General information | | | | |
Product type designation | DQ 8x230 V AC/5 A ST (relay) | DQ 16x 230 V AC/2 A ST (relay) | DQ 8x230 V AC/2A ST (triac) | DQ 16x230VAC/1A ST (Triac) |
HW functional status | FS01 | FS01 | FS01 | FS01 |
Firmware version | V2.0.0 | V1.0.0 | V2.0.0 | V1.0.0 |
| Yes | Yes | Yes | Yes |
Product function | | | | |
| Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 |
Engineering with | | | | |
| V12 / V12 | V13 SP1 / - | V12 / V12 | V13 SP1 / - |
| V5.5 SP3 / - | V5.5 SP3 / - | V5.5 SP3 / - | V5.5 SP3 / - |
| V1.0 / V5.1 | V1.0 / V5.1 | V1.0 / V5.1 | V1.0 / V5.1 |
| V2.3 / - | V2.3 / - | V2.3 / - | V2.3 / - |
Operating mode | | | | |
| Yes | Yes | Yes | Yes |
| No | No | No | No |
| No | No | No | No |
| No | No | No | No |
| Yes | Yes | Yes | Yes |
Supply voltage | | | | |
Rated value (DC) | 24 V | 24 V | | |
permissible range, lower limit (DC) | 20.4 V | 20.4 V | | |
permissible range, upper limit (DC) | 28.8 V | 28.8 V | | |
Reverse polarity protection | Yes | Yes | | |
Input current | | | | |
Current consumption, max. | 80 mA | 150 mA | | |
Output voltage | | | | |
Rated value (AC) | 230 V; 24 V DC to 120 V DC / 24 V AC to 230 V AC | 230 V; 24 V DC to 120 V DC / 24 V AC to 230 V AC | 230 V; 120/230 V AC, 50/60 Hz | 230 V; 120/230 V AC, 50/60 Hz |
Power | | | | |
Power available from the backplane bus | 0.8 W | 0.8 W | 0.9 W | 1.2 W |
Power loss | | | | |
Power loss, typ. | 5 W | 5 W | 10.8 W | 11.1 W |
Digital outputs | | | | |
Type of digital output | Relays | Relays | Triac | Triac |
Number of digital outputs | 8 | 16 | 8 | 16 |
Current-sinking | Yes | Yes | | Yes |
Current-sourcing | Yes | Yes | Yes | Yes |
Short-circuit protection | No | No | No | No |
Controlling a digital input | possible | Yes | | |
Switching capacity of the outputs | | | | |
| | | 2 A | 1 A |
| 1 500 W; 10 000 operating cycles | 50 W (230 V AC), 5 W (24 V DC) | 50 W | 50 W |
| 10x 58 W (25 000 operating cycles) | | | |
| 1x 58 W (25 000 operating cycles) | | | |
| 10x 58 W (25 000 operating cycles) | | | |
Output voltage | | | | |
| | | L1 (-1.5 V) at maximum output current; L1 (-8.5 V) at minimum output current | L1 (-1.5 V) at maximum output current; L1 (-8.5 V) at minimum output current |
Output current | | | | |
| 5 A | 2 A | 2 A | 1 A |
| 5 mA; 10 V | 10 mA; 10 V | 10 mA | 10 mA |
| 8 A; thermal continuous current | 2 A; thermal continuous current | 15 A; max. 1 AC cycle | 15 A; max. 1 AC cycle |
| 0 A | 0 A | 2 mA | 2 mA |
Output delay with resistive load | | | | |
| | | 1 AC cycle | 1 AC cycle |
| | | 1 AC cycle | 1 AC cycle |
Parallel switching of two outputs | | | | |
| Yes | Yes | No | No |
| No | No | No | No |
| Yes | Yes | Yes | Yes |
Switching frequency | | | | |
| 2 Hz | 1 Hz | 10 Hz | 10 Hz |
| 0.5 Hz | 0.5 Hz | 0.5 Hz | 0.5 Hz |
| 2 Hz | 1 Hz | 1 Hz | 1 Hz |
Total current of the outputs | | | | |
| 8 A; see additional description in the manual | 2 A; see additional description in the manual | 2 A; see additional description in the manual | 1 A; see additional description in the manual |
| 8 A; see additional description in the manual | 4 A; see additional description in the manual | 2 A; see additional description in the manual | 2 A; see additional description in the manual |
| 64 A; see additional description in the manual | 32 A; see additional description in the manual | 10 A; see additional description in the manual | 10 A; see additional description in the manual |
Relay outputs | | | | |
| 8 | 16 | | |
| 24 V | 24 V | | |
| 80 mA | 150 mA | | |
| With miniature circuit breaker with characteristic B for: cos П† 1.0: 600 A cos П† 0.5 ... 0.7: 900 A with 8 A Diazed fuse: 1000 A | Miniature circuit breaker B10 / B16 | | |
| No | No | | |
| 5 | 5 | | |
| 4 000 000; see additional description in the manual | see additional description in the manual | | |
| Yes; 250 V AC/5 A g.p.; 120 V AC TV-4 tungsten; A300, R300 | No | | |
Switching capacity of contacts | | | | |
| see additional description in the manual | 2 A; see additional description in the manual | | |
| see additional description in the manual | 2 A; see additional description in the manual | | |
Triac outputs | | | | |
| | | 5 | 4 |
Cable length | | | | |
| 1 000 m | 1 000 m | 1 000 m | 1 000 m |
| 600 m | 600 m | 600 m | 600 m |
Isochronous mode | | | | |
Isochronous operation (application synchronized up to terminal) | No | No | No | No |
Interrupts/diagnostics/status information | | | | |
Diagnostics function | Yes | Yes | No | No |
Substitute values connectable | Yes | Yes | Yes | Yes |
Alarms | | | | |
| Yes | Yes | No | No |
Diagnostic messages | | | | |
| Yes | Yes | No | No |
| No | No | No | No |
| No | No | No | No |
Diagnostics indication LED | | | | |
| Yes; Green LED | Yes; Green LED | Yes; Green LED | Yes; Green LED |
| Yes; Red LED | Yes; Red LED | Yes; Red LED | Yes; Red LED |
| Yes; Green LED | Yes; Green LED | No | No |
| Yes; Green LED | Yes; Green LED | Yes; Green LED | Yes; Green LED |
| No | No | No | No |
| Yes; Red LED | Yes; Red LED | Yes; Red LED | Yes; Red LED |
Potential separation | | | | |
Potential separation channels | | | | |
| Yes; Switching of different phases permitted | No | Yes | No |
| 1 | 2 | 1 | 2 |
| Yes | Yes | Yes | Yes |
| Yes | Yes | | |
| | | Yes | |
Permissible potential difference | | | | |
between different circuits | 250 V AC between the channels and the supply voltage L+; 250 V AC between the channels and the backplane bus; 500 V AC between the channels | 250 V AC between the channels and the supply voltage L+; 250 V AC between the channels and the backplane bus; 500 V AC between the channels | 250 V AC between the channels and the backplane bus; 500 V AC between the channels | 250 V AC between the channels and the backplane bus; 500 V AC between the channels |
Isolation | | | | |
Isolation tested with | Between channels: 3 100 V DC; between channels backplane bus: 3 100 V DC; between L+ and backplane bus: 707 V DC (type test) | Between channels: 3 100 V DC; between channels backplane bus: 3 100 V DC; between L+ and backplane bus: 707 V DC (type test) | 3 100 V DC | 3 100 V DC |
Ambient conditions | | | | |
Ambient temperature during operation | | | | |
| 0 °C | 0 °C | 0 °C | 0 °C |
| 60 °C | 60 °C | 60 °C | 60 °C |
| 0 °C | 0 °C | 0 °C | 0 °C |
| 40 °C | 40 °C | 40 °C | 60 °C |
Decentralized operation | | | | |
Prioritized startup | Yes | Yes | Yes | Yes |
Dimensions | | | | |
Width | 35 mm | 35 mm | 35 mm | 35 mm |
Height | 147 mm | 147 mm | 147 mm | 147 mm |
Depth | 129 mm | 129 mm | 129 mm | 129 mm |
Weights | | | | |
Weight, approx. | 350 g | 350 g | 290 g | 310 g |