Mode of operation | |
Measuring principle | Radar level measurement |
Frequency | K-band (25.0 GHz) |
Minimum measuring range | 50 mm (2 inch) from end of antenna |
Maximum measuring range | 10 m (32.8 ft) or 20 m (66 ft) when used in a stilling pipe with dk ≥ 1.6 |
Output | |
HART | Version 5.1 |
| 4 ... 20 mA |
| ± 0.02 mA |
| - Programmable as high low or
hold (loss of echo) - NE 43 programmable
|
PROFIBUS PA | Profile 3.1 |
| 2 Analog Input (AI) |
FOUNDATION Fieldbus | H1 |
| Basic or LAS |
| ITK 5.2.0 |
| 2 Analog Input (AI) |
Performance (according to reference conditions IEC60770-1) | |
Maximum measured error | - > 500 mm from sensor reference point: 3 mm (0.118 inch)
- < 500 mm from sensor reference point: 25 mm (1 inch)
|
Influence of ambient temperature | < 0.003 %/K |
Rated operating conditions | |
Installation conditions | |
| Indoor/outdoor |
Ambient conditions (enclosure) | |
| -40 ... +80 °C (-40 ... +176 °F) |
| I |
| 4 |
Medium conditions | |
Dielectric constant εr | ≥ 3 (1.6 in stillpipe) |
Process temperature | -40 ... +80 °C (-40 ... +176 °F) at process connection (Is suitable for CIP at 120 °C for 1/2 hr max.) |
Process pressure | Up to 5 bar g (72 psi g) temperature dependent. See Pressure/Temperature curves for more information |
Design | |
Enclosure | |
| Aluminum, polyester powder-coated |
| 2 x M20 x 1.5 or 2 x Ѕ" NPT |
Degree of protection | Type 4X/NEMA 4X, Type 6/ NEMA 6, IP67, IP68 |
Weight | Approximately 3.3 kg (7.27 lb) |
Display (local) | Graphic local user interface including quick start wizard and echo profile display |
Antenna | |
| PVDF (Polyvinylidene fluoride) |
- Dimensions (nominal sizes)
| 2 inch (48 mm) |
Process connections | |
| 2" NPT [(Taper), ASME B1.20.1] 2" [(BSPT), EN 10226] 2" [(BSPP), EN ISO 228-1] |
Power supply | |
4 ... 20 mA/HART | Nominal 24 V DC (max. 30 V DC) with max. 550 О© |
PROFIBUS PA | |
FOUNDATION Fieldbus | |
Certificates and approvals | |
General | CSAUS/C, CE, FM, NE 21, RCM |
Radio | FCC, Industry Canada, and Europe ETSI EN 302-372, RCM |
Hazardous | |
| INMETRO Ex d ia mb IIC T4 Ga/Gb, Ex ia ta IIIC T100 °C Da |
- Increased Safety (Brazil)
| INMETRO Ex e ia mb IIC T4 Ga/Gb, Ex ia ta IIIC T100 °C Da |
- Intrinsically Safe (Brazil)
| INMETRO Ex ia IIC T4 Ga, Ex ia ta IIIC T100 °C Da |
- Explosion Proof (Canada/USA)
| CSA/FM Class I, Div. 1, Groups A, B, C, D; Class II, Div. 1, Groups E, F, G; Class III T4 |
- Intrinsically Safe (Canada/USA)
| CSA/FM Class I, Div. 1, Groups A, B, C, D; Class II, Div. 1, Groups E, F, G; Class III T4 |
- Non-incendive (Canada/USA)
| CSA/FM Class I, Div. 2, Groups A, B, C, D T5 |
- Flame Proof/Increased Safety
(China)
| Ex d ia mb IIC T4 Ga/Gb, Ex e ia mb IIC T4 Ga/Gb, Ex iaD 20 T90 IP67 DIP A20 TA90 єC |
- Intrinsically Safe (China)
| Ex ia IIC T4 Ga, Ex iaD 20 T90 IP67 DIP A20 TA90 єC |
| NEPSI Ex nA IIC T4 Gc |
- Intrinsically Safe (Europe)
| ATEX II 1G Ex ia IIC T4 Ga ATEX II 1D Ex ia ta IIC T100 °C Da |
- Non-sparking/Energy Limited (Europe)
| ATEX II 3G Ex nA IIC T4 Gc |
- Flame Proof (International/Europe)
| IECEx/ATEX II 1/2 GD, 1D, 2D, Ex d mb ia IIC T4 Ga/Gb, Ex ia ta IIC T100 °C Da |
- Increased Safety (International/Europe)
| IECEx/ATEX II 1/2 GD, 1D, 2D, Ex e mb ia IIC T4 Ga/Gb, Ex ia ta IIIC T100 °C Da |
- Intrinsically Safe (International)
| IECEx/ATEX II 1 G Ex ia IIC T4 Ga, IECEX/ATEX II 1D Ex ia ta IIC T100 °C Da |
- Explosion Proof (Russia/Kazakhstan)
| EAC Ex d |
- Increased Safety (Russia/Kazakhstan)
| EAC Ex e |
- Intrinsically Safe (Russia/Kazakhstan)
| EAC Ex ia |
| - Lloyd's Register of Shipping
- ABS Type Approval
- Bureau Veritas
|
Functional Safety | SIL-2 suitable in accordance with IEC 61508/61511 |
Programming | |
Intrinsically Safe Siemens handheld programmer | Infrared receiver |
- Approvals for handheld programmer
| IS model: ATEX II 1 GD Ex ia IIC T4 Ga Ex ia D 20 T135 °C Ta = -20 ... +50 °C CSA/FM Class I, II, III, Div. 1, Groups A, B, C, D, E, F, G, T6 Ta = +50 °C IECEx SIR 09.0073 |
Handheld communicator | HART communicator 375/475 |
PC | - SIMATIC PDM
- Emerson AMS
- SITRANS DTM (for connection into FDT, such as PACTware or
Fieldcare)
|
Display (local) | Graphic local user interface including quick start wizard and echo profile displays |