Supply voltage | | | |
Load voltage L+ | | | |
| | 24V | 24V; A power supply according to EN 50155 shall be used for railway applications |
| | Yes | Yes |
Input current | | | |
from load voltage L+ (without load), max. | | 80mA | 200mA |
from backplane bus 5 V DC, max. | 90mA | 50mA | 50mA |
Power loss | | | |
Power loss, typ. | 0.4W | 1.3W | 1W |
Analog inputs | | | |
Number of analog inputs | 8 | 2 | 8 |
| 8 | 1 | 4 |
permissible input voltage for voltage input (destruction limit), max. | 30V; 12 V continuous, 30 V for max. 1 s | 20V; continuous; 75 V for max. 1 s (mark to space ratio 1:20) | 20V; continuous; 75 V for max. 1 s (mark to space ratio 1:20) |
permissible input current for current input (destruction limit), max. | 40mA | 40mA | 40mA |
Input ranges | | | |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| No | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
Input ranges (rated values), voltages | | | |
| Yes | No | No |
| 100kΩ | | |
| Yes | Yes | Yes |
| 100kΩ | 100kΩ | 100kΩ |
| No | No | No |
| Yes | Yes | Yes |
| 100kΩ | 10MΩ | 10MΩ |
| Yes | Yes | Yes |
| 100kΩ | 100kΩ | 100kΩ |
| No | Yes | Yes |
| | 100kΩ | 100kΩ |
| No | Yes | Yes |
| | 10MΩ | 10MΩ |
| Yes | Yes | Yes |
| 100kΩ | 100kΩ | 100kΩ |
| Yes | No | No |
| 100kΩ | | |
| Yes | Yes | Yes |
| 100kΩ | 10MΩ | 10MΩ |
| No | Yes | Yes |
| | 10MΩ | 10MΩ |
Input ranges (rated values), currents | | | |
| Yes | Yes | Yes |
| 100Ω | 25Ω | 25Ω |
| No | Yes | Yes |
| | 25Ω | 25Ω |
| Yes | Yes | Yes |
| 100Ω | 25Ω | 25Ω |
| No | Yes | Yes |
| | 25Ω | 25Ω |
| Yes | Yes | Yes |
| 100Ω | 25Ω | 25Ω |
Input ranges (rated values), thermocouples | | | |
| No | | No |
| No | | No |
| No | Yes | Yes |
| | 10MΩ | 10MΩ |
| No | Yes | Yes |
| | 10MΩ | 10MΩ |
| No | Yes | Yes |
| | 10MΩ | 10MΩ |
| No | No | No |
| No | Yes | Yes |
| | 10MΩ | 10MΩ |
| No | No | No |
| No | No | No |
| No | No | No |
| No | No | No |
| No | No | No |
Input ranges (rated values), resistance thermometer | | | |
| No | No | No |
| Yes; Standard/climate | Yes | Yes; Standard |
| 100MΩ | 10MΩ; Standard | 10MΩ |
| Yes | | No |
| 100MΩ | | |
| Yes; Standard/climate | | No |
| 100MΩ | | |
| No | | No |
| No | | No |
| No | | No |
| Yes; Standard/climate | Yes | Yes; Standard |
| 100MΩ | 10kΩ; Standard | 10MΩ |
| No | | No |
| No | | No |
| No | | No |
Input ranges (rated values), resistors | | | |
| No | Yes | Yes |
| | 10MΩ | 10MΩ |
| No | Yes | Yes |
| | 10MΩ | 10MΩ |
| Yes | Yes | Yes |
| 100MΩ | 10MΩ | 10MΩ |
| Yes | No | No |
| 100MΩ | | |
Thermocouple (TC) | | | |
Temperature compensation | | | |
| | Yes | Yes |
| | Yes | Yes |
| | Yes | Yes |
Characteristic linearization | | | |
| Yes | Yes | Yes |
| | Type E, J, K, L, N | Type E, J, K, L, N |
| yes; Pt100 standard/air con.; Ni100 standard/air con.; Ni1000 standard/air con.; LG-Ni1000 standard/air con. | Pt100 (standard, climatic range), Ni100 (standard, climatic range) | Pt100 (standard, climatic range), Ni100 (standard, climatic range) |
Cable length | | | |
| 200m; max. 50 m at 50 mV | 200m; 50 m at 80 mV and thermocouples | 200m; 50 m at 80 mV and thermocouples |
Analog value generation for the inputs | | | |
Measurement principle | integrating | integrating | integrating |
Integration and conversion time/resolution per channel | | | |
| 13bit | 15bit; Unipolar: 9/12/12/14 bit; bipolar: 9 bit + sign/12 bit + sign/12 bit + sign/14 bit + sign | 15bit; Unipolar: 9/12/12/14 bit; bipolar: 9 bit + sign/12 bit + sign/12 bit + sign/14 bit + sign |
| Yes; 60 / 50 ms | Yes; 2,5 / 16,67 / 20 / 100 ms | Yes; 2,5 / 16,67 / 20 / 100 ms |
| 66 / 55 ms | | |
| 50 / 60 Hz | 400 / 60 / 50 / 10 Hz | 400 / 60 / 50 / 10 Hz |
Encoder | | | |
Connection of signal encoders | | | |
| Yes; with external supply | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
Errors/accuracies | | | |
Operational error limit in overall temperature range | | | |
| 0.6%; 0.6 % (5 V, 10 V, 1 to 5 V, 0 to 10 V); 0.5 % (50 mV, 500 mV, 1 V) @ 0 ... +60 C; 0.7 % (5 V, 10 V, 1 to 5 V, 0 to 10 V); 0.6 % (50 mV, 500 mV, 1 V) @ -25 ... +70 C | 1%; 1% (80 mV); 0.6% (250 mV to 1 000 mV); 0.8% (2.5 V to 10 V) @ 0 ... +60 C; 1.3% (80 mV); 0.8% (250 mV to 1 000 mV); 1% (2.5 V to 10 V) @ -25 ... +70 C | 1%; 1% (80 mV); 0.6% (250 mV to 1 000 mV); 0.8% (2.5 V to 10 V) @ 0 ... +60 C; 1.3% (80 mV); 0.8% (250 mV to 1 000 mV); 1% (2.5 V to 10 V) @ -25 ... +70 C |
| 0.5%; @ 0 ... +60 C; 0.6% @ -25 ... +70 C; 20 mA, 0 to 20 mA, 4 to 20 mA | 0.7%; @ 0 ... +60 C; 0.9% @ -25 ... +70 C; from 3.2 mA to 20 mA | 0.7%; @ 0 ... +60 C; 0.9% @ -25 ... +70 C; from 3.2 mA to 20 mA |
| 0.5%; @ 0 ... +60 C; 0.6% @ -25 ... +70 C; 0 to 6 kohm, 0 to 600 kohm | 0.7%; @ 0 ... +60 C; 0.9% @ -25 ... +70 C; 150, 300, 600 ohm | 0.7%; @ 0 ... +60 C; 0.9% @ -25 ... +70 C; 150, 300, 600 ohm |
| 1 Kelvin (Pt100, Ni100, climate; Ni1000, LG-Ni1000, standard; Ni1000, LG-Ni1000, climate); 1.2 Kelvin (Pt100, Ni100, standard) @ 0 ... +60 C; 1.2 Kelvin (Pt100, Ni100, climate; Ni1000, LG-Ni1000, standard; Ni1000, LG-Ni1000, climate); 1.4 Kelvin (Pt100, Ni100, standard) @ -25 ... +70 C | 0.7%; 0.7 % (Pt100 / Ni100); 0.8 % (Pt100 climate) @ 0 ... +60 C; 0.9 % (Pt100 / Ni100); 1 % (Pt100 climate) @ -25 ... +70 C | 0.7%; 0.7 % (Pt100 / Ni100); 0.8 % (Pt100 climate) @ 0 ... +60 C; 0.9 % (Pt100 / Ni100); 1 % (Pt100 climate) @ -25 ... +70 C |
Basic error limit (operational limit at 25 C) | | | |
| 0.4%; 0.4% (5 V, 10 V, 1 to 5 V, 0 to 10 V); 0.3% (50 mV, 500 mV, 1 V) | 0.6%; 0.6% (80 mV, 2.5 V to 10 V); 0.4% (250 mV to 1 000 mV) | 0.6%; 0.4 % (250 mV to 1 000 mV); 0.6 % (2.5 mV to 10 mV); 0.7 % (80 mV) |
| 0.3%; 20 mA, 0 to 20 mA, 4 to 20 mA | 0.5%; 3.2 to 20 mA | 0.5%; 3.2 to 20 mA |
| 0.3%; 0 to 6 kohms, 0 to 600 kohms | 0.5%; 150, 300, 600 Ohm | 0.5%; 150, 300, 600 Ohm |
| 1 Kelvin (Pt100, Ni100, standard); 0.8 Kelvin (Pt100, Ni100, climatic; Ni1000, LG-Ni1000, standard; Ni1000, LG-Ni1000, climatic) | 0.6%; 0.5% (Pt100/ Ni100), 0.6% (Pt100 climate) | 0.6%; 0.5% (Pt100/ Ni100), 0.6% (Pt100 climate) |
Interrupts/diagnostics/status information | | | |
Diagnostic functions | No | Yes; Parameterizable | Yes; Parameterizable |
Alarms | | | |
| No | Yes | Yes; Parameterizable, channels 0 and 2 |
| No | Yes; Parameterizable, channel 0 | Yes; Parameterizable |
Diagnostic messages | | | |
| No | Yes | Yes |
Diagnostics indication LED | | | |
| No | Yes | Yes |
Potential separation | | | |
Potential separation analog inputs | | | |
| Yes | Yes | Yes |
Isolation | | | |
Isolation tested with | 500 V DC | 500 V DC | 500 V DC |
Standards, approvals, certificates | | | |
CE mark | Yes | Yes | Yes |
UL approval | Yes; File E239877 | Yes; File E239877 | Yes; File E239877 |
FM approval | Yes; CofC 3028431 | Yes; CofC 3028431 | Yes; CofC 3028431 |
RCM (formerly C-TICK) | Yes | Yes | Yes |
KC approval | Yes | Yes | Yes |
EAC (formerly Gost-R) | Yes | Yes | Yes |
Railway application | | | |
| No | No | No |
| No | No | Yes; T1 Category 1 Class A/B horizontal mounting position |
Ambient conditions | | | |
Ambient temperature during operation | | | |
| -25C | -25C; = Tmin | -25C; = Tmin |
| 70C; = Tmax; 60 C @ UL/cUL, ATEX and FM use | 70C; = Tmax; 60 C @ UL/cUL, ATEX and FM use | 70C; = Tmax; for use on railway vehicles according to EN50155, the rated temperature range -25 ... +55 C (T1) or 60 C @ UL/ULhaz/ATEX/FM use applies |
Ambient temperature during storage/transportation | | | |
| | -40C | -40C |
| | 70C | 70C |
Altitude during operation relating to sea level | | | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity | | | |
| 100%; RH incl. condensation/frost (no commissioning under condensation conditions) | 100%; RH incl. condensation/frost (no commissioning under condensation conditions) | 100%; RH incl. condensation/frost (no commissioning under condensation conditions) |
Resistance | | | |
Use in stationary industrial systems | | | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Connection method | | | |
required front connector | 40-pin | 20-pin | 20-pin |
Dimensions | | | |
Width | 40mm | 40mm | 40mm |
Height | 125mm | 125mm | 125mm |
Depth | 117mm | 120mm | 120mm |
Weights | | | |
Weight, approx. | 250g | 250g | 250g |