General information | | |
HW functional status | 01 | 01 |
Firmware version | V3.2 | V3.2 |
Engineering with | | |
| STEP 7 V5.5 or higher, Distributed Safety V5.4 SP4 | As of STEP 7 V5.5 with HSP 222 + Distributed Safety V5.4 SP4 |
Supply voltage | | |
Rated value (DC) | 24 V | 24 V |
permissible range, lower limit (DC) | 20.4 V | 20.4 V |
permissible range, upper limit (DC) | 28.8 V | 28.8 V |
external protection for power supply lines (recommendation) | MCB 24 V DC / 16 A with tripping characteristic Type B and C (see ET 200pro manual) | MCB 24 V DC / 16 A with tripping characteristic Type B and C (see ET 200pro manual) |
Load voltage L+ | | |
| 24 V | 24 V |
| 20.4 V | 20.4 V |
| 28.8 V | 28.8 V |
| Yes | Yes |
Input current | | |
Current consumption, typ. | 350 mA | 350 mA |
Current consumption (in no-load operation), typ. | 250 mA; Typical, current consumption for CPU in STOP state | 250 mA; Typical, current consumption for CPU in STOP state |
Inrush current, typ. | 2 A | 2 A |
IІt | 0.25 AІ·s; Typical | 0.25 AІ·s; Typical |
Power loss | | |
Power loss, typ. | 8.5 W | 8.5 W |
Memory | | |
Work memory | | |
| 512 kbyte | 1 536 kbyte |
| No | No |
Load memory | | |
| Yes | Yes |
| 8 Mbyte | 8 Mbyte |
| 10 y | 10 y |
Backup | | |
| Yes; Guaranteed by MMC (maintenance-free) | Yes; Guaranteed by MMC (maintenance-free) |
| Yes; Program and data | Yes; Program and data |
CPU processing times | | |
for bit operations, typ. | 0.05 µs | 0.025 µs |
for word operations, typ. | 0.09 µs | 0.03 µs |
for fixed point arithmetic, typ. | 0.12 µs | 0.04 µs |
for floating point arithmetic, typ. | 0.45 µs | 0.16 µs |
CPU-blocks | | |
Number of blocks (total) | 1 024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used. | 1 024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used. |
DB | | |
| 1 024; Number range: 1 to 16000 | 1 024; Number range: 1 to 16000 |
| 64 kbyte | 64 kbyte |
FB | | |
| 1 024; Number range: 0 to 7999 | 1 024; Number range: 0 to 7999 |
| 64 kbyte | 64 kbyte |
FC | | |
| 1 024; Number range: 0 to 7999 | 1 024; Number range: 0 to 7999 |
| 64 kbyte | 64 kbyte |
OB | | |
| 64 kbyte | 64 kbyte |
| 1; OB 1 | 1; OB 1 |
| 1; OB 10 | 1; OB 10 |
| 2; OB 20, 21 | 2; OB 20, 21 |
| 4; OB 32, 33, 34, 35 | 4; OB 32, 33, 34, 35 |
| 1; OB 40 | 1; OB 40 |
| 3; OB 55, 56, 57 | 3; OB 55, 56, 57 |
| 1; OB 61 | 1; OB 61 |
| 1; OB 100 | 1; OB 100 |
| 6; OB 80, 82, 83, 85, 86, 87 (OB83 only for centralized I/O and PROFINET IO) | 6; OB 80, 82, 83, 85, 86, 87 (OB83 only for centralized I/O and PROFINET IO) |
| 2; OB 121, 122 | 2; OB 121, 122 |
Nesting depth | | |
| 16 | 16 |
| 4 | 4 |
Counters, timers and their retentivity | | |
S7 counter | | |
| 256 | 256 |
Retentivity | | |
| Yes | Yes |
| 0 | 0 |
| 255 | 255 |
| Z 0 to Z 7 | Z 0 to Z 7 |
Counting range | | |
| Yes | Yes |
| 0 | 0 |
| 999 | 999 |
IEC counter | | |
| Unlimited (limited only by RAM capacity) | Unlimited (limited only by RAM capacity) |
S7 times | | |
| 256 | 256 |
Retentivity | | |
| Yes | Yes |
| 0 | 0 |
| 255 | 255 |
| No retentivity | No retentivity |
Time range | | |
| 10 ms | 10 ms |
| 9 990 s | 9 990 s |
IEC timer | | |
| Yes | Yes |
| SFB | SFB |
| Unlimited (limited only by RAM capacity) | Unlimited (limited only by RAM capacity) |
Data areas and their retentivity | | |
retentive data area in total | All, 128 KB max. | All, 128 KB max. |
Flag | | |
| 2 048 byte | 2 048 byte |
| Yes; MB 0 to MB 2047 | Yes; MB 0 to MB 2047 |
| MB 0 to MB 15 | MB 0 to MB 15 |
| 8 | 8 |
Data blocks | | |
| Yes; via non-retain property on DB | Yes; via non-retain property on DB |
| Yes | Yes |
Local data | | |
| 32 768 byte; Max. 2048 bytes per block | 32 768 byte; Max. 2048 bytes per block |
Address area | | |
I/O address area | | |
| 2 048 byte | 2 048 byte |
| 2 048 byte | 2 048 byte |
of which distributed | | |
| 2 048 byte | 2 048 byte |
| 2 048 byte | 2 048 byte |
Process image | | |
| 2 048 byte | 2 048 byte |
| 2 048 byte | 2 048 byte |
| 128 byte | 128 byte |
| 128 byte | 128 byte |
Subprocess images | | |
| 1; With PROFINET IO, the length of the user data is limited to 1600 bytes | 1; With PROFINET IO, the length of the user data is limited to 1600 bytes |
Digital channels | | |
| 16 384 | 16 384 |
| 128 | 128 |
| 16 384 | 16 384 |
| 64 | 64 |
Analog channels | | |
| 1 024 | 1 024 |
| 64 | 64 |
| 1 024 | 1 024 |
| 64 | 64 |
Hardware configuration | | |
Integrated power supply | No | No |
Number of DP masters | | |
| 1 | 1 |
Rack | | |
| 1 | 1 |
| 16; Expansion width max. 1 m | 16; Expansion width max. 1 m |
Time of day | | |
Clock | | |
| Yes | Yes |
| Yes | Yes |
| 6 wk; At 40 °C ambient temperature | 6 wk; At 40 °C ambient temperature |
| 10 s; Typ.: 2 s | 10 s; Typ.: 2 s |
Operating hours counter | | |
| 1 | 1 |
| 0 | 0 |
| 0 to 2^31 hours (when using SFC 101) | 0 to 2^31 hours (when using SFC 101) |
| 1 h | 1 h |
| Yes; Must be restarted at each restart | Yes; Must be restarted at each restart |
Clock synchronization | | |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
| Yes; With DP slave only slave clock | Yes; With DP slave only slave clock |
| Yes | Yes |
| Yes; As client | Yes; As client |
Interfaces | | |
Number of industrial Ethernet interfaces | 1 | 1 |
Number of PROFINET interfaces | 1 | 1 |
Number of wireless interfaces | 0 | 0 |
1. Interface | | |
Interface type | Integrated RS 485 interface | Integrated RS 485 interface |
Physics | RS 485/connection: 2 x M12 b-coded | RS 485/connection: 2 x M12 b-coded |
Isolated | Yes | Yes |
Power supply to interface (15 to 30 V DC), max. | May only be used for external terminating resistor | May only be used for external terminating resistor |
Functionality | | |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
| No | No |
MPI | | |
| 12 Mbit/s | 12 Mbit/s |
Services | | |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
| No | No |
| Yes | Yes |
DP master | | |
| 12 Mbit/s | 12 Mbit/s |
| 124 | 124 |
Services | | |
| Yes | Yes |
| Yes | Yes |
| No | No |
| Yes; I blocks only | Yes; I blocks only |
| Yes | Yes |
| No | No |
| Yes; Connection configured on one side only | Yes; Connection configured on one side only |
| Yes | Yes |
| Yes; OB 61 - isochronous mode is possible either on DP or PROFINET IO (not simultaneously) | Yes; OB 61 - isochronous mode is possible either on DP or PROFINET IO (not simultaneously) |
| Yes | Yes |
| Yes | Yes |
| Yes; As subscriber | Yes; As subscriber |
| Yes | Yes |
Address area | | |
| 2 048 byte | 2 048 byte |
| 2 048 byte | 2 048 byte |
User data per DP slave | | |
| 244 byte | 244 byte |
| 244 byte | 244 byte |
DP slave | | |
| 12 Mbit/s | 12 Mbit/s |
| Yes; only with passive interface | Yes; only with passive interface |
| 32 | 32 |
| 32 byte | 32 byte |
Services | | |
| Yes; with interface active | Yes; with interface active |
| No | No |
| No | No |
| Yes | Yes |
| No | No |
| Yes; Connection configured on one side only | Yes; Connection configured on one side only |
| Yes | Yes |
| No | No |
Transfer memory | | |
| 244 byte | 244 byte |
| 244 byte | 244 byte |
2. Interface | | |
Interface type | PROFINET | PROFINET |
Physics | Ethernet (2 x M12 d-coded; 1 x RJ45) | Ethernet (2 x M12 d-coded; 1 x RJ45) |
Isolated | Yes; Galvanic isolation for P3 is implemented in IM154-8, for P1 and P2 in CM | Yes; Galvanic isolation for P3 is implemented in IM154-8, for P1 and P2 in CM |
automatic detection of transmission rate | Yes; 10/100 Mbit/s | Yes; 10/100 Mbit/s |
Autonegotiation | Yes | Yes |
Autocrossing | Yes | Yes |
Change of IP address at runtime, supported | Yes | Yes |
Interface types | | |
| 3 | 3 |
| Yes | Yes |
Media redundancy | | |
| Yes | Yes |
| 200 ms; PROFINET MRP | 200 ms; PROFINET MRP |
| 50 | 50 |
Functionality | | |
| No | No |
| Yes; Also simultaneously with IO-Device functionality | Yes; Also simultaneously with IO-Device functionality |
| Yes; Also simultaneously with IO Controller functionality | Yes; Also simultaneously with IO Controller functionality |
| Yes | Yes |
| No | No |
| No | No |
| Yes; Via TCP/IP, ISO on TCP, and UDP | Yes; Via TCP/IP, ISO on TCP, and UDP |
| Yes | Yes |
PROFINET IO Controller | | |
| 100 Mbit/s | 100 Mbit/s |
Services | | |
| Yes | Yes |
| Yes | Yes |
| Yes; With loadable FBs, max. configurable connections: 14, max. number of instances: 32 | Yes; With loadable FBs, max. configurable connections: 14, max. number of instances: 32 |
| Yes; OB 61 - isochronous mode is possible either on DP or PROFINET IO (not simultaneously) | Yes; OB 61 - isochronous mode is possible either on DP or PROFINET IO (not simultaneously) |
| Yes; Via TCP/IP, ISO on TCP, and UDP | Yes; Via TCP/IP, ISO on TCP, and UDP |
| Yes | Yes |
| Yes | Yes |
| 32 | 32 |
| 128 | 128 |
| 64 | 64 |
| 64 | 64 |
| 128 | 128 |
| 61 | 61 |
| 128 | 128 |
| 128 | 128 |
| Yes | Yes |
| 8 | 8 |
| Yes | Yes |
| 8 | 8 |
| Yes | Yes |
| 250 Ојs, 500 Ојs,1 ms; 2 ms, 4 ms (not in the case of IRT with "high flexibility" option) | 250 Ојs, 500 Ојs,1 ms; 2 ms, 4 ms (not in the case of IRT with "high flexibility" option) |
| 250 µs to 512 ms (depending on the operating mode, see "IM 154-8 CPU Interface Module" operating instructions for more details) | 250 µs to 512 ms (depending on the operating mode, see "IM 154-8 CPU Interface Module" operating instructions for more details) |
Address area | | |
| 2 048 byte | 2 048 byte |
| 2 048 byte | 2 048 byte |
| 1 024 byte | 1 024 byte |
PROFINET IO Device | | |
Services | | |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
| Yes; With loadable FBs, max. configurable connections: 14, max. number of instances: 32 | Yes; With loadable FBs, max. configurable connections: 14, max. number of instances: 32 |
| No | No |
| Yes; Via TCP/IP, ISO on TCP, and UDP | Yes; Via TCP/IP, ISO on TCP, and UDP |
| Yes | Yes |
| Yes; With SFB 73 / 74 prepared for loadable PROFIenergy standard FB for I-Device | Yes; With SFB 73 / 74 prepared for loadable PROFIenergy standard FB for I-Device |
| Yes | Yes |
| 2 | 2 |
Transfer memory | | |
| 1 440 byte; Per IO Controller with shared device | 1 440 byte; Per IO Controller with shared device |
| 1 440 byte; Per IO Controller with shared device | 1 440 byte; Per IO Controller with shared device |
Submodules | | |
| 64 | 64 |
| 1 024 byte | 1 024 byte |
PROFINET CBA | | |
| Yes | Yes |
| Yes | Yes |
Open IE communication | | |
| 8 | 8 |
| 0, 20, 21, 23, 25, 80, 102, 135, 161, 443, 8080, 34962, 34963, 34964, 65532, 65533, 65534, 65535 | 0, 20, 21, 23, 25, 80, 102, 135, 161, 443, 8080, 34962, 34963, 34964, 65532, 65533, 65534, 65535 |
| Yes | Yes |
Protocols | | |
Open IE communication | | |
| Yes; via integrated PROFINET interface and loadable FBs | Yes; via integrated PROFINET interface and loadable FBs |
| 32 768 byte; 1460 bytes with connection type 01H; 32768 bytes with connection type 11H | 32 768 byte; 1460 bytes with connection type 01H; 32768 bytes with connection type 11H |
| Yes | Yes |
| Yes | Yes |
| 32 768 byte | 32 768 byte |
| Yes | Yes |
| 1 472 byte | 1 472 byte |
Web server | | |
| Yes | Yes |
| 5 | 5 |
Isochronous mode | | |
Isochronous operation (application synchronized up to terminal) | Yes; Via PROFIBUS DP or PROFINET interface | Yes; Via PROFIBUS DP or PROFINET interface |
Communication functions | | |
PG/OP communication | Yes | Yes |
Global data communication | | |
| Yes | Yes |
| 8 | 8 |
| 8 | 8 |
| 8 | 8 |
| 8 | 8 |
| 22 byte | 22 byte |
| 22 byte | 22 byte |
S7 basic communication | | |
| Yes | Yes |
| 76 byte | 76 byte |
| 76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server) | 76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server) |
S7 communication | | |
| Yes | Yes |
| Yes | Yes |
| Yes; via integrated PROFINET interface and loadable FBs | Yes; via integrated PROFINET interface and loadable FBs |
| See online help of STEP 7 (shared parameters of the SFBs/FBs and of the SFCs/FCs of S7 Communication) | See online help of STEP 7 (shared parameters of the SFBs/FBs and of the SFCs/FCs of S7 Communication) |
Web server | | |
| Yes | Yes |
PROFINET CBA (at set setpoint communication load) | | |
| 50 % | 50 % |
| 32 | 32 |
| 30 | 30 |
| 1 000 | 1 000 |
| 4 000 byte | 4 000 byte |
| 4 000 byte | 4 000 byte |
| 500 | 500 |
| 4 000 byte | 4 000 byte |
| 1 400 byte | 1 400 byte |
Remote interconnections with acyclic transmission | | |
| 500 ms | 500 ms |
| 100 | 100 |
| 100 | 100 |
| 2 000 byte | 2 000 byte |
| 2 000 byte | 2 000 byte |
| 1 400 byte | 1 400 byte |
Remote interconnections with cyclic transmission | | |
| 1 ms | 1 ms |
| 200 | 200 |
| 200 | 200 |
| 2 000 byte | 2 000 byte |
| 2 000 byte | 2 000 byte |
| 450 byte | 450 byte |
HMI variables via PROFINET (acyclic) | | |
| 3; 2x PN OPC/1x iMap | 3; 2x PN OPC/1x iMap |
| 500 ms | 500 ms |
| 200 | 200 |
| 2 000 byte | 2 000 byte |
PROFIBUS proxy functionality | | |
| Yes | Yes |
| 16 | 16 |
| 240 byte; Slave-dependent | 240 byte; Slave-dependent |
Number of connections | | |
| 16 | 16 |
| 15 | 15 |
| 1 | 1 |
| 1 | 1 |
| 15 | 15 |
| 15 | 15 |
| 1 | 1 |
| 1 | 1 |
| 15 | 15 |
| 14 | 14 |
| 0 | 0 |
| 0 | 0 |
| 14 | 14 |
| X1 as MPI: max. 10; X1 as DP master: max. 24; X1 as DP slave (active): max. 14; X2 as PROFINET: 24 max. | X1 as MPI: max. 10; X1 as DP master: max. 24; X1 as DP slave (active): max. 14; X2 as PROFINET: 24 max. |
S7 message functions | | |
Number of login stations for message functions, max. | 16; Depending on the configured connections for PG/OP and S7 basic communication | 16; Depending on the configured connections for PG/OP and S7 basic communication |
Process diagnostic messages | Yes | Yes |
simultaneously active Alarm-S blocks, max. | 300 | 300 |
Test commissioning functions | | |
Status block | Yes; Up to 2 simultaneously | Yes; Up to 2 simultaneously |
Single step | Yes | Yes |
Number of breakpoints | 4 | 4 |
Status/control | | |
| Yes | Yes |
| Inputs, outputs, memory bits, DB, times, counters | Inputs, outputs, memory bits, DB, times, counters |
| 30 | 30 |
| 30 | 30 |
| 14 | 14 |
Forcing | | |
| Yes | Yes |
| I/O | I/O |
| 10 | 10 |
Diagnostic buffer | | |
| Yes | Yes |
| 500; Only the last 100 entries are retentive at power on/off | 500; Only the last 100 entries are retentive at power on/off |
| No | No |
| 10 | 10 |
Potential separation | | |
between backplane bus and electronics | No | No |
between backplane bus and all other circuit components | Yes | Yes |
between supply and all other circuits | Yes | Yes |
Isolation | | |
Isolation tested with | In general, 707 V DC (type test), Ethernet interface 1 500 V AC (for P1 and P2 on CM, for P3 on IM) | In general, 707 V DC (type test), Ethernet interface 1 500 V AC (for P1 and P2 on CM, for P3 on IM) |
Degree and class of protection | | |
IP degree of protection | IP65/67 | IP65/67 |
Standards, approvals, certificates | | |
CE mark | Yes | Yes |
CSA approval | No | No |
cULus | Yes | Yes |
FM approval | No | No |
RCM (formerly C-TICK) | Yes | Yes |
Highest safety class achievable in safety mode | | |
| PLe | PLe |
| SIL 3 | SIL 3 |
Configuration | | |
Configuration software | | |
| Yes; V5.5 or higher | Yes; V5.5 or higher |
Programming | | |
| see instruction list | see instruction list |
| 8 | 8 |
| see instruction list | see instruction list |
| see instruction list | see instruction list |
Programming language | | |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
Know-how protection | | |
| Yes | Yes |
| Yes; With S7 block Privacy | Yes; With S7 block Privacy |
Dimensions | | |
Width | 135 mm | 135 mm |
Height | 130 mm | 130 mm |
Depth | 65 mm; 60 mm without cover for RJ45 socket; 65 mm with cover for RJ45 socket | 65 mm; 60 mm without cover for RJ45 socket; 65 mm with cover for RJ45 socket |
Weights | | |
Weight, approx. | 720 g | 720 g |