General information | | | |
Product type designation | CP 340 | CP 340 | CP 340 |
Supply voltage | | | |
Rated value (DC) | | A power supply according to EN 50155 shall be used | |
| No; Power supply via backplane bus 5V | No; Power supply via backplane bus 5V | No; Power supply via backplane bus 5V |
Input current | | | |
from backplane bus 5 V DC, max. | 165 mA | 165 mA | 165 mA |
Power loss | | | |
Power loss, typ. | 0.6 W | 0.6 W | 0.6 W |
Power loss, max. | 0.85 W | 0.85 W | 0.85 W |
Interfaces | | | |
Number of interfaces | 1; Isolated | 1; Isolated | 1; Isolated |
Interface physics, RS 232C (V.24) | Yes | Yes | |
Interface (physical) RS 422/485 (X.27) | | | Yes |
Transmission rate, min. | 2.4 kbit/s | 2.4 kbit/s | 2.4 kbit/s |
Transmission rate, max. | 19.2 kbit/s | 19.2 kbit/s | 19.2 kbit/s |
Point-to-point | | | |
| 15 m | 15 m | 1 200 m |
| HP-Deskjet, HP-Laserjet, IBM-Proprinter, user-defined | HP-Deskjet, HP-Laserjet, IBM-Proprinter, user-defined | HP-Deskjet, HP-Laserjet, IBM-Proprinter, user-defined |
| 9-pin sub D connector | 9-pin sub D connector | 15-pin sub D socket |
Integrated protocol driver | | | |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| No | No | No |
| No | No | No |
Telegram length, max. | | | |
| 1 024 byte | 1 024 byte | 1 024 byte |
| 1 024 byte | 1 024 byte | 1 024 byte |
Transmission rate, RS 422/485 | | | |
| | | 19.2 kbit/s |
| | | 9.6 kbit/s |
| | | 9.6 kbit/s |
Transmission speed, RS 232 | | | |
| 19.2 kbit/s | 19.2 kbit/s | |
| 9.6 kbit/s | 9.6 kbit/s | |
| 9.6 kbit/s | 9.6 kbit/s | |
Standards, approvals, certificates | | | |
CE mark | Yes | Yes | Yes |
UL approval | Yes; File E239877 | Yes; File E239877 | Yes; File E239877 |
FM approval | Yes; CofC 3028431 | Yes; CofC 3028431 | Yes; CofC 3028431 |
RCM (formerly C-TICK) | Yes | Yes | Yes |
KC approval | Yes | Yes | Yes |
EAC (formerly Gost-R) | Yes | Yes | Yes |
Railway application | | | |
| | Yes; Sections 4, 5 and 12; no further agreements apply; T1, Category 1, Class A/B | |
Ambient conditions | | | |
Ambient temperature during operation | | | |
| -25 °C; = Tmin | -25 °C; = Tmin | -25 °C; = Tmin |
| 70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use | 60 °C; = Tmax; the rated temperature range of -25 ... +55 °C (T1) applies for the use on railway vehicles according to EN50155 | 60 °C; = Tmax |
Ambient temperature during storage/transportation | | | |
| -40 °C | -40 °C | -40 °C |
| 70 °C | 70 °C | 70 °C |
Altitude during operation relating to sea level | | | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Relative humidity | | | |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Resistance | | | |
Use in stationary industrial systems | | | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Software | | | |
Block | | | |
| 2 700 byte; Data communication, sending and receiving | 2 700 byte; Data communication, sending and receiving | 2 700 byte; Data communication, sending and receiving |
Connection method | | | |
Power supply | Over backplane bus | Over backplane bus | Over backplane bus |
Dimensions | | | |
Width | 40 mm | 40 mm | 40 mm |
Height | 125 mm | 125 mm | 125 mm |
Depth | 120 mm | 120 mm | 120 mm |
Weights | | | |
Weight, approx. | 300 g | 300 g | 300 g |