General information | | | |
Product type designation | DQ 8x24VDC/0.5A HF | RQ 4x24VUC/2A CO ST | RQ 4x120 VDC … 230 VAC/5 A NO ST |
Firmware version | V1.2 | V1.0 | |
| Yes | Yes | Yes |
usable BaseUnits | BU type A0 | BU type A0 | BU type B0, B1 |
Color code for module-specific color identification plate | CC02 | CC00 | CC00 |
Product function | | | |
| Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 |
Engineering with | | | |
| GSD Revision 5 | GSD Revision 5 | GSD Revision 5 |
| GSDML V2.3 | GSDML V2.3 | GSDML V2.3 |
Operating mode | | | |
| Yes | Yes | Yes |
| No | No | No |
| No | No | No |
| No | No | No |
| Yes | No | No |
Supply voltage | | | |
Rated value (DC) | 24 V | 24 V | 24 V |
permissible range, lower limit (DC) | 19.2 V | 19.2 V | 19.2 V |
permissible range, upper limit (DC) | 28.8 V | 28.8 V | 28.8 V |
Reverse polarity protection | Yes | | Yes |
Input current | | | |
Current consumption (rated value) | | 50 mA | |
Current consumption, max. | 45 mA; without load | | 100 mA; without load |
Output voltage | | | |
Rated value (DC) | 24 V | | |
Power loss | | | |
Power loss, typ. | 1 W | 1.2 W | 1.5 W |
Address area | | | |
Address space per module | | | |
| 1 byte; + 1 byte for QI information | 1 byte; + 1 byte for QI information | 1 byte; + 1 byte for QI information |
| | 1 byte; With QI | 1 byte; With QI |
| | 1 byte | 1 byte |
Digital outputs | | | |
Type of digital output | | Relays | Relays |
Number of digital outputs | 8 | 4 | 4 |
Current-sinking | No | | |
Current-sourcing | Yes | | |
Short-circuit protection | | No | No |
| 0.7 to 1.3 A | | |
Limitation of inductive shutdown voltage to | Typ. L+ (-50 V) | | |
Controlling a digital input | Yes | | |
Switching capacity of the outputs | | | |
| 0.5 A | | |
| 5 W | | |
Load resistance range | | | |
| 48 Ω | | |
| 12 kΩ | | |
Output current | | | |
| 0.5 A | | |
| 0.1 mA | | |
Output delay with resistive load | | | |
| 50 µs | | |
| 100 µs | | |
Parallel switching of two outputs | | | |
| No | | |
| Yes | | |
Switching frequency | | | |
| 100 Hz | 2 Hz | 2 Hz |
| 2 Hz | | 0.5 Hz |
| 10 Hz | | 2 Hz |
Total current of the outputs | | | |
| 0.5 A | 2 A | 5 A |
| 4 A | 8 A | 20 A |
Total current of the outputs (per module) | | | |
horizontal installation | | | |
| 4 A | 8 A | 20 A |
vertical installation | | | |
| 4 A | 8 A | 20 A |
Relay outputs | | | |
| | 4 | 4 |
| | 24 V | 24 V |
| | 40 mA | 40 mA |
| | | Yes, with 6A |
| | | 7 000 000; see additional description in the manual |
Switching capacity of contacts | | | |
| | | 2 A; see additional description in the manual |
| | 2 A | 5 A; see additional description in the manual |
| | 2 A | 5 A; Max. 1 385 VA, 150 W |
| | 1 mA; 5 V DC | 100 mA; 5 V DC |
| | 24 V | 24 V DC to 120 V DC |
| | 24 V | 24V AC to 230V AC |
Cable length | | | |
| 1 000 m | 1 000 m | 1 000 m |
| 600 m | 200 m | 200 m |
Isochronous mode | | | |
Isochronous operation (application synchronized up to terminal) | Yes | No | No |
Execution and activation time (TCO), min. | 48 µs | | |
Bus cycle time (TDP), min. | 500 µs | | |
Interrupts/diagnostics/status information | | | |
Diagnostics function | Yes | Yes | Yes |
Substitute values connectable | Yes | Yes | Yes |
Alarms | | | |
| Yes | Yes | Yes |
Diagnostic messages | | | |
| Yes | Yes | Yes |
| Yes; channel by channel | No | No |
| Yes; channel by channel | No | No |
| Yes | Yes | Yes |
Diagnostics indication LED | | | |
| Yes; green PWR LED | Yes; green PWR LED | Yes; green PWR LED |
| Yes; Green LED | Yes; Green LED | Yes; Green LED |
| Yes; Red LED | No | No |
| Yes; green/red DIAG LED | Yes; green/red DIAG LED | Yes; green/red DIAG LED |
Potential separation | | | |
Potential separation channels | | | |
| No | Yes | Yes |
| Yes | Yes | Yes |
| | Yes | Yes |
Permissible potential difference | | | |
between different circuits | 75 V DC/60 V AC (base isolation) | 75 V DC/60 V AC (base isolation) | |
between channels and backplane bus/supply voltage | | | 240 V AC |
Isolation | | | |
Isolation tested with | 707 V DC (type test) | 707 V DC (type test) | 2 500 V DC (type test) |
tested with | | | |
| | | 2500 V DC |
| | | 707 V DC (type test) |
Ambient conditions | | | |
Ambient temperature during operation | | | |
| -40 °C; = Tmin | -40 °C; = Tmin; Startup @ -25 °C | -40 °C; = Tmin |
| 70 °C; = Tmax; > +60 °C max. total current 1.0 A | 60 °C; = Tmax | 70 °C; = Tmax; see Derating BasedOn (e.g. manual), additionally Tmax > 60 °C max. continuous current of 3 A per relay |
| -40 °C; = Tmin | | |
| 50 °C; = Tmax | | |
Altitude during operation relating to sea level | | | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) | Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... Tmax -5K) at 795 hPa ... 701 hPa (+2 000 m ... +3 000 m) |
Relative humidity | | | |
| 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation | 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation | 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation |
Use in stationary industrial systems | | | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Dimensions | | | |
Width | 15 mm | 15 mm | 20 mm |
Height | | 73 mm | 73 mm |
Depth | | 58 mm | 58 mm |
Weights | | | |
Weight, approx. | 30 g | 30 g | 40 g |