General features | |
Processors | - Intel Atom E660 1.3 GHz, 2 GB RAM
- Intel Atom E640 1.0 GHz, 1 GB RAM
|
Chipset | Intel Controller Hub EG20T |
NVRAM optional | 512 KB, of which 128 KB can be written within the buffer time |
Operating system | - Windows Embedded Standard 2009 preinstalled,
in combination with CF card of 2 GB or more, or solid-state drive, or hard drive (optional) - Windows XP Professional MUI (in connection with
solid-state drive or hard drive; MUI: Multi Language User Interface) (optional) - Windows Embedded Standard 7 32-bit, preinstalled,
in combination with CF card or solid-state drive (optional) - Windows 7 Ultimate MUI 32-bit (in combination with
solid-state drive; MUI: Multi Language User Interface) (optional) - Linux 1) (project-specific, on request)
Others on request project-specifically |
Power supply | - 24 V DC (20.4 V ... 28.8 V)
- Isolated
- With buffering of temporary power failures: max. 10 ms
- Line side switch
- With power failure indication by means of Power Fail signal
|
Drives | |
FlashDrive | Optional; replaceable, accessible, diagnosable |
Solid-state drive (SSD) | Optional - 80 GB SATA, 2.5"
- 160 GB SATA, 2.5"
|
CD/DVD/Floppy | Via USB (not included in scope of delivery) |
Ports | |
PROFINET | PROFINET RT via Standard Ethernet controller |
Ethernet | - 2 x 10/100/1000 Mbps (RJ 45)
- Two independent Intel Controllers:
Intel 82574L / Intel Controller Hub EG20T
With teaming function |
USB | V2.0, 3 x |
Serial | COM1 (V.24) |
Keyboard | Via USB (not included in scope of delivery) |
Mouse | Via USB (not included in scope of delivery) |
Monitoring functions | |
Temperature | - Processor temperature
- Motherboard
Messages can be evaluated by the application program |
Watchdog | - Monitoring of program execution
- Monitoring time can be parameterized in software
- Can be parameterized for a fault or restart
Messages can be evaluated by the application program |
Monitoring functions via the network | - DiagBase
- SIMATIC IPC DiagMonitor
Remote monitoring capability for: - Watchdog
- Temperature
- Mass memory monitoring (SMART)
- System/Ethernet monitoring (Heart Beat)
- Runtime meter
Communication: - Ethernet interface (SNMP protocol)
- OPC for integration in SIMATIC software
- Configuration of client/server architectures
- Structure of log files
|
Supply voltage | |
Supply voltage | 24 V DC |
Monitoring functions | |
Temperature | Yes |
Watchdog | Yes |
Mass storage | Yes |
Ambient conditions | |
Vibration load during operation | Requirements according to: IEC 61131-2, tested according to: IEC 60068-2-6, Test Fc 10-58: 0.0375 mm, 58-200: 9.8 m/s2, 10x /axis |
Shock loading during operation | Requirements according to: IEC 61131-2, tested according to: IEC 60068-2-27, Test Ea, 50 m/s2 |
Relative humidity | Tested in accordance with DIN IEC 68-78, DIN IEC 60068-2-30: 5% to 80% at 25 °C (no condensation) |
Maximum permissible installation angle +/- | 45° over vertical |
Ambient temperature during operation | 0 °C … +50° C in maximum configuration; no fan (19": 0 °C … +45 °C) |
Certifications & standards | |
Approvals | CE, cULus (508), marine approval available for 7"/9"/12" (GL, LRS, BV, DNV, ABS, ClassNK) |
EMC | CE, FFC A, 55022A, EN 61000-6-4, EN 61000-6-2 |