Supply voltage | |
Load voltage L+ | |
| 24 V |
| No |
Input current | |
From load voltage L+ (no load), typ. | 100 mA |
from backplane bus 3.3 V DC, max. | 28 mA |
Power loss | |
Power loss, typ. | 3.5 W |
Digital outputs | |
Number of digital outputs | 4 |
Short-circuit protection | Yes |
Limitation of inductive shutdown voltage to | Typ. (2L+) -47 V |
Controlling a digital input | No |
Switching capacity of the outputs | |
| 10 W |
Load resistance range | |
| 12 Ω |
| 1 kΩ |
Output voltage | |
| L+ (-2,0 V), current sourcing switch: L+ (-1,5 V), voltage drop on current sinking switch: max. 0.5 V |
Output current | |
| 2 A |
| 20 mA |
| 2.4 A |
| 0.5 mA; Current-sourcing and current-sinking switches |
Parallel switching of two outputs | |
| No |
| No |
Switching frequency | |
| 30 Hz; Symmetrical |
| 0.1 Hz; Symmetrical |
| 10 Hz; Symmetrical |
Total current of the outputs | |
| 6 A |
Total current of the outputs (per group) | |
horizontal installation | |
| 6 A |
| 5 A |
| 4 A |
vertical installation | |
| 4 A |
Cable length | |
| 500 m |
| 500 m |
Interrupts/diagnostics/status information | |
Diagnostic functions | Yes |
Diagnostic messages | |
| Yes |
| Yes |
Diagnostics indication LED | |
| Yes |
| Yes |
Potential separation | |
Potential separation digital outputs | |
| No |
| Yes |
| No |
Isolation | |
tested with | |
| 2 545 V DC |
Standards, approvals, certificates | |
Highest safety class achievable in safety mode | |
| 4 |
| PLe |
| SIL 3 |
Ambient conditions | |
Ambient temperature during operation | |
| -25 °C |
| 60 °C |
| -25 °C |
Altitude during operation relating to sea level | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) |
Relative humidity | |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Resistance | |
Use in stationary industrial systems | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Dimensions | |
Width | 30 mm |
Height | 81 mm |
Depth | 52 mm |
Weights | |
Weight, approx. | 85 g |