synchronized up to terminal)

Yes

No

No

Execution and activation time (TCO), min.

48 µs

Bus cycle time (TDP), min.

500 µs

Interrupts/diagnostics/status information

 

 

 

Diagnostics function

Yes

Yes

Yes

Substitute values connectable

Yes

Yes

Yes

Alarms

 

 

 

  • в—Џ Diagnostic alarm

Yes

Yes

Yes

Diagnostic messages

 

 

 

  • в—Џ Monitoring the supply voltage

Yes

Yes

Yes

  • в—Џ Wire-break

Yes; channel by channel

No

No

  • в—Џ Short-circuit

Yes; channel by channel

No

No

  • в—Џ Group error

Yes

Yes

Yes

Diagnostics indication LED

 

 

 

  • в—Џ Monitoring of the supply voltage (PWR-LED)

Yes; green PWR LED

Yes; green PWR LED

Yes; green PWR LED

  • в—Џ Channel status display

Yes; Green LED

Yes; Green LED

Yes; Green LED

  • в—Џ for channel diagnostics

Yes; Red LED

No

No

  • в—Џ for module diagnostics

Yes; green/red DIAG LED

Yes; green/red DIAG LED

Yes; green/red DIAG LED

Potential separation

 

 

 

Potential separation channels

 

 

 

  • в—Џ between the channels

No

Yes

Yes

  • в—Џ between the channels and backplane bus

Yes

Yes

Yes

  • в—Џ between the channels and the power supply of the electronics

Yes

Yes

Permissible potential difference

 

 

 

between different circuits

75 V DC/60 V AC (base isolation)

75 V DC/60 V AC (base isolation)

between channels and backplane bus/supply voltage

240 V AC

Isolation

 

 

 

Isolation tested with

707 V DC (type test)

707 V DC (type test)

2 500 V DC (type test)

tested with

 

 

 

  • в—Џ between channels and backplane bus/supply voltage

2500 V DC

  • в—Џ between backplane bus and supply voltage

707 V DC (type test)

Ambient conditions

 

 

 

Ambient temperature during operation

 

 

 

  • в—Џ horizontal installation, min.

-40 °C; = Tmin

-40 °C; = Tmin; Startup @ -25 °C

-40 °C; = Tmin

  • в—Џ horizontal installation, max.

70 °C; = Tmax; > +60 °C max. total current 1.0 A

60 °C; = Tmax

70 °C; = Tmax; see Derating BasedOn (e.g. manual), additionally Tmax > 60 °C max. continuous current of 3 A per relay

  • в—Џ vertical installation, min.

-40 °C; = Tmin

  • в—Џ vertical installation, max.

50 °C; = Tmax

Altitude during operation relating to sea level

 

 

 

  • в—Џ Ambient air temperature-barometric pressure-altitude

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)

Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... Tmax -5K) at 795 hPa ... 701 hPa (+2 000 m ... +3 000 m)

Relative humidity

 

 

 

  • в—Џ With condensation, tested in accordance with IEC 60068-2-38, max.

100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation

100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation

100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation

Use in stationary industrial systems

 

 

 

  • — to biologically active substances according to EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

  • — to chemically active substances according to EN 60721-3-3

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

  • — to mechanically active substances according to EN 60721-3-3

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Dimensions

 

 

 

Width

15 mm

15 mm

20 mm

Height

73 mm

73 mm

Depth

58 mm

58 mm

Weights

 

 

 

Weight, approx.

30 g

30 g

40 g


Article number

6AG1132-6BD20-7CA0

SIPLUS ET 200SP DQ 4X24VDC/2A HF

General information

 

Product type designation

DQ 4x24 V DC/2 A HF

Firmware version

V1.0

  • в—Џ FW update possible

Yes

usable BaseUnits

BU type A0

Color code for module-specific color identification plate

CC02

Product function

 

  • в—Џ I&M data

Yes; I&M0 to I&M3

Engineering with

 

  • в—Џ PROFIBUS as of GSD version/GSD revision

GSD Revision 5

  • в—Џ PROFINET as of GSD version/GSD revision

GSDML V2.3

Operating mode

 

  • в—Џ Oversampling

No

Supply voltage

 

Rated value (DC)

24 V

permissible range, lower limit (DC)

19.2 V

permissible range, upper limit (DC)

28.8 V

Reverse polarity protection

Yes

Input current

 

Current consumption, max.

60 mA; without load

Power loss

 

Power loss, typ.

1 W

Address area

 

Address space per module

 

  • в—Џ Address space per module, max.

1 byte; + 1 byte for QI information

Isochronous mode

 

Isochronous operation (application synchronized up to terminal)

Yes

Bus cycle time (TDP), min.

500 µs

Jitter, max.

8 µs

Interrupts/diagnostics/status information

 

Diagnostics function

Yes

Substitute values connectable

Yes

Alarms

 

  • в—Џ Diagnostic alarm

Yes

Diagnostic messages

 

  • в—Џ Monitoring the supply voltage

Yes

  • в—Џ Wire-break

Yes; channel by channel

  • в—Џ Short-circuit

Yes; channel by channel

  • в—Џ Group error

Yes

Diagnostics indication LED

 

  • в—Џ Monitoring of the supply voltage (PWR-LED)

Yes; green PWR LED

  • в—Џ Channel status display

Yes; Green LED

  • в—Џ for channel diagnostics

Yes; Red LED

  • в—Џ for module diagnostics

Yes; green/red DIAG LED

Potential separation

 

Potential separation channels

 

  • в—Џ between the channels

No

  • в—Џ between the channels and backplane bus

Yes

Isolation

 

Isolation tested with

707 V DC (type test)

Ambient conditions

 

Ambient temperature during operation

 

  • в—Џ horizontal installation, min.

-40 °C; = Tmin

  • в—Џ horizontal installation, max.

70 °C; = Tmax; see Derating BasedOn (e.g. manual), additionally Tmax > 60 °C max. total current 1 A

Altitude during operation relating to sea level

 

  • в—Џ Ambient air temperature-barometric pressure-altitude

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Relative humidity

 

  • в—Џ With condensation, tested in accordance with IEC 60068-2-38, max.

100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation

Use in stationary industrial systems

 

  • — to biologically active substances according to EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

  • — to chemically active substances according to EN 60721-3-3

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

  • — to mechanically active substances according to EN 60721-3-3

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Dimensions

 

Width

15 mm

Height

73 mm

Depth

58 mm

Weights

 

Weight, approx.

30 g


















skener.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Арматура DENDOR

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Датчики и измерители

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Регуляторы и регистраторы

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Пневматическое оборудование

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Краны и Клапаны

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Измерительные приборы

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Системы беспроводного управления «умный дом»

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Бесконтактные выключатели Конечные выключатели Оптические датчики Энкодеры

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Установка умягчения

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Установка обезжелезивания
Каталог оборудования 2018
Siemens Industry Catalog Drive technology Automation technology Automation systems SIMATIC Industrial Automation Systems Controllers I/O systems SIMATIC ET 200 systems for the control cabinet SIMATIC ET 200SP Interface modules Central processing units I/O modules Digital input modules Digital output modules Analog input modules Analog output modules SIPLUS I/O modules SIPLUS digital inputs SIPLUS digital outputs SIPLUS analog inputs SIPLUS analog outputs Technology modules Communication Fail-safe I/O modules ET 200SP motor starters Pneumatic BaseUnits SIPLUS BaseUnits BusAdapters SIPLUS BusAdapters Accessories SIMATIC ET 200MP SIMATIC ET 200S SIMATIC ET 200M SIMATIC ET 200iSP SIMATIC ET 200 systems without control cabinet IO systems for heating elements PROFIBUS components PROFINET components Network components for PROFIBUS Network transitions SIMATIC control systems Software for SIMATIC Controllers Programming devices Siemens Partner Programm SIMOTION Motion Control System SINUMERIK CNC automation systems System cabling/control cabinets Operator control and monitoring systems SIMATIC HMI Identification systems Industrial communication Industrial controls Industry software PC-based Automation Process control systems Process instrumentation Process analytics SITOP power supply Products for specific requirements Energy Building Technologies Low-Voltage controls and distribution Safety Systems - Safety Integrated Market-specific solutions Industry Services Software ... and everything else you need




  © ООО "СК ЭНЕРГО" 2007-2022
  (4872) 700-366  skenergo@mail.ru
Яндекс.Метрика