Supply voltage | | | | |
Load voltage L+ | | | | |
| 24 V | 24 V | 24 V; A power supply according to EN 50155 shall be used for railway applications | 24 V |
| Yes | Yes | Yes | Yes |
Input current | | | | |
from load voltage L+ (without load), max. | 240 mA | 290 mA | 135 mA | 340 mA |
from backplane bus 5 V DC, max. | 60 mA | 120 mA | 60 mA | 100 mA |
Power loss | | | | |
Power loss, typ. | 3 W | 3 W | 3 W | 6 W |
Analog outputs | | | | |
Number of analog outputs | 4 | 4; Isochronous mode | 2 | 8; 4 @ +70 °C |
Voltage output, short-circuit protection | Yes | Yes | Yes | Yes |
Voltage output, short-circuit current, max. | 25 mA | 40 mA | 25 mA | 25 mA |
Current output, no-load voltage, max. | 18 V | 18 V | 18 V | 18 V |
Output ranges, voltage | | | | |
| Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes |
Output ranges, current | | | | |
| Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes |
Load impedance (in rated range of output) | | | | |
| 1 kΩ | 1 kΩ | 1 kΩ | 1 kΩ |
| 1 µF | 1 µF | 1 µF | 1 µF |
| 500 Ω | 500 Ω | 500 Ω | 500 Ω |
| 10 mH | 1 mH | 10 mH | 10 mH |
Cable length | | | | |
| 200 m | 200 m | 200 m | 200 m |
Analog value generation for the outputs | | | | |
Integration and conversion time/resolution per channel | | | | |
| 12 bit; ±10 V, ±20 mA, 4 mA to 20 mA, 1 V to 5 V: 11 bit + sign; 0 V to 10 V, 0 mA to 20 mA: 12 bit | 16 bit | 12 bit; ±10 V, ±20 mA, 4 mA to 20 mA, 1 V to 5 V: 11 bit + sign; 0 V to 10 V, 0 mA to 20 mA: 12 bit | 12 bit; ±10 V, ±20 mA, 4 mA to 20 mA, 1 V to 5 V: 11 bit + sign; 0 V to 10 V, 0 mA to 20 mA: 12 bit |
| 0.8 ms | 200 µs; in isochronous mode 640 µs | 0.8 ms | 0.8 ms |
Settling time | | | | |
| 0.2 ms | 0.2 ms | 0.2 ms | 0.2 ms |
| 3.3 ms | 3.3 ms | 3.3 ms | 3.3 ms |
| 0.5 ms; 0.5 ms (1 mH); 3.3 ms (10 mH) | 0.5 ms | 0.5 ms; 0.5 ms (1 mH); 3.3 ms (10 mH) | 0.5 ms; 0.5 ms (1 mH); 3.3 ms (10 mH) |
Errors/accuracies | | | | |
Operational error limit in overall temperature range | | | | |
| 0.5 %; ±0.6 % @ < 0 °C or > 60 °C | 0.12 % | 0.5 %; ±0.6 % @ < 0 °C or > 60 °C | 0.5 %; ±0.6 % @ < 0 °C or > 60 °C |
| 0.6 %; ±0.7 % @ < 0 °C or > 60 °C | 0.18 % | 0.6 %; /-0.7% @ < 0 °C or > 60 °C | 0.6 %; ±0.7 % @ < 0 °C or > 60 °C |
Basic error limit (operational limit at 25 °C) | | | | |
| 0.4 % | 0.02 % | 0.4 % | 0.4 % |
| 0.5 % | 0.02 % | 0.5 % | 0.5 % |
Interrupts/diagnostics/status information | | | | |
Diagnostic functions | Yes; Parameterizable | | Yes; Parameterizable | Yes; Parameterizable |
Substitute values connectable | Yes; Parameterizable | Yes; Parameterizable | Yes; Parameterizable | Yes; Parameterizable |
Alarms | | | | |
| Yes; Parameterizable | Yes | Yes; Parameterizable | Yes; Parameterizable |
Diagnostic messages | | | | |
| Yes | | Yes | Yes |
Diagnostics indication LED | | | | |
| Yes | Yes | Yes | Yes |
Potential separation | | | | |
Potential separation analog outputs | | | | |
| Yes | Yes | Yes | Yes |
Isolation | | | | |
Isolation tested with | 500 V DC | 1500 V DC | 500 V DC | 500 V DC |
Standards, approvals, certificates | | | | |
CE mark | Yes | Yes | Yes | Yes |
UL approval | Yes; File E239877 | Yes; File E239877 | Yes; File E239877 | Yes; File E239877 |
FM approval | Yes; CofC 3028431 | Yes | Yes; CofC 3028431 | Yes; CofC 3028431 |
RCM (formerly C-TICK) | Yes | Yes | Yes | Yes |
KC approval | Yes | Yes | Yes | Yes |
EAC (formerly Gost-R) | Yes | Yes | Yes | Yes |
Railway application | | | | |
| No | | No | No |
| No | | Yes; T1 Category 1 Class A/B horizontal mounting position | No |
Ambient conditions | | | | |
Ambient temperature during operation | | | | |
| -25 °C; = Tmin | 0 °C; = Tmin | -25 °C; = Tmin | -25 °C |
| 70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use | 60 °C; = Tmax | 70 °C; = Tmax; for use on railway vehicles according to EN50155, the rated temperature range -25 ... +55 °C (T1) or 60 °C @ UL/ULhaz/ATEX/FM use applies | 70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use |
Ambient temperature during storage/transportation | | | | |
| -40 °C | -40 °C | -40 °C | -40 °C |
| 70 °C | 70 °C | 70 °C | 70 °C |
Altitude during operation relating to sea level | | | | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Relative humidity | | | | |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Resistance | | | | |
Use in stationary industrial systems | | | | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Connection method | | | | |
required front connector | 20-pin | 20-pin | 20-pin | 40-pin |
Dimensions | | | | |
Width | 40 mm | 40 mm | 40 mm | 40 mm |
Height | 125 mm | 125 mm | 125 mm | 125 mm |
Depth | 120 mm | 120 mm | 120 mm | 120 mm |
Weights | | | | |
Weight, approx. | 220 g | 220 g | 220 g | 272 g |