Type of current supply | 300 W, input: 85-264 V, output:DC 24 |
Electrical data Input | |
Voltage curve at input | AC single phase |
Supply voltage at AC | 85 ... 264 V |
Supply voltage 1 at AC Rated value | 230 V |
Design of input wide range input | Yes |
Overvoltage category | Category II (20 A rated branch circuit) |
Buffering time for rated value of the output current in the event of power failure minimum | 16 ms |
Line frequency | |
| 50 Hz |
| 60 Hz |
Line frequency | 47 ... 63 Hz |
Input current at rated input voltage 230 V Rated value | 1.8 A |
Current limitation of inrush current at 25 °C maximum | 40 A |
Fuse protection type at input | replaceable |
Electrical data Output | |
Voltage curve at output | Controlled, isolated DC voltage |
Output voltage at DC Rated value | 24 V |
Display version for normal operation | Green LED for 24 V ok and fault LED |
Behavior of the output voltage when switching on | Overshoot of Ua < 5 % |
ON-delay time maximum | 1.5 s |
Voltage increase time of the output voltage maximum | 15 ms |
Output current | |
| 12.5 A |
| 0 ... 12.5 A |
Supplied active power typical | 300 W |
Product feature Parallel switching of channels | Yes |
Number of parallel-switched resources for increasing the power | 2 |
Efficiency in percent | 87 % |
Power loss [W] | 39 W |
Electrical data Closed-loop control | |
Relative overall tolerance of the voltage | 2 % |
Residual ripple maximum | 0.36 V |
Voltage peak maximum | 240 V |
Relative control precision of the output voltage | |
| 0.2 % |
| 0.4 % |
| 3.25 % |
| 0.8 % |
Setting time | |
| 2 ms |
| 2 ms |
Electrical data Protection and monitoring | |
Design of the overvoltage protection at output | < 37 V |
Response value current limitation typical | 1.15 A |
Property of the output Short-circuit proof | Yes |
Design of short-circuit protection | Electronic shutdown, automatic restart |
Electrical data Safety | |
Galvanic isolation between entrance and outlet | Yes |
Galvanic isolation | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 |
Operating resource protection class | Class I |
Leakage current | |
| 3 mA |
| 0.858 mA |
Interfaces | |
Type of electrical connection | |
| IEC plug |
| for plugging into basic device or screw terminal in accordance with specification |
Design, dimensions and weight | |
Width | 446 mm |
Height | 44 mm |
Depth | 140 mm |
Net weight | 1.7 kg |
Product feature of the enclosure housing for side-by-side mounting | No |
Mounting type | Plugged into the basic unit or rack mounted |
| Yes |
| No |
| No |
| No |
Permitted ambient conditions | |
Ambient temperature | |
| 60 °C |
| -25 ... +70 °C |
| -25 ... +70 °C |
| Operation with integral fan, non-replaceable |
Environmental category acc. to IEC 60721 | Climate class 3K3, without condensation |
Protection class IP | IP20 |
Standards, specifications, approvals | |
Standard | |
| UL 60950-1, CSA C22.2 No. 60950-1 |
| EN 55022 (Class B) |
| EN 61000-6-2 |
Certificate of suitability | EN 55022, EN 61000-6-4 |
| Yes |
| Yes |
| No |
| No |
| No |
| No |
| No |