General information | | | | | |
Product type designation | DQ 8x24VDC/2A HF | DQ 16x24VDC/0.5A HF | DQ 32x24VDC/0.5A HF | DQ 8x230 V AC/5 A ST (relay) | DQ 8x230 V AC/2A ST (triac) |
Firmware version | | | | | |
| | Yes | | | |
Product function | | | | | |
| Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 |
Operating mode | | | | | |
| | Yes | Yes | | |
| | No | | | |
| | No | | | |
| | No | | | |
| | Yes | Yes | Yes | |
Supply voltage | | | | | |
Rated value (DC) | 24 V | 24 V | 24 V | 24 V | |
permissible range, lower limit (DC) | 20.4 V | 20.4 V | 20.4 V | 20.4 V | |
permissible range, upper limit (DC) | 28.8 V | 28.8 V | 28.8 V | 28.8 V | |
Reverse polarity protection | | Yes; through internal protection with 7 A per group | Yes; through internal protection with 7 A per group | | |
Input current | | | | | |
Current consumption, max. | 40 mA; 20 mA per group, no output is activated. | 30 mA | 60 mA | 80 mA | |
Output voltage | | | | | |
Rated value (DC) | | 24 V | 24 V | | |
Rated value (AC) | | | | | 120/230 V AC, 50/60 Hz |
Power | | | | | |
Power available from the backplane bus | 0.9 W | 1.1 W | 1.1 W | 0.8 W | 0.9 W |
Power loss | | | | | |
Power loss, typ. | 5.6 W | 2 W | 3.5 W | 3 W | 10.8 W |
Digital outputs | | | | | |
Type of digital output | Transistor | Transistor | Transistor | Relays | Triac |
Number of digital outputs | 8; > +60 °C Number of simultaneously controllable outputs max. 8x 0.5 A, max. total current per group 2 A | 16 | 32 | 8 | 8; > +60 °C number of simultaneously controllable outputs max. 8x 0.25 A, max. total current 2 A |
Current-sourcing | | Yes | Yes | | |
Short-circuit protection | Yes | Yes; Clocked electronically | Yes; Clocked electronically | | |
| 3 A | 1 A | 1 A | | |
Limitation of inductive shutdown voltage to | -17 V | L+ (-53 V) | L+ (-53 V) | | |
Controlling a digital input | | Yes | Yes | possible | |
Switching capacity of the outputs | | | | | |
| 2 A | 0.5 A | 0.5 A | | 2 A |
| 10 W | 5 W | 5 W | 1 500 W; 10 000 operating cycles | 50 W |
| | | | 10x 58 W (25 000 operating cycles) | |
| | | | 1x 58 W (25 000 operating cycles) | |
| | | | 10x 58 W (25 000 operating cycles) | |
Load resistance range | | | | | |
| 12 Ω | 48 Ω | 48 Ω | | |
| 4 kΩ | 12 kΩ | 12 kΩ | | |
Output voltage | | | | | |
| L+ (-0.8 V) | L+ (-0.8 V) | L+ (-0.8 V) | | L1 (-1.5 V) at maximum output current; L1 (-8.5 V) at minimum output current |
Output current | | | | | |
| 2 A | 0.5 A | 0.5 A | 5 A | 2 A |
| | | | 5 mA; 10 V | 10 mA |
| 2.4 A | 0.5 A | 0.5 A | 8 A; thermal continuous current | 15 A; max. 1 AC cycle |
| 0.5 mA | 0.5 mA | 0.5 mA | 0 A | 2 mA |
Output delay with resistive load | | | | | |
| 100 µs | 100 µs | 100 µs | | 1 AC cycle |
| 500 µs | 500 µs | 500 µs | | 1 AC cycle |
Parallel switching of two outputs | | | | | |
| Yes | Yes | Yes | Yes | No |
| No | No | No | No | No |
| Yes | Yes | Yes | Yes | Yes |
Switching frequency | | | | | |
| 100 Hz | 100 Hz | 100 Hz | 2 Hz | 10 Hz |
| 0.5 Hz; According to IEC 60947-5-1, DC-13 | 0.5 Hz; According to IEC 60947-5-1, DC-13 | 0.5 Hz; According to IEC 60947-5-1, DC-13 | 0.5 Hz | 0.5 Hz |
| 10 Hz | 10 Hz | 10 Hz | 2 Hz | 1 Hz |
Total current of the outputs | | | | | |
| 2 A; Note derating data in the manual | 0.5 A; see additional description in the manual | 0.5 A; see additional description in the manual | 8 A; Note derating data in the manual | 2 A; = Tmax; > +60 °C number of simultaneously controllable outputs max. 8x 0.25 A, max. total current per group 2 A |
| 8 A; Note derating data in the manual | 4 A; see additional description in the manual | 4 A; see additional description in the manual | 8 A; Note derating data in the manual | 2 A; = Tmax; > +60 °C number of simultaneously controllable outputs max. 8x 0.25 A, max. total current per group 2 A |
| 16 A; Note derating data in the manual | 8 A; see additional description in the manual | 16 A; see additional description in the manual | 64 A; Note derating data in the manual | 10 A; = Tmax; > +60 °C number of simultaneously controllable outputs max. 8x 0.25 A, max. total current per group 2 A |
Relay outputs | | | | | |
| | | | 8 | |
| | | | 24 V | |
| | | | 80 mA | |
| | | | With miniature circuit breaker with characteristic B for: cos П† 1.0: 600 A cos П† 0.5 ... 0.7: 900 A with 8 A Diazed fuse: 1000 A | |
| | | | No | |
| | | | 5 | 5 |
| | | | 4 000 000; see additional description in the manual | |
| | | | Yes; 250 V AC/5 A g.p.; 120 V AC TV-4 tungsten; A300, R300 | |
Switching capacity of contacts | | | | | |
| | | | see additional description in the manual | |
| | | | see additional description in the manual | |
Triac outputs | | | | | |
| | | | | 5 |
Cable length | | | | | |
| 1 000 m | 1 000 m | 1 000 m | 1 000 m | 1 000 m |
| 600 m | 600 m | 600 m | 600 m | 600 m |
Isochronous mode | | | | | |
Isochronous operation (application synchronized up to terminal) | No | Yes | Yes | No | No |
Execution and activation time (TCO), min. | | 70 µs | 70 µs | | |
Bus cycle time (TDP), min. | | 250 µs | 250 µs | | |
Interrupts/diagnostics/status information | | | | | |
Diagnostics function | Yes | Yes | Yes | Yes | No |
Substitute values connectable | Yes | Yes | Yes | Yes | Yes |
Alarms | | | | | |
| Yes | Yes | Yes | Yes | No |
Diagnostic messages | | | | | |
| Yes | Yes | Yes | Yes | No |
| No | Yes | Yes | No | No |
| Yes | Yes | Yes | No | No |
| | Yes | Yes | | |
| No | | | | No |
Diagnostics indication LED | | | | | |
| Yes; Green LED | Yes; Green LED | Yes; Green LED | Yes; Green LED | Yes; Green LED |
| Yes; Red LED | Yes; Red LED | Yes; Red LED | Yes; Red LED | Yes; Red LED |
| Yes; Green LED | Yes; Green LED | Yes; Green LED | Yes; Green LED | No |
| Yes; Green LED | Yes; Green LED | Yes; Green LED | Yes; Green LED | Yes; Green LED |
| Yes; Red LED | Yes; Red LED | Yes; Red LED | No | No |
| Yes; Red LED | Yes; Red LED | Yes; Red LED | Yes; Red LED | Yes; Red LED |
Potential separation | | | | | |
Potential separation channels | | | | | |
| Yes | No | No | Yes; Switching of different phases permitted | Yes |
| 4 | 8 | 8 | 1 | 1 |
| Yes | Yes | Yes | Yes | Yes |
| | | | Yes | |
| | | | | Yes |
Permissible potential difference | | | | | |
between different circuits | 75 V DC/60 V AC | | | 75 V DC/60 V AC (base isolation) between backplane bus and the supply voltage L+; 250 V AC between the channels and the supply voltage L+; 250 V AC between the channels and the backplane bus; 500 V AC between the channels | 250 V AC between the channels and the backplane bus; 500 V AC between the channels |
Isolation | | | | | |
Isolation tested with | 707 V DC (type test) | 707 V DC (type test) | 707 V DC (type test) | Between the channels: 2 500 V DC; between the channels and backplane bus: 2 500 V DC; between L+ backplane bus 707 V DC (type test) | 2500 V DC |
Ambient conditions | | | | | |
Ambient temperature during operation | | | | | |
| -40 °C; = Tmin | -40 °C; = Tmin | -40 °C; = Tmin | -25 °C; = Tmin | -40 °C; = Tmin |
| 70 °C; = Tmax; > +60 °C Number of simultaneously controllable outputs max. 8x 0.5 A, max. total current per group 2 A | 70 °C; = Tmax; see Derating BasedOn (e.g. manual), additionally Tmax > 60 °C max. aggregate current 2 A per group | 70 °C; = Tmax; see Derating BasedOn (e.g. manual), additionally Tmax > 60 °C max. aggregate current 2 A per group | 60 °C; = Tmax | 70 °C; = Tmax; > +60 °C number of simultaneously controllable outputs max. 8x 0.25 A, max. total current 2 A |
| -40 °C; = Tmin | | | -25 °C; = Tmin | -40 °C; = Tmin |
| 40 °C; = Tmax | | | 40 °C; = Tmax | 40 °C; = Tmax |
Altitude during operation relating to sea level | | | | | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) |
Relative humidity | | | | | |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation | 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Use in stationary industrial systems | | | | | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Decentralized operation | | | | | |
Fast Startup supported | Yes; 500 ms | | | Yes; 500 ms | Yes; 500 ms |
Prioritized startup | | Yes | Yes | | |
Dimensions | | | | | |
Width | 35 mm | 35 mm | 35 mm | 35 mm | 35 mm |
Height | 147 mm | 147 mm | 147 mm | 147 mm | 147 mm |
Depth | 129 mm | 129 mm | 129 mm | 129 mm | 129 mm |
Weights | | | | | |
Weight, approx. | 240 g | 230 g | 280 g | 200 g | 290 g |