Input current | | |
from backplane bus 5 V DC, typ. | 15 mA | 15 mA |
Output voltage | | |
Power supply to the transmitters | | |
| 25 mA | 25 mA |
Power loss | | |
Power loss, typ. | 1.5 W | 1.5 W |
Analog inputs | | |
Number of analog inputs | 0 | 0 |
Analog outputs | | |
Number of analog outputs | 1 | 1 |
Cycle time (all channels) max. | Voltage: 300 ОјS (R), 750 ОјS (1 uF) Current: 600 ms (1 mH); 2 ms (10 mH) | Voltage: 300 ОјS (R), 750 ОјS (1 uF) Current: 600 ms (1 mH); 2 ms (10 mH) |
Output ranges, voltage | | |
| Yes | Yes |
Output ranges, current | | |
| Yes | Yes |
Load impedance (in rated range of output) | | |
| 1 000 Ω | 1 000 Ω |
| 600 Ω | 600 Ω |
Cable length | | |
| 10 m; shielded, twisted pair | 10 m; shielded, twisted pair |
Analog value generation for the outputs | | |
Conversion principle | | Differential |
Integration and conversion time/resolution per channel | | |
| | 12 bit |
Errors/accuracies | | |
Temperature error (relative to output range), (+/-) | 25 °C ±0.5%, to 55 °C ±1% | 25 °C ±0.5 %, up to 55 °C ±1.8 % |
Interrupts/diagnostics/status information | | |
Alarms | Yes | Yes |
Diagnostic functions | Yes | Yes |
Diagnostics indication LED | | |
| | Yes |
Degree and class of protection | | |
Degree of protection acc. to EN 60529 | | |
| Yes | Yes |
Standards, approvals, certificates | | |
CE mark | Yes | Yes |
FM approval | Yes | Yes |
RCM (formerly C-TICK) | Yes | Yes |
Ambient conditions | | |
Free fall | | |
| 0.3 m; five times, in product package | 0.3 m; five times, in product package |
Ambient temperature during operation | | |
| 0 °C; = Tmin | -40 °C; = Tmin; Startup @ -25 °C |
| 55 °C; = Tmax | 55 °C; = Tmax |
Ambient temperature during storage/transportation | | |
| -40 °C | -40 °C |
| 70 °C | 70 °C |
Altitude during operation relating to sea level | | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Relative humidity | | |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Use in stationary industrial systems | | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Mechanics/material | | |
Enclosure material (front) | | |
| Yes | Yes |
Dimensions | | |
Width | 38 mm | 38 mm |
Height | 62 mm | 62 mm |
Depth | 21 mm | 21 mm |
Weights | | |
Weight, approx. | | 40 g |