Siemens
01 2018
(4872) 700-366
skenergo@mail.ru

Article number

6ES7131-6BF00-0AA0

6ES7131-6BF60-0AA0

6ES7131-6BF00-0BA0

6ES7131-6BH00-0BA0

ET 200SP, DI 8X24VDC BASIC

ET 200SP, DI 8X24VDC SOURCE BA

ET 200SP, DI 8X24VDC ST

ET 200SP, DI 16X24VDC ST

General information

Product type designation

DI 8x24 VDC BA

DI 8x24 VDC SRC BA

DI 8x24 VDC ST

DI 16x24 VDC ST

Firmware version

V1.0

V1.0

V1.1

V1.1

  • FW update possible

Yes

Yes

Yes

Yes

usable BaseUnits

BU type A0

BU type A0

BU type A0

BU type A0

Color code for module-specific color identification plate

CC01

CC02

CC01

CC00

Product function

  • I&M data

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Engineering with

  • STEP 7 TIA Portal configurable/integrated as of version

V13 SP1

V13 / V13

V11 SP2 / V13

V13 SP1

  • STEP 7 configurable/integrated as of version

V5.5 SP3 / -

V5.5 SP3 / -

V5.5 SP3 / -

V5.5 / -

  • PCS 7 configurable/integrated as of version

V8.1 SP1

V8.1 SP1

  • PROFIBUS as of GSD version/GSD revision

GSD Revision 5

GSD Revision 5

GSD Revision 5

GSD Revision 5

  • PROFINET as of GSD version/GSD revision

GSDML V2.3

GSDML V2.3

GSDML V2.3

GSDML V2.3

Operating mode

  • DI

Yes

Yes

Yes

Yes

  • Counter

No

No

No

No

  • Oversampling

No

No

No

No

  • MSI

No

No

No

No

Supply voltage

Rated value (DC)

24V

24V

24V

24V

permissible range, lower limit (DC)

19.2V

19.2V

19.2V

19.2V

permissible range, upper limit (DC)

28.8V

28.8V

28.8V

28.8V

Reverse polarity protection

Yes

Yes

Yes

Yes

Input current

Current consumption (rated value)

8mA; without sensor supply

Current consumption, max.

70mA; All channels are supplied from the encoder supply

50mA

90mA

Encoder supply

Number of outputs

8

8

Output voltage encoder supply, min.

19.2V

19.2V

Short-circuit protection

No

No

Yes; per module

No

24 V encoder supply

  • 24 V

Yes

Yes

No

  • Short-circuit protection

Yes

Yes

No

  • Output current, max.

700mA

700mA; Total current of all encoders

Power loss

Power loss, typ.

1.6W; 24 V, 8 inputs supplied via encoder supply

1.5W

1W

1.7W

Address area

Address space per module

  • Address space per module, max.

1byte

1byte

1byte; + 1 byte for QI information

2byte; + 2 bytes for QI information

  • Inputs

1byte

1byte

Hardware configuration

Automatic encoding

  • Mechanical coding element

Yes

Selection of BaseUnit for connection variants

  • 1-wire connection

BU type A0

BU type A0

BU type A0

BU type A0

  • 2-wire connection

BU type A0

BU type A0

BU type A0

BU type A0 + external terminals

  • 3-wire connection

BU type A0 with AUX terminals

BU type A0 with AUX terminals

BU type A0 with AUX terminals

BU type A0 + external terminals

  • 4-wire connection

BU type A0 + external terminals

BU type A0 + external terminals

BU type A0 + external terminals

BU type A0 + external terminals

Digital inputs

Number of digital inputs

8

8

8

16

Source/sink input

P-reading

Yes; m-reading

P-reading

P-reading

Input characteristic curve in accordance with IEC 61131, type 1

Yes

Yes

Yes

Yes

Input characteristic curve in accordance with IEC 61131, type 2

Yes

No

No

No

Input characteristic curve in accordance with IEC 61131, type 3

Yes

Yes

Yes

Yes

Pulse extension

No

No

No

No

Input voltage

  • Type of input voltage

DC

DC

DC

DC

  • Rated value (DC)

24V

24V

24V

24V

  • for signal "0"

-30 to +5V

30 V to -5 V (reference potential is L+)

-30 to +5V

-30 to +5V

  • for signal "1"

+11 to +30V

-11 V to -30 V (reference potential is L+)

+11 to +30V

+11 to +30V

Input current

  • for signal "1", typ.

6.8mA

6mA

2.5mA

2.5mA

Input delay (for rated value of input voltage)

for standard inputs

  • parameterizable

Yes; None / 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms (in each case + delay of 30 s to 500 s, depending on line length)

Yes; 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms (in each case + delay of 30 to 500 s, depending on line length)

Yes; 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms (in each case + delay of 30 to 500 s, depending on line length)

Yes; 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms (in each case + delay of 30 to 500 s, depending on line length)

  • at "0" to "1", min.

0.05ms

  • at "0" to "1", max.

20ms

  • at "1" to "0", min.

0.05ms

  • at "1" to "0", max.

20ms

for interrupt inputs

  • parameterizable

No

No

No

No

for counter/technological functions

  • parameterizable

No

No

No

No

Cable length

  • shielded, max.

1000m

1000m

1000m

1000m

  • unshielded, max.

600m

200m

600m

600m

Encoder

Connectable encoders

  • 2-wire sensor

Yes

Yes

Yes

Yes

  • permissible quiescent current (2-wire sensor), max.

2mA

1.5mA

1.5mA

1.5mA

Isochronous mode

Isochronous operation (application synchronized up to terminal)

No

No

No

No

Interrupts/diagnostics/status information

Diagnostics function

Yes

Yes

Yes

Yes

Alarms

  • Diagnostic alarm

Yes

Yes

Yes

Yes

  • Hardware interrupt

No

Diagnostic messages

  • Diagnostic information readable

Yes

Yes

Yes

Yes

  • Monitoring the supply voltage

Yes

Yes

Yes

Yes

  • parameterizable

Yes

Yes

Yes

Yes

  • Monitoring of encoder power supply

No

No

Yes; Module-wise

No

  • Wire-break

No

No

Yes; Module-by-module, optional protective circuit for preventing wire-break diagnostics in the case of simple encoder contacts: 25 kOhm to 45 kOhm

Yes; Module-by-module, optional protective circuit for preventing wire-break diagnostics in the case of simple encoder contacts: 25 kOhm to 45 kOhm

  • Short-circuit

No

No

Yes; Module-wise

No

  • Group error

Yes

Yes

Diagnostics indication LED

  • Monitoring of the supply voltage (PWR-LED)

Yes; green PWR LED

Yes; green PWR LED

Yes; green PWR LED

Yes; green PWR LED

  • Channel status display

Yes; Green LED

Yes; Green LED

Yes; Green LED

Yes; Green LED

  • for channel diagnostics

No

No

No

No

  • for module diagnostics

Yes; green/red DIAG LED

Yes; green/red DIAG LED

Yes; green/red DIAG LED

Yes; green/red DIAG LED

Potential separation

Potential separation channels

  • between the channels

No

No

No

No

  • between the channels and backplane bus

Yes

Yes

Yes

Yes

  • between the channels and the power supply of the electronics

No

No

No

No

Isolation

Isolation tested with

707 V DC (type test)

707 V DC (type test)

707 V DC (type test)

707 V DC (type test)

Dimensions

Width

15mm

15mm

15mm

15mm

Height

73mm

73mm

73mm

73mm

Depth

58mm

58mm

58mm

58mm

Weights

Weight, approx.

28g

28g

28g

28g


Article number

6ES7131-6BF00-0CA0

6ES7131-6BF00-0DA0

6ES7131-6TF00-0CA0

6ES7131-6FD00-0BB1

ET 200SP, DI 8X24VDC HF

ET 200SP, DI 8X24VDC HIGH SPEED

ET 200SP, DI 8XNAMUR HF

ET 200SP, DI 4X120..230VAC ST

General information

Product type designation

DI 8x24 V DC HF

DI 8x24 V DC HS

DI 8xNAMUR HF

DI 4x120 … 230 V AC ST

Firmware version

V2.0

V1.0.2

V1.0

V1.0

  • FW update possible

Yes

Yes

Yes

Yes

usable BaseUnits

BU type A0

BU type A0

BU type A0

BU type B1

Color code for module-specific color identification plate

CC01

CC01

CC01

CC41

Product function

  • I&M data

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Yes; I&M0 to I&M3

Engineering with

  • STEP 7 TIA Portal configurable/integrated as of version

V13 SP1 / -

V13 SP1

V13 / V13

V13 / V13

  • STEP 7 configurable/integrated as of version

V5.5 / -

V5.5 SP3 / -

V5.5 SP3 / -

V5.5 SP3 / -

  • PCS 7 configurable/integrated as of version

V8.1 SP1

  • PROFIBUS as of GSD version/GSD revision

One GSD file each, Revision 3 and 5 and higher

GSD Revision 5

GSD Revision 5

GSD Revision 5

  • PROFINET as of GSD version/GSD revision

GSDML V2.3

GSDML V2.3

GSDML V2.3

GSDML V2.3

Operating mode

  • DI

Yes

Yes

Yes

Yes

  • Counter

No

Yes

No

No

  • Oversampling

No

Yes

No

No

  • MSI

Yes

No

No

No

Supply voltage

Rated value (DC)

24V

24V

24V

permissible range, lower limit (DC)

19.2V

19.2V

19.2V

permissible range, upper limit (DC)

28.8V

28.8V

28.8V

Rated value (AC)

230V

Reverse polarity protection

Yes

Yes

Yes

No

Input current

Current consumption (rated value)

10mA

Current consumption, max.

70mA; without sensor supply

Encoder supply

Number of outputs

8

8

4

Output voltage encoder supply, min.

19.2V

Short-circuit protection

Yes

Yes

No; when using BU type B1, a fuse with 10 A tripping current must be provided

Output current

  • up to 60 C, max.

10A

24 V encoder supply

  • 24 V

Yes

Yes

No

No

  • Short-circuit protection

Yes; per channel, electronic

Yes; per module, electronic

No

No

  • Output current, max.

700mA

Power loss

Power loss, typ.

1.5W; 24 V, 8 inputs supplied via encoder supply

1.5W

1.5W

1W; Active power, load voltage 230 V, all inputs connected with 230 V, 50 Hz

Address area

Address space per module

  • Address space per module, max.

45byte

1byte; + 1 byte for QI information

1byte; + 1 byte for QI information

  • Inputs

1byte; + 1 byte for QI information

32byte; 1 byte + 1 byte for QI information in DI mode; 32 bytes in Oversampling mode; 25 bytes in Counter mode

1byte

  • Outputs

20byte; In count mode

Hardware configuration

Automatic encoding

Yes

  • Mechanical coding element

Yes

Submodules

  • Number of configurable submodules, max.

4

Selection of BaseUnit for connection variants

  • 1-wire connection

BU type A0

BU type A0

BU type A0

BU type B1

  • 2-wire connection

BU type A0

BU type A0

BU type A0

BU type B1

  • 3-wire connection

BU type A0 with AUX terminals

BU type A0 with AUX terminals

BU type A0 + external terminals

BU type B1

  • 4-wire connection

BU type A0 + Potential isolation module

BU type A0 + external terminals

BU type A0 + external terminals

BU type B1 + external terminals

Digital inputs

Number of digital inputs

8

8

8; NAMUR

4

Digital inputs, parameterizable

Yes

Yes

Source/sink input

P-reading

P-reading

No

Input characteristic curve in accordance with IEC 61131, type 3

Yes

Yes

Pulse extension

Yes; Pulse duration from 4 s

Yes

Yes; 0.5 s, 1 s, 2 s

No

  • Length

2s; 50 ms, 100 ms, 200 ms, 500 ms, 1 s, 2 s

2s; 50 ms, 100 ms, 200 ms, 500 ms, 1 s, 2 s

Edge evaluation

Yes; rising edge, falling edge, edge change

Yes; rising edge, falling edge, edge change

Signal change flutter

Yes; 2 to 32 signal changes

Flutter observation window

Yes; 0.5 s, 1 s to 100 s in 1-s steps

Digital input functions, parameterizable

  • Gate start/stop

Yes

  • Freely usable digital input

Yes

  • Counter

Yes

  • Number, max.

4

  • Counting frequency, max.

10kHz

  • Counting width

32bit

  • Counting direction up/down

Yes

  • Digital input with oversampling

Yes

  • Number, max.

8

  • Values per cycle, max.

32

  • Resolution, min.

7.8125s

Input voltage

  • Type of input voltage

DC

DC

DC

120/230 V AC (47 Hz to 63 Hz)

  • Rated value (DC)

24V

24V

8.2V

  • Rated value (AC)

230V

  • for signal "0"

-30 to +5V

-30 to +5V

0V AC to 40V AC

  • for signal "1"

+11 to +30V

+11 to +30V

74 V AC to 264 V AC

Input current

  • for signal "1", typ.

2.5mA

6mA

10.8mA

for 10 k switched contact

  • for signal "0"

0.35 to 1.2 mA

  • for signal "1"

2.1 to 7 mA

for unswitched contact

  • for signal "0", max. (permissible quiescent current)

0.5mA

  • for signal "1"

typ. 8 mA

for NAMUR encoders

  • for signal "0"

0.35 to 1.2 mA

  • for signal "1"

2.1 to 7 mA

Input delay (for rated value of input voltage)

  • tolerated changeover time for changeover contacts

300ms

for standard inputs

  • parameterizable

Yes; 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms (in each case + delay of 30 to 500 s, depending on line length)

Yes; none / 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms

No

No

  • at "0" to "1", min.

0.05ms

1.5ms

  • at "0" to "1", max.

20ms

4ms

  • at "1" to "0", min.

0.05ms

10ms

  • at "1" to "0", max.

20ms

10ms

for interrupt inputs

  • parameterizable

Yes

for counter/technological functions

  • parameterizable

Yes

for NAMUR inputs

  • at "0" to "1", max.

12ms

  • at "1" to "0", max.

12ms

Cable length

  • shielded, max.

1000m

50m

200m

1000m

  • unshielded, max.

600m

50m

600m

Encoder

Connectable encoders

  • NAMUR encoder/changeover contact according to EN 60947

Yes

  • Single contact / changeover contact unconnected

Yes

  • Single contact / changeover contact connected with 10 kΩ

Yes

  • 2-wire sensor

Yes

Yes

Yes

  • permissible quiescent current (2-wire sensor), max.

1.5mA

1.5mA

Isochronous mode

Isochronous operation (application synchronized up to terminal)

Yes

Yes

No

No

Filtering and processing time (TCI), min.

420s

Bus cycle time (TDP), min.

500s

125s

Jitter, max.

8s

5s

Interrupts/diagnostics/status information

Diagnostics function

Yes

Yes

Yes

Alarms

  • Diagnostic alarm

Yes; channel by channel

Yes

Yes; channel by channel

No

  • Hardware interrupt

Yes; Parameterizable, channels 0 to 7

Yes

Yes; Parameterizable, channels 0 to 7

No

Diagnostic messages

  • Diagnostic information readable

Yes

Yes

Yes

  • Monitoring the supply voltage

Yes

Yes

Yes

  • parameterizable

Yes

Yes

Yes

  • Monitoring of encoder power supply

Yes; channel by channel

Yes; Module-wise

Yes; channel by channel

  • Wire-break

Yes; Channel by channel, optional protective circuit for preventing wire-break diagnostics in the case of simple encoder contacts: 25 kOhm to 45 kOhm

No

Yes; channel by channel

No

  • Short-circuit

Yes; channel by channel

Yes; Module-wise

Yes; channel by channel

No

  • Group error

Yes

Yes

Diagnostics indication LED

  • Monitoring of the supply voltage (PWR-LED)

Yes; green PWR LED

Yes; green PWR LED

Yes; green PWR LED

Yes; green PWR LED

  • Channel status display

Yes; Green LED

Yes; Green LED

Yes; Green LED

Yes; Green LED

  • for channel diagnostics

Yes; Red LED

No

Yes; Red LED

No

  • for module diagnostics

Yes; green/red DIAG LED

Yes; green/red DIAG LED

Yes; green/red DIAG LED

Yes; green/red DIAG LED

Potential separation

Potential separation channels

  • between the channels

No

No

No

No

  • between the channels and backplane bus

Yes

Yes

Yes

Yes

  • between the channels and the power supply of the electronics

No

No

Yes

No

Isolation

Isolation tested with

707 V DC (type test)

707 V DC (type test)

707 V DC (type test)

2 545 V DC/2 s (routine test)

Ambient conditions

Ambient temperature during operation

  • horizontal installation, min.

0C

  • horizontal installation, max.

60C

  • vertical installation, min.

0C

  • vertical installation, max.

50C

Altitude during operation relating to sea level

  • Ambient air temperature-barometric pressure-altitude

On request: Negative ambient temperature down to -30 C (without condensation), installation altitudes between 2 000 m and 5 000 m

Dimensions

Width

15mm

15mm

15mm

20mm

Height

73mm

73mm

73mm

73mm

Depth

58mm

58mm

58mm

58mm

Weights

Weight, approx.

28g

28g

32g

36g



















  © " " 2007-2022