General information | | | | |
Product type designation | DI 8x24 V DC HF | DI 8x24 V DC HS | DI 8xNAMUR HF | DI 4x120 … 230 V AC ST |
Firmware version | V2.0 | V1.0.2 | V1.0 | V1.0 |
| Yes | Yes | Yes | Yes |
usable BaseUnits | BU type A0 | BU type A0 | BU type A0 | BU type B1 |
Color code for module-specific color identification plate | CC01 | CC01 | CC01 | CC41 |
Product function | | | | |
| Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 |
Engineering with | | | | |
| V13 SP1 / - | V13 SP1 | V13 / V13 | V13 / V13 |
| V5.5 / - | V5.5 SP3 / - | V5.5 SP3 / - | V5.5 SP3 / - |
| V8.1 SP1 | | | |
| One GSD file each, Revision 3 and 5 and higher | GSD Revision 5 | GSD Revision 5 | GSD Revision 5 |
| GSDML V2.3 | GSDML V2.3 | GSDML V2.3 | GSDML V2.3 |
Operating mode | | | | |
| Yes | Yes | Yes | Yes |
| No | Yes | No | No |
| No | Yes | No | No |
| Yes | No | No | No |
Supply voltage | | | | |
Rated value (DC) | 24V | 24V | 24V | |
permissible range, lower limit (DC) | 19.2V | 19.2V | 19.2V | |
permissible range, upper limit (DC) | 28.8V | 28.8V | 28.8V | |
Rated value (AC) | | | | 230V |
Reverse polarity protection | Yes | Yes | Yes | No |
Input current | | | | |
Current consumption (rated value) | | | | 10mA |
Current consumption, max. | | 70mA; without sensor supply | | |
Encoder supply | | | | |
Number of outputs | 8 | | 8 | 4 |
Output voltage encoder supply, min. | 19.2V | | | |
Short-circuit protection | Yes | | Yes | No; when using BU type B1, a fuse with 10 A tripping current must be provided |
Output current | | | | |
| | | | 10A |
24 V encoder supply | | | | |
| Yes | Yes | No | No |
| Yes; per channel, electronic | Yes; per module, electronic | No | No |
| | 700mA | | |
Power loss | | | | |
Power loss, typ. | 1.5W; 24 V, 8 inputs supplied via encoder supply | 1.5W | 1.5W | 1W; Active power, load voltage 230 V, all inputs connected with 230 V, 50 Hz |
Address area | | | | |
Address space per module | | | | |
| | 45byte | 1byte; + 1 byte for QI information | 1byte; + 1 byte for QI information |
| 1byte; + 1 byte for QI information | 32byte; 1 byte + 1 byte for QI information in DI mode; 32 bytes in Oversampling mode; 25 bytes in Counter mode | | 1byte |
| | 20byte; In count mode | | |
Hardware configuration | | | | |
Automatic encoding | Yes | | | |
| Yes | | | |
Submodules | | | | |
| 4 | | | |
Selection of BaseUnit for connection variants | | | | |
| BU type A0 | BU type A0 | BU type A0 | BU type B1 |
| BU type A0 | BU type A0 | BU type A0 | BU type B1 |
| BU type A0 with AUX terminals | BU type A0 with AUX terminals | BU type A0 + external terminals | BU type B1 |
| BU type A0 + Potential isolation module | BU type A0 + external terminals | BU type A0 + external terminals | BU type B1 + external terminals |
Digital inputs | | | | |
Number of digital inputs | 8 | 8 | 8; NAMUR | 4 |
Digital inputs, parameterizable | Yes | | Yes | |
Source/sink input | P-reading | P-reading | | No |
Input characteristic curve in accordance with IEC 61131, type 3 | Yes | | | Yes |
Pulse extension | Yes; Pulse duration from 4 s | Yes | Yes; 0.5 s, 1 s, 2 s | No |
| 2s; 50 ms, 100 ms, 200 ms, 500 ms, 1 s, 2 s | 2s; 50 ms, 100 ms, 200 ms, 500 ms, 1 s, 2 s | | |
Edge evaluation | Yes; rising edge, falling edge, edge change | | Yes; rising edge, falling edge, edge change | |
Signal change flutter | | | Yes; 2 to 32 signal changes | |
Flutter observation window | | | Yes; 0.5 s, 1 s to 100 s in 1-s steps | |
Digital input functions, parameterizable | | | | |
| | Yes | | |
| | Yes | | |
| | Yes | | |
| | 4 | | |
| | 10kHz | | |
| | 32bit | | |
| | Yes | | |
| | Yes | | |
| | 8 | | |
| | 32 | | |
| | 7.8125s | | |
Input voltage | | | | |
| DC | DC | DC | 120/230 V AC (47 Hz to 63 Hz) |
| 24V | 24V | 8.2V | |
| | | | 230V |
| -30 to +5V | -30 to +5V | | 0V AC to 40V AC |
| +11 to +30V | +11 to +30V | | 74 V AC to 264 V AC |
Input current | | | | |
| 2.5mA | 6mA | | 10.8mA |
for 10 k switched contact | | | | |
| | | 0.35 to 1.2 mA | |
| | | 2.1 to 7 mA | |
for unswitched contact | | | | |
| | | 0.5mA | |
| | | typ. 8 mA | |
for NAMUR encoders | | | | |
| | | 0.35 to 1.2 mA | |
| | | 2.1 to 7 mA | |
Input delay (for rated value of input voltage) | | | | |
| | | 300ms | |
for standard inputs | | | | |
| Yes; 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms (in each case + delay of 30 to 500 s, depending on line length) | Yes; none / 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms | No | No |
| 0.05ms | | | 1.5ms |
| 20ms | | | 4ms |
| 0.05ms | | | 10ms |
| 20ms | | | 10ms |
for interrupt inputs | | | | |
| | Yes | | |
for counter/technological functions | | | | |
| | Yes | | |
for NAMUR inputs | | | | |
| | | 12ms | |
| | | 12ms | |
Cable length | | | | |
| 1000m | 50m | 200m | 1000m |
| 600m | 50m | | 600m |
Encoder | | | | |
Connectable encoders | | | | |
| | | Yes | |
| | | Yes | |
| | | Yes | |
| Yes | Yes | | Yes |
| 1.5mA | 1.5mA | | |
Isochronous mode | | | | |
Isochronous operation (application synchronized up to terminal) | Yes | Yes | No | No |
Filtering and processing time (TCI), min. | 420s | | | |
Bus cycle time (TDP), min. | 500s | 125s | | |
Jitter, max. | 8s | 5s | | |
Interrupts/diagnostics/status information | | | | |
Diagnostics function | Yes | Yes | Yes | |
Alarms | | | | |
| Yes; channel by channel | Yes | Yes; channel by channel | No |
| Yes; Parameterizable, channels 0 to 7 | Yes | Yes; Parameterizable, channels 0 to 7 | No |
Diagnostic messages | | | | |
| Yes | Yes | Yes | |
| Yes | Yes | Yes | |
| Yes | Yes | Yes | |
| Yes; channel by channel | Yes; Module-wise | Yes; channel by channel | |
| Yes; Channel by channel, optional protective circuit for preventing wire-break diagnostics in the case of simple encoder contacts: 25 kOhm to 45 kOhm | No | Yes; channel by channel | No |
| Yes; channel by channel | Yes; Module-wise | Yes; channel by channel | No |
| | | Yes | Yes |
Diagnostics indication LED | | | | |
| Yes; green PWR LED | Yes; green PWR LED | Yes; green PWR LED | Yes; green PWR LED |
| Yes; Green LED | Yes; Green LED | Yes; Green LED | Yes; Green LED |
| Yes; Red LED | No | Yes; Red LED | No |
| Yes; green/red DIAG LED | Yes; green/red DIAG LED | Yes; green/red DIAG LED | Yes; green/red DIAG LED |
Potential separation | | | | |
Potential separation channels | | | | |
| No | No | No | No |
| Yes | Yes | Yes | Yes |
| No | No | Yes | No |
Isolation | | | | |
Isolation tested with | 707 V DC (type test) | 707 V DC (type test) | 707 V DC (type test) | 2 545 V DC/2 s (routine test) |
Ambient conditions | | | | |
Ambient temperature during operation | | | | |
| 0C | | | |
| 60C | | | |
| 0C | | | |
| 50C | | | |
Altitude during operation relating to sea level | | | | |
| On request: Negative ambient temperature down to -30 C (without condensation), installation altitudes between 2 000 m and 5 000 m | | | |
Dimensions | | | | |
Width | 15mm | 15mm | 15mm | 20mm |
Height | 73mm | 73mm | 73mm | 73mm |
Depth | 58mm | 58mm | 58mm | 58mm |
Weights | | | | |
Weight, approx. | 28g | 28g | 32g | 36g |