Flowmeter SITRANS FC430 | |
Sizes | DN 15 (Ѕ") DN 25 (1") DN 50 (2") DN 80 (3") DN 100 (4") DN 150 (6") |
Accuracy | ± 0.10 % |
Repeatability | ± 0.05 % |
Flow range (water @ 1 bar pressure loss) (Qnom) | |
| 3 700 kg/h (8 157 lb/h) |
| 11 500 kg/h (25 353 lb/h) |
| 52 000 kg/h (114 640 lb/h) |
| 136 000 kg/h (300 000 lb/h) |
| 285 800 kg/h (630 081 lb/h) |
| 492 200 kg/h (1 012 362 lb/h) |
Architecture | Compact or remote configuration |
Display | Full graphical display, 240 x 160 pixels with selection of 6 languages |
Power Supply | 20 ... 27 V DC ± 10%; 100 ... 240 V AC ± 10 %, 47 ... 63 Hz ± 10% |
Weight | 4.6 ... 212 kg |
Materials | |
| |
| 316L stainless steel or Hastelloy C22 |
| 304 stainless steel |
| Aluminum with corrosion-resistant coating |
Enclosure rating (IP) | IP67 |
Pressure ratings | |
| |
| 100 bar (1450 psi) |
| 160 bar (2321 psi) |
| 20 bar (DN15, DN25) 17 bar (DN50, DN80) 0 bar (DN 100, DN 150) |
- Sensor enclosure burst pressure
| > 160 bar (all sizes) |
Temperature ratings | |
| |
| -50 ... 200 °C (-58 ... +392 °F) |
| -50 ... 205 °C (-58 ... +400 °F) |
| -40 ... 60 °C (-40 ... +140 °F)1) |
| -20 ... 60 °C (-4 ... +140 °F) |
Process connections | |
| EN 1092-1 B1, EN 1092-1 D, ANSI/ASME B16.5, JIS B 2220, DIN 11864-2 |
| ASME B1.20 (NPT), ISO228-1 G (BSPP), VCO Quick-connect |
| DIN 11851, DIN 11864-1A, ISO 2853, SMS 1145 |
| DIN 11864-3A, DIN 32676, ISO 2852 |
Approvals | |
| ATEX, IECEx, EAC Ex, FM, NEPSI, CSA, cCSA us, INMETRO |
| PED, CRN |
| 3A, EHEDG |
| OIML R 117, NTEP |
- Operational safety2) (compact system only)
| SIL 2 Single SIL 3 Redundant system |
NAMUR | NAMUR-compliant (e.g. NE 21, NE 41, NE 107 and NE 132) |
I/O | Up to 4 channels combining analog, relay or digital outputs and binary input |
Communication | HART PROFIBUS PA PROFIBUS DP Modbus RTU (RS 485) |
EMC performance | |
| EN 55011/CISPR-11 (Class A) |
| EN/IEC 61326-1 (Industry) |
Mechanical load | 18 to 400 Hz random The flow meter will mechanically tolerate 3.17 g RMS in all directions. Flow accuracy cannot be guaranteed under all conditions. |