General information | | |
Vendor identification (VendorID) | 806Ah | |
Supply voltage | | |
Mains buffering | | |
| 20 ms | 20 ms |
Input current | | |
from supply voltage 1L+, max. | 200 mA | 200 mA |
Power loss | | |
Power loss, typ. | 3.3 W | 3.3 W |
Address area | | |
Addressing volume | | |
| 244 byte | 244 byte |
| 244 byte | 244 byte |
Interfaces | | |
Interface physics, RS 485 | Yes; 9-pin sub D socket | Yes |
PROFIBUS DP | | |
| 80 mA | |
| 12 Mbit/s; 9,6 / 19,2 / 45,45 / 93,75 / 187,5 / 500 kbit/s; 1,5 / 3 / 6 / 12 Mbit/s | 12 Mbit/s |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
Protocols | | |
Supports protocol for PROFINET IO | | No |
PROFIBUS DP | Yes | Yes |
Protocols (Ethernet) | | |
| | No |
Isochronous mode | | |
Isochronous operation (application synchronized up to terminal) | No | Yes |
Interrupts/diagnostics/status information | | |
Alarms | Yes | Yes |
Diagnostic functions | Yes | Yes |
Diagnostics indication LED | | |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
Potential separation | | |
between backplane bus and electronics | No | No |
between electronic block and PROFIBUS DP | Yes | Yes |
between supply voltage and electronics | No | No |
Permissible potential difference | | |
between different circuits | 75 V DC/60 V AC | 75 V DC/60 V AC |
Isolation | | |
Isolation tested with | 500 V DC | 500 V DC |
Standards, approvals, certificates | | |
CE mark | Yes | Yes |
UL approval | | Yes |
Ambient conditions | | |
Ambient temperature during operation | | |
| -25 °C; = Tmin | -25 °C; = Tmin |
| 70 °C; = Tmax | 60 °C; = Tmax |
Altitude during operation relating to sea level | | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Relative humidity | | |
| 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation | 100 %; RH incl. condensation/frost permitted (no commissioning in bedewed state) |
Resistance | | |
Use in stationary industrial systems | | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| Yes; Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Dimensions | | |
Width | 45 mm | 45 mm |
Height | 119.5 mm | 119.5 mm |
Depth | 75 mm | 75 mm |
Weights | | |
Weight, approx. | | 150 g |