Mode of operation | |
Measuring principle | Radar level measurement |
Frequency | 78 GHz FMCW |
Minimum detectable distance | 400 mm (15.75 inch) from sensor reference point |
Maximum measuring range1) | - 40 m (131 ft) version
- 100 m (328 ft) version
|
Output | |
Analog output | 4 ... 20 mA |
Communications | - HART
- Optional: PROFIBUS PA
- Optional: FOUNDATION Fieldbus
|
Fail-safe | - Programmable as high, low or hold (Loss of Echo)
- NE43 programmable
|
Performance (according to reference conditions IEC60770-1) | |
Maximum measured error (including hysteresis and non-repeatability)2) | 5 mm (0.2 inch) |
Rated operating conditions (according to reference conditions IEC60770-1) | |
Installation conditions | |
| Indoor/outdoor |
Ambient conditions (enclosure) | |
| -40 ... +80 °C (-40 ... +176 °F) |
| I |
| 4 |
Medium conditions | |
Dielectric constant Оµr | > 1.6 |
Process temperature and pressure | See chart below |
Design | |
Enclosure | |
| 316L/1.4404 stainless steel |
| M20 x 1.5, or Ѕ" NPT via adapter |
| 1/8" NPT, 30 cfm at max. 100 psi |
| - 40 m version: PEI
- 100 m version: PEEK
|
| Damage to lens could result from continuous purging/cleaning (due to abrasive solids). Recommended to purge/clean only a few seconds every hour. |
| Type 4X/NEMA 4X, Type 6/NEMA 6, IP68 |
| 3.15 kg (6.94 lb) including 3 inch flange |
- Optional local display interface
| Graphic LCD, with bar graph representing level |
Process connections | |
- Universal flat-faced flanges3)
| - 3, 4, 6 inch/80, 100, 150 mm, 304 stainless steel
- 3, 4, 6 inch/80, 100, 150 mm, 316L/1.4404 or 316L/1.4435 stainless steel
|
| 3, 4, 6 inch/80, 100, 150 mm, polyurethane powder-coated cast aluminum |
Power supply | |
4 ... 20 mA/HART | Nominal 24 V DC (max. 30 V DC) with max. 550 О© |
PROFIBUS PA/FOUNDATION Fieldbus | 13.5 mA 9 ... 32 V DC, per IEC 61158-2 |
Certificates and approvals | |
General | CSAUS/C, CE, FM |
Radio | Europe (R&TTE), FCC, Industry Canada, RCM |
Hazardous | |
| IECEx SIR 09.0149X ATEX II 1D, 1/2D, 2D Ex ta IIIC T139 єC Da ATEX II 3G Ex nA II T4 Gc Ex nL IIC T4 Gc |
| FM/CSA Class II, Div. 1, Groups E, F, G Class III T4 FM/CSA Class I, Div. 2, Groups A, B, C, D, T4 |
| NEPSI Ex nA II T4 Ex nL IIC T4 DIP A20 TA, T139 єC |
| INMETRO Ex na IIC T4 Gc Ex ta IIIC T139 єC Da |
Programming | |
Intrinsically Safe Siemens handheld programmer | Infrared receiver |
- Approvals for handheld programmer
| IS model: ATEX II 1GD Ex ia IIC T4 Ga Ex iaD 20 T135 °C Ta = -20 ... +50 °C CSA/FM Class I, II, and III, Div. 1, Groups A, B, C, D, E, F, G, T6 Ta = 50 °C |
Handheld communicator | HART communicator 375/475 |
PC | SIMATIC PDM, AMS, PACTware |
Display (local) | Graphic local user interface including quick start wizard and echo profile displays |