Article number

6GK5792-4DN00-0AA6

CPU416-5H PN/DP, 16MB F. S7-400H/F/FH

General information

 

Product type designation

CPU 416-5H PN/DP

HW functional status

1

Firmware version

V6.0

Engineering with

 

  • в—Џ Programming package

As of STEP 7 V5.5 SP2 with HF1

CiR – Configuration in RUN

 

CiR synchronization time, basic load

100 ms

CiR synchronization time, time per I/O byte

0 µs

Supply voltage

 

Rated value (DC)

  • в—Џ 24 V DC

No; Power supply via system power supply

Input current

 

from backplane bus 5 V DC, typ.

1.6 A

from backplane bus 5 V DC, max.

1.9 A

from backplane bus 24 V DC, max.

150 mA; 150 mA per DP interface

from interface 5 V DC, max.

90 mA; At each DP interface

Power loss

 

Power loss, typ.

7.5 W

Memory

 

Type of memory

other

Work memory

 

  • в—Џ integrated

16 Mbyte

  • в—Џ integrated (for program)

6 Mbyte

  • в—Џ integrated (for data)

10 Mbyte

  • в—Џ expandable

No

Load memory

 

  • в—Џ expandable FEPROM

Yes; with Memory Card (FLASH)

  • в—Џ expandable FEPROM, max.

64 Mbyte

  • в—Џ integrated RAM, max.

1 Mbyte

  • в—Џ expandable RAM

Yes

  • в—Џ expandable RAM, max.

64 Mbyte

Backup

 

  • в—Џ present

Yes

  • в—Џ with battery

Yes; all data

  • в—Џ without battery

No

Battery

 

Backup battery

 

  • в—Џ Backup current, typ.

180 µA; Valid up to 40°C

  • в—Џ Backup current, max.

1 000 µA

  • в—Џ Backup time, max.

Dealt with in the module data manual with the secondary conditions and the factors of influence

  • в—Џ Feeding of external backup voltage to CPU

5 V DC to 15 V DC

CPU processing times

 

for bit operations, typ.

12.5 ns

for word operations, typ.

12.5 ns

for fixed point arithmetic, typ.

12.5 ns

for floating point arithmetic, typ.

25 ns

CPU-blocks

 

DB

 

  • в—Џ Number, max.

16 000; Number range: 1 to 16000

  • в—Џ Size, max.

64 kbyte

FB

 

  • в—Џ Number, max.

8 000; Number range: 0 to 7999

  • в—Џ Size, max.

64 kbyte

FC

 

  • в—Џ Number, max.

8 000; Number range: 0 to 7999

  • в—Џ Size, max.

64 kbyte

OB

 

  • в—Џ Number, max.

see instruction list

  • в—Џ Size, max.

64 kbyte

  • в—Џ Number of free cycle OBs

1; OB 1

  • в—Џ Number of time alarm OBs

8; OB 10-17

  • в—Џ Number of delay alarm OBs

4; OB 20-23

  • в—Џ Number of cyclic interrupt OBs

9; OB 30-38

  • в—Џ Number of process alarm OBs

8; OB 40-47

  • в—Џ Number of DPV1 alarm OBs

3; OB 55-57

  • в—Џ Number of startup OBs

2; OB 100, 102

  • в—Џ Number of asynchronous error OBs

9; OB 80-88

  • в—Џ Number of synchronous error OBs

2; OB 121, 122

Nesting depth

 

  • в—Џ per priority class

24

  • в—Џ additional within an error OB

2

Counters, timers and their retentivity

 

S7 counter

 

  • в—Џ Number

2 048

Retentivity

 

  • — adjustable

Yes

  • — lower limit

0

  • — upper limit

2 047

  • — preset

Z 0 to Z 7

Counting range

 

  • — lower limit

0

  • — upper limit

999

IEC counter

 

  • в—Џ Number

Unlimited (limited only by RAM capacity)

S7 times

 

  • в—Џ Number

2 048

Retentivity

 

  • — adjustable

Yes

  • — lower limit

0

  • — upper limit

2 047

  • — preset

No times retentive

Time range

 

  • — lower limit

10 ms

  • — upper limit

9 990 s

IEC timer

 

  • в—Џ present

Yes

  • в—Џ Type

SFB

  • в—Џ Number

Unlimited (limited only by RAM capacity)

Data areas and their retentivity

 

retentive data area in total

Total working and load memory (with backup battery)

Flag

 

  • в—Џ Number, max.

16 384 byte

  • в—Џ Retentivity available

Yes

  • в—Џ Retentivity preset

MB 0 to MB 15

  • в—Џ Number of clock memories

8; in 1 memory byte

Data blocks

 

  • в—Џ Number, max.

16 000; Number range: 1 to 16000

  • в—Џ Size, max.

64 kbyte

Local data

 

  • в—Џ adjustable, max.

64 kbyte

  • в—Џ preset

32 kbyte

Address area

 

I/O address area

 

  • в—Џ Inputs

16 kbyte

  • в—Џ Outputs

16 kbyte

of which distributed

 

  • — MPI/DP interface, inputs

2 kbyte

  • — MPI/DP interface, outputs

2 kbyte

  • — DP interface, inputs

8 kbyte

  • — DP interface, outputs

8 kbyte

  • — PROFINET interface, inputs

8 kbyte

  • — PROFINET interface, outputs

8 kbyte

Process image

 

  • в—Џ Inputs, adjustable

16 kbyte

  • в—Џ Outputs, adjustable

16 kbyte

  • в—Џ Inputs, default

1 024 byte

  • в—Џ Outputs, default

1 024 byte

  • в—Џ consistent data, max.

244 byte

  • в—Џ Access to consistent data in process image

Yes

Subprocess images

 

  • в—Џ Number of subprocess images, max.

15

Digital channels

 

  • в—Џ Inputs

131 072

  • — of which central

131 072

  • в—Џ Outputs

131 072

  • — of which central

131 072

  • в—Џ Number of addressable digital I/Os, max.

131 072

Analog channels

 

  • в—Џ Inputs

8 192

  • — of which central

8 192

  • в—Џ Outputs

8 192

  • — of which central

8 192

  • в—Џ Number of addressable analog I/Os, max.

8 192

Hardware configuration

 

Number of expansion units, max.

21

connectable OPs

95

Multicomputing

No

Interface modules

 

  • в—Џ Number of connectable IMs (total), max.

6

  • в—Џ Number of connectable IM 460s, max.

6

  • в—Џ Number of connectable IM 463s, max.

4; Single mode only

Number of DP masters

 

  • в—Џ integrated

2

  • в—Џ via CP

10; CP 443-5 Extended

  • в—Џ Mixed mode IM + CP permitted

No

  • в—Џ via interface module

0

Number of IO Controllers

 

  • в—Џ integrated

1

  • в—Џ via CP

0

Number of operable FMs and CPs (recommended)

 

  • в—Џ FM

See manual Automation System S7-400H fault-tolerant systems. Limited by number of slots and number of connections

  • в—Џ CP, PtP

See manual Automation System S7-400H fault-tolerant systems. Limited by number of slots and number of connections

  • в—Џ PROFIBUS and Ethernet CPs

14; Of which max. 10 CP as DP master

Slots

 

  • в—Џ required slots

2

Time of day

 

Clock

 

  • в—Џ Hardware clock (real-time)

Yes

  • в—Џ retentive and synchronizable

Yes

  • в—Џ Resolution

1 ms

  • в—Џ Deviation per day (buffered), max.

1.7 s; Power off

  • в—Џ Deviation per day (unbuffered), max.

8.6 s; Power on

Operating hours counter

 

  • в—Џ Number

16

  • в—Џ Number/Number range

0 to 15

  • в—Џ Range of values

SFCs 2, 3 and 4: 0 to 32767 hours SFC 101: 0 to 2^31 - 1 hours

  • в—Џ Granularity

1 hour

  • в—Џ retentive

Yes

Clock synchronization

 

  • в—Џ supported

Yes

  • в—Џ to MPI, master

Yes

  • в—Џ to MPI, slave

Yes

  • в—Џ to DP, master

Yes

  • в—Џ to DP, slave

Yes

  • в—Џ in AS, master

Yes

  • в—Џ in AS, slave

Yes

  • в—Џ on Ethernet via NTP

Yes; As client

Time difference in system when synchronizing via

 

  • в—Џ Ethernet, max.

10 ms; Via NTP

  • в—Џ MPI, max.

200 ms

Interfaces

 

Number of RS 485 interfaces

2

Number of other interfaces

2; Fiber-optic interface

1. Interface

 

Interface type

Integrated

Physics

RS 485 / PROFIBUS + MPI

Isolated

Yes

Power supply to interface (15 to 30 V DC), max.

150 mA

Number of connection resources

MPI: 44, DP: 32

Functionality

 

  • в—Џ MPI

Yes

  • в—Џ PROFIBUS DP master

Yes

  • в—Џ PROFIBUS DP slave

No

MPI

 

  • в—Џ Number of connections

44; If a diagnostics repeater is used on the line, the number of connection resources on the line is reduced by 1

  • в—Џ Transmission rate, max.

12 Mbit/s

Services

 

  • — PG/OP communication

Yes

  • — Routing

Yes

  • — Global data communication

No

  • — S7 basic communication

No

  • — S7 communication

Yes

  • — S7 communication, as client

Yes

  • — S7 communication, as server

Yes

DP master

 

  • в—Џ Number of connections, max.

32; If a diagnostics repeater is used on the line, the number of connection resources on the line is reduced by 1

  • в—Џ Transmission rate, max.

12 Mbit/s

  • в—Џ Number of DP slaves, max.

32

Services

 

  • — PG/OP communication

Yes

  • — Routing

Yes

  • — Global data communication

No

  • — S7 basic communication

No

  • — S7 communication

Yes

  • — S7 communication, as client

Yes

  • — S7 communication, as server

Yes

  • — Equidistance

No

  • — Isochronous mode

No

  • — SYNC/FREEZE

No

  • — Activation/deactivation of DP slaves

No

  • — Direct data exchange (slave-to-slave communication)

No

  • — DPV1

Yes

Address area

 

  • — Inputs, max.

2 kbyte

  • — Outputs, max.

2 kbyte

User data per DP slave

 

  • — User data per DP slave, max.

244 byte

  • — Inputs, max.

244 byte

  • — Outputs, max.

244 byte

  • — Slots, max.

244

  • — per slot, max.

128 byte

DP slave

 

  • в—Џ Number of connections

No configuration of CPU as DP slave

2. Interface

 

Interface type

PROFINET

Physics

Ethernet RJ45

Isolated

Yes

automatic detection of transmission rate

Yes; Autosensing

Autonegotiation

Yes

Autocrossing

Yes

Change of IP address at runtime, supported

No

Number of connection resources

96

Interface types

 

  • в—Џ Number of ports

2

  • в—Џ integrated switch

Yes

Media redundancy

 

  • в—Џ supported

Yes

  • в—Џ Switchover time on line break, typ.

200 ms

  • в—Џ Number of stations in the ring, max.

50

Functionality

 

  • в—Џ PROFINET IO Controller

Yes

  • в—Џ PROFINET IO Device

No

  • в—Џ PROFINET CBA

No

  • в—Џ PROFIBUS DP master

No

  • в—Џ PROFIBUS DP slave

No

  • в—Џ Open IE communication

Yes

  • в—Џ Web server

No

  • в—Џ Point-to-point connection

No

PROFINET IO Controller

 

  • в—Џ Transmission rate, max.

100 Mbit/s

Services

 

  • — PG/OP communication

Yes

  • — S7 routing

Yes

  • — S7 communication

Yes

  • — Isochronous mode

No

  • — Open IE communication

Yes

  • — Shared device

Yes; Single mode only

  • — Prioritized startup

No

  • — Number of connectable IO Devices, max.

256; In redundant mode via both interfaces

  • — Number of connectable IO Devices for RT, max.

256

  • — of which in line, max.

256

  • — Activation/deactivation of IO Devices

No

  • — IO Devices changing during operation (partner ports), supported

No

  • — Device replacement without swap medium

Yes

  • — Send cycles

250 µs, 500 µs, 1 ms, 2 ms, 4 ms

  • — Updating time

250 µs to 512 ms, minimum value depends on the number of configured user data and the configured single or redundant mode

Address area

 

  • — Inputs, max.

8 kbyte

  • — Outputs, max.

8 kbyte

  • — User data consistency, max.

1 024 byte

Open IE communication

 

  • в—Џ Number of connections, max.

94

  • в—Џ Local port numbers used at the system end

0, 20, 21, 25, 102, 135, 161, 34962, 34963, 34964, 65532, 65533, 65534, 65535

  • в—Џ Keep-alive function, supported

Yes

3. Interface

 

Interface type

Integrated

Physics

RS 485 / PROFIBUS

Power supply to interface (15 to 30 V DC), max.

150 mA

Number of connection resources

32

Functionality

 

  • в—Џ PROFIBUS DP master

Yes

  • в—Џ PROFIBUS DP slave

No

DP master

 

  • в—Џ Number of connections, max.

32

  • в—Џ Number of DP slaves, max.

125

Services

 

  • — PG/OP communication

Yes

  • — Routing

Yes

  • — Global data communication

No

  • — S7 basic communication

No

  • — S7 communication

Yes

  • — S7 communication, as client

Yes

  • — S7 communication, as server

Yes

  • — Equidistance

No

  • — Isochronous mode

No

  • — SYNC/FREEZE

No

  • — Activation/deactivation of DP slaves

No

  • — Direct data exchange (slave-to-slave communication)

No

  • — DPV0

Yes

  • — DPV1

Yes

Address area

 

  • — Inputs, max.

8 kbyte

  • — Outputs, max.

8 kbyte

User data per DP slave

 

  • — User data per DP slave, max.

244 byte

  • — Inputs, max.

244 byte

  • — Outputs, max.

244 byte

  • — Slots, max.

244

  • — per slot, max.

128 byte

4. Interface

 

Interface type

Pluggable synchronization submodule (FO)

Plug-in interface modules

Synchronization modules 6ES7960-1AA06-0XA0 or 6ES7960-1AB06-0XA0

5. Interface

 

Interface type

Pluggable synchronization submodule (FO)

Plug-in interface modules

Synchronization modules 6ES7960-1AA06-0XA0 or 6ES7960-1AB06-0XA0

Protocols

 

SIMATIC communication

 

  • в—Џ S7 routing

Yes

Open IE communication

 

  • в—Џ TCP/IP

Yes; via integrated PROFINET interface and loadable FBs

  • — Data length, max.

32 kbyte

  • — several passive connections per port, supported

Yes

  • в—Џ ISO-on-TCP (RFC1006)

Yes; Via integrated PROFINET interface or CP 443-1 and loadable FBs

  • — Data length, max.

32 kbyte; 1452 bytes via CP 443-1 Adv.

  • в—Џ UDP

Yes; via integrated PROFINET interface and loadable FBs

  • — Data length, max.

1 472 byte

Isochronous mode

 

Isochronous operation (application synchronized up to terminal)

No

Equidistance

No

Communication functions

 

PG/OP communication

Yes

  • в—Џ Number of connectable OPs without message processing

95

  • в—Џ Number of connectable OPs with message processing

95; When using Alarm_S/SQ and Alarm_D/DQ

Data record routing

Yes

Global data communication

 

  • в—Џ supported

No

S7 basic communication

 

  • в—Џ supported

No

S7 communication

 

  • в—Џ supported

Yes

  • в—Џ as server

Yes

  • в—Џ as client

Yes

  • в—Џ User data per job, max.

64 kbyte

  • в—Џ User data per job (of which consistent), max.

462 byte; 1 variable

S5 compatible communication

 

  • в—Џ supported

Yes; (via CP max. 10 and FC AG_SEND and FC AG_RECV)

  • в—Џ User data per job, max.

8 kbyte

  • в—Џ User data per job (of which consistent), max.

240 byte

  • в—Џ Number of simultaneous AG-SEND/AG-RECV orders per CPU, max.

64/64

Standard communication (FMS)

 

  • в—Џ supported

Yes; Via CP and loadable FB

Web server

 

  • в—Џ supported

No

Number of connections

 

  • в—Џ overall

96

  • в—Џ usable for PG communication

  • — reserved for PG communication

1

  • — adjustable for PG communication, max.

0

  • в—Џ usable for OP communication

  • — reserved for OP communication

1

  • — adjustable for OP communication, max.

0

  • в—Џ usable for S7 basic communication

  • — reserved for S7 basic communication

0

  • — adjustable for S7 basic communication, max.

0

  • в—Џ usable for S7 communication

  • — reserved for S7 communication

0

  • — adjustable for S7 communication, max.

0

  • в—Џ usable for routing

  • — reserved for routing

0

  • — adjustable for routing, max.

0

S7 message functions

 

Number of login stations for message functions, max.

95; Max. 95 with Alarm_S/SQ and Alarm_D/DQ (OPs); max. 8 with Alarm, Alarm_8, Alarm_8P, Notify and Notify_8 (e.g. WinCC)

Symbol-related messages

No

SCAN procedure

No

Program alarms

Yes

Process diagnostic messages

Yes

simultaneously active Alarm-S blocks, max.

1 000; Simultaneously active alarm_S/SQ blocks or alarm_D/DQ blocks

Alarm 8-blocks

Yes

  • в—Џ Number of instances for alarm 8 and S7 communication blocks, max.

10 000

  • в—Џ preset, max.

1 200

Process control messages

Yes

Number of archives that can log on simultaneously (SFB 37 AR_SEND)

64

Test commissioning functions

 

Status block

Yes

Single step

Yes

Number of breakpoints

16

Status/control

 

  • в—Џ Status/control variable

Yes; Up to 16 variable tables

  • в—Џ Variables

Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters

  • в—Џ Number of variables, max.

70

Forcing

 

  • в—Џ Forcing

Yes

  • в—Џ Forcing, variables

Inputs/outputs, bit memories, distributed I/Os

  • в—Џ Number of variables, max.

512

Diagnostic buffer

 

  • в—Џ present

Yes

  • в—Џ Number of entries, max.

3 200

  • — adjustable

Yes

  • — preset

120

Service data

 

  • в—Џ can be read out

Yes

EMC

 

Emission of radio interference acc. to EN 55 011

 

  • в—Џ Limit class A, for use in industrial areas

Yes

  • в—Џ Limit class B, for use in residential areas

No

Configuration

 

Configuration software

 

  • в—Џ STEP 7

Yes

Programming

 

  • в—Џ Command set

see instruction list

  • в—Џ Nesting levels

7

  • в—Џ Access to consistent data in process image

Yes

  • в—Џ System functions (SFC)

see instruction list

  • в—Џ System function blocks (SFB)

see instruction list

Programming language

 

  • — LAD

Yes

  • — FBD

Yes

  • — STL

Yes

  • — SCL

Yes

  • — CFC

Yes

  • — GRAPH

Yes

  • — HiGraph®

Yes

Number of simultaneously active SFCs

 

  • — RD_REC

8

  • — WR_REC

8

  • — WR_PARM

8

  • — PARM_MOD

1

  • — WR_DPARM

2

  • — DPNRM_DG

8

  • — RDSYSST

8

  • — DP_TOPOL

1

Number of simultaneously active SFBs

 

  • — RDREC

8

  • — WRREC

8

Know-how protection

 

  • в—Џ User program protection/password protection

Yes

  • в—Џ Block encryption

Yes; With S7 block Privacy

Dimensions

 

Width

50 mm

Height

290 mm

Depth

219 mm

Weights

 

Weight, approx.

995 g


















skener.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Арматура DENDOR

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Датчики и измерители

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Регуляторы и регистраторы

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Пневматическое оборудование

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Краны и Клапаны

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Измерительные приборы

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Системы беспроводного управления «умный дом»

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Бесконтактные выключатели Конечные выключатели Оптические датчики Энкодеры

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Установка умягчения

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Установка обезжелезивания

  © ООО "СК ЭНЕРГО" 2007-2022
  (4872) 700-366  skenergo@mail.ru
Рейтинг@Mail.ru Яндекс.Метрика