All racks included:

  • Mounting rail with threaded bolts for fixing the modules and lateral cutouts for mounting the rack
  • Plastic parts serve as guides when swinging the modules into place
  • Connection for protective conductors
  • Backplane bus with plug-in connections
UR1 for central controllers
  • 18 single-width slots
  • Always required: Power module (PS) and one CPU
  • Can be expanded centrally (up to 5 m) and in distributed configuration (up to 600 m)
  • The following are required when expanded:
    • Interface modules (send IMs); max. 6 interface modules can be plugged in
  • Up to 21 expansion units can be connected
UR2 for central controllers
  • 9 single-width slots
  • Always required: Power module (PS) and one CPU
  • Can be expanded centrally (up to 5 m) and in distributed configuration (up to 600 m)
  • The following are required when expanded:
    • Interface modules (send IMs); max. 6 interface modules can be plugged in
  • Up to 21 expansion units can be connected
CR2 for central controllers
  • 18 single-width slots; 2 segments with 8 or 10 slots
  • Always required: Power module (PS) und 2 CPUs
  • Can be expanded centrally (up to 5 m) and in distributed configuration (up to 600 m)
  • The following are required when expanded:
    • Interface modules (send IMs). Max. 6 interface modules can be plugged in
  • Up to 21 expansion units can be connected.
  • 2 CPUs can be operated next to each other, each with its own I/O:
    2 P bus segments with 10 or 8 slots for 1 CPU each with its own I/O
  • C bus throughout: C bus nodes can be addressed from both segments.
CR3 for central controllers
  • 4 single-width slots
  • Always required: Power module (PS) and one CPU
  • Can be expanded centrally (up to 5 m) and in distributed configuration (up to 600 m)
  • The following are required when expanded:
    • Interface modules (send IMs); max. 2 interface modules can be plugged in
  • Up to 16 expansion units can be connected
  • C bus and P bus throughout
UR2-H
  • 18 single-width slots; 2 segments with 9 slots each
  • Always required: 2 power modules (PS) und 2 CPUs
  • Can be expanded centrally (up to 5 m) and in distributed configuration (up to 600 m)
  • The following are required when expanded:
    • Interface modules (send IMs); max. 6 interface modules can be plugged in
  • Up to 21 expansion units can be connected
  • 2 CPUs can be operated next to each other, each with its own I/O:
    2 P bus segments and 2 C bus segments with 9 slots each for 1 CPU each with its own I/O
  • C bus throughout: C bus nodes can be addressed from both segments
UR1 for expansion units
  • 18 single-width slots
  • Always required: Interface module (receive IM)
UR2 for expansion units
  • 9 single-width slots
  • Always required: Interface module (receive IM)
ER1 for expansion units
  • 18 single-width slots
  • Always required: Interface module (receive IM)
  • P bus with restricted functionality:
    • No alarm processing
    • No battery backup of the plugged-in modules
    • No 24 V DC supply of the modules
  • No C bus
  • The following can be used:
    • SM modules
    • Receive IM
    • Power supply module
ER2 for expansion units
  • 9 single-width slots
  • Always required: Interface module (receive IM)
  • P bus with restricted functionality:
    • No alarm processing
    • No battery backup of the plugged-in modules
    • No 24 V DC supply of the modules
  • No C bus
  • The following can be used:
    • SM modules
    • Receive IM
    • Power supply module