Transmission rate | |
Transfer rate | |
| 10 ... 100 Mbit/s |
| 50 ... 38 400 bit/s |
Interfaces | |
Number of interfaces acc. to Industrial Ethernet | 2 |
Number of electrical connections | |
| 2 |
| 1 |
Type of electrical connection | |
| RJ45 port |
| 9 pin Sub-D-connector, RS232 switchable to RS485 |
| 9-pole D-sub connector, RS232 can be switched to RS485 |
| 2-pole plugable terminal block |
design of the removable storage C-PLUG | Yes |
Supply voltage, current consumption, power loss | |
Type of voltage of the supply voltage | DC |
Supply voltage | 24 V |
Supply voltage | 20.4 ... 28.8 V |
Supply voltage external at DC Rated value | 24 V |
Supply voltage external at DC rated value | 20.4 ... 28.8 V |
Consumed current | |
| 0.2 A |
| 0.17 A |
Power loss [W] | 4.6 W |
Product extension optional Backup battery | Yes |
Type of battery | Lithium AA / 3.6 V / 2.3 Ah |
Backup current | |
| 100 µA |
| 160 µA |
Permitted ambient conditions | |
Ambient temperature | |
| 0 ... 60 °C |
| -40 ... +70 °C |
| -40 ... +70 °C |
Relative humidity at 25 °C without condensation during operation maximum | 95 % |
Protection class IP | IP20 |
Design, dimensions and weight | |
Module format | Compact module S7-300 double width |
Width | 80 mm |
Height | 125 mm |
Depth | 120 mm |
Net weight | 0.4 kg |
Product properties, functions, components general | |
Number of units | |
| Number of TIM 4R‑IE per S7‑300/S7-400: multiple, number depends on the connection resources of the CPU |
Wire length | |
| 6 m |
| 30 m |
Performance data S7 communication | |
Number of possible connections for S7 communication | |
| 64 |
| 2 |
| 62 |
Service | |
| Yes |
| Yes |
Performance data multi-protocol mode | |
Number of active connections with multi-protocol mode | 128 |
Performance data telecontrol | |
Suitability for use | |
| Yes |
| Yes |
| Yes |
Protocol is supported | |
| Yes |
| No |
| Yes |
| Yes |
Product function data buffering if connection is aborted | Yes; 56,000 data messages |
Storage capacity | |
| 20 Kibyte |
| 0 Kibyte |
| TD7onCPU: at least 20 KB, actual requirement determined by data volume and functional scope TD7onTIM: 0 bytes in most favorable case |
Product feature Buffered message frame memory | Yes |
Transmission format | |
| Yes |
| Yes |
| Yes |
| Yes |
Operating mode for scanning of data transmission | |
| Polling, polling with time slot procedure |
| Polling, polling with time slot procedure, multi-master polling with time slot procedure |
| spontaneous |
| spontaneous |
Hamming distance | |
| 4 |
| 4 |
Configuration software | |
| SINAUT ST7 ES |
| Yes |
| Yes |
Storage location of TIM configuration data | on internal TIM flash memory, or on TIM in optional C‑PLUG, or on MMC of the S7-300 CPU if TIM installed in S7-300 controller |
Product functions Security | |
Suitability for operation Virtual Private Network | Yes |
Type of authentication with Virtual Private Network PSK | Yes |
Product function | |
| Yes |
| Yes |
Protocol | |
| Yes |
| TCP/IP |
Key length for MSC with Virtual Private Network | 128 bit |
Number of possible connections | |
| 1 |
| 128 |
Product functions Time | |
Product component Hardware real-time clock | Yes |
Product feature Hardware real-time clock w. battery backup | Yes |
Accuracy of the hardware real-time clock per day maximum | 4 s |
time synchronization | |
| Yes |