Feature | Comment |
Connection macros and application macros | Sets groups of parameters to simplify commissioning - Connection macros for connections
- Application macros for application
|
Keep running mode | Single-parameter setting for a mode which keeps the motor going – enables VDC max controller, kinetic buffering, restart after fault, flying start, disables warnings etc. |
ECO mode | Economy mode – searches for most efficient operating point |
Hibernation mode | Converter shuts down automatically when “nothing to do” but starts up again automatically when there is “something to do”. |
PID controller | Integrated PID controller with auto-tuning function |
Kinetic buffering (Vdcmin controller) | Keep the minimal DC voltage by the regeneration energy to keep running |
Vdcmax controller | Auto change the ramp down time / decelerate time |
Imax controller | Auto change the ramp up time to avoid the over-current |
Automatic restart | Automatically restart the drive automatically once the power has been restored following a power failure. All faults are acknowledged automatically and the drive is switched on again. |
Flying restart | Allows the converter to be switched to a rotating motor. |
Energy consumption monitoring | Display simple estimate of “energy or cost saved” against use of a mains connected motor |
50/60 Hz customization | Easy selection of 50 Hz (Europe, China) / 60 Hz (USA) operation |
V/f and V2/f | V/f control is perfectly suitable for almost any application in which the speed of induction motors is to be changed. V2/f is suitable for centrifugal fans/pumps. |
FCC | Maintains motor flux current for improved efficiency |
Programmable V/f coordinates | Freely adjust the V/f characteristics, e.g. torque behavior of the synchronous motor |
JOG | Move the motor to test the direction or move the load to specific position. If the BOP switches to the JOG mode, the pressing of the start button of the BOP will run the motor to the JOG frequency. The releasing the start button will stop the motor. |
DC braking | Stop the motor which runs at the constant speed and only is broken down to standstill in longer time intervals, e.g. centrifuges, saws, grinding machines and conveyor belts. |
Mechanical hold braking control | The motor holding brake prevents the motor from undesirable turning when the converter is switched off. The converter has internal logic to control a motor holding brake. |
USS | Universal Serial Interface Protocol |
Modbus RTU | Modbus RTU communication available of the RS485 link |
Super torque mode | Big torque boost for starting high-inertia applications |
Hammer start mode | A number of torque pulses at start to start difficult or “stuck” loads |
Blockage clearing mode | Multiple-reverse function to clear blocked pumps |
Simple parameter-based menu on internal and external BOPs | Easy selection for displaying values, editing parameters, doing converter setup |
Simple text menu for setup | The parameter number will be shown as the short text in 7-segment LED display. |
Motor frequency display scaling | User settable display scaling for special applications i.e. rather than show Hz, it shows application-specific value like “gallons per minute”, “potatoes per hour”, etc. |
Customization of parameter defaults | Customer or OEM can set his own special “unerasable” defaults (can be erased in a special mode) |
Converter status at fault | Record the fault with running data - Fault code
- Drive setpoint
- Drive status
- DC link voltage
- Output current
- Output voltage
|
List of modified parameters | The parameter list only displays the parameters which were modified by users after this filter has been activated. |
Belt-failure detection | Detect the load torque to avoid the failure between the mechanical connection between the motor, overload, locking or no-load operation. |
Phase loss detection | Detect and protect against phase loss |
Cavitation protection | Protection from cavitation damage to pumps |
Condensation protection | Automatically apply DC current to motor to protect from condensation |
Frost protection | Automatically turns motor to stop fluids freezing when temperature falls near or below freezing. |
Motor staging | Automatic control and staging of several motors |
Dual ramp | Switchable ramps for certain applications |
Programmable fixed frequency setpoint | 16 fixed frequencies can be defined and be switched by the digital inputs or the communication. |
Drive data sets (DDS) | 3 parameter sets for the motor and load, The user can switch the parameter set to fit the motors and applications. |
Command data sets (CDS) | 3 parameter sets for the setpoint and command. The user can switch the parameter set to fit the control system. |
Flexible boost control | Increase the output voltage to compensate resistive losses or increase the output torque. |
Skippable frequency bandwidth | Define 1 to 4 frequencies, which avoid effects of mechanical resonance and suppress frequencies within adjustable skip frequency bandwidth. |
2-wire / 3-wire control | The wide range of setting options is especially intended to be able to emulate existing control methods on the plant or system side if the converter has to be integrated into an existing application. |