- Two separate interfaces (integrated network separation):
- Gigabit interface with one RJ45 port with 10/100/1000 Mbps, full/half-duplex with auto-sensing functionality
- PROFINET interface with four RJ45 ports with 10/100 Mbps full/half duplex with autosensing and autocrossover functionality via integrated 4-port switch
- Communication services via both interfaces:
- Open communication (TCP/IP and UDP):
Multicast with UDP, including routing between both interfaces - PG/OP communication: Inter-network with S7 routing
- S7 communication (client, server, multiplexing) including routing between both interfaces
- S7 H communication for S7-400 H systems, now also across network boundaries (ISO-on-TCP)
- IT communication:
HTTP communication permits access to process data via user's own Web pages. HTTPS communication is also possible with the CP 443-1 Advanced1). The e-mail client function allows e-mails to be sent directly from the user program. FTP communication allows program-controlled FTP client communication. Access to data blocks via FTP server.
- Communication services via PROFINET interfaces:
- Certified PROFINET IO controller with real-time properties (RT and IRT)
- PROFINET CBA
- IP address assignment via DHCP, simple PC tool or via user program (e.g. for HMI)
- Media redundancy (MRP):
- Within an Ethernet network with ring topology, the CP supports the MRP media redundancy protocol as an MRP manager and as an MRP client
- Diagnostics and network management:
- Comprehensive diagnostics functions for all modules in the rack (including graphical diagnostics, e.g. topology)
- Integration in network management systems due to support of SNMP V1/V3
- Security mechanisms:
- Access protection by means of configurable IP access list
- Firewall for filtering connections on the basis of their IP/port addresses
- Bandwidth limitation to avoid communication overload
- VPN server and VPN client for tap-proof access to controllers
- Encrypted HTML pages using SSL (HTTPs)
- Secure file transfer (FTPs)
- Tap-proof transfer of network analysis information to the network management system (SNMP)
- Translation of private and public IP addresses (NAT/NAPT)
- Secure transfer of the time of day (NTP V3)
- Secure firmware update
- Plagiarism detection
- Certification as per the Achilles Level II Standard
http://www.wurldtech.com/product_services/certifications/certified_products/
- Configuration of all functions with STEP 7;
The security functions are configured using the Security Configuration Tool (SCT) included in the scope of delivery for STEP 7 V5.5 SP2 HF1. - Configuration with STEP 7 Professional V11;
only possible with a limited range of functions of the predecessor CP 443-1 (6GK7 443-1GX20-0XE0), without security functions and CBA. Version with security functions for TIA Portal in the planning stages. - When using the blocks AG_SSEND (FC53), AG_SRECV (FC63), TSEND (FB63), TRCV (FB64), TCON (FB65) and TDISCON (FB66), please note the following information: http://support.automation.siemens.com/WW/view/en/60037071
- Module replacement without programming device:
All information is stored on the C-PLUG (as well as file system for IT functions) - Note: For communication via Modbus TCP, please observe the information at the following link https://support.industry.siemens.com/cs/ww/en/view/22660304
|
|