Input | |
Input | 3-phase AC |
Rated voltage value Vin rated | 400 ... 480 V |
Voltage range AC | 340 ... 550 V |
| 320 ... 340 V for max. 1 min |
Wide-range input | Yes |
Overvoltage resistance | Implemented internally with varistors |
Mains buffering at Iout rated, min. | 15 ms; at Vin = 400 V |
Rated line frequency 1 | 50 Hz |
Rated line frequency 2 | 60 Hz |
Rated line range | 45 ... 66 Hz |
Input current | |
| 0.5 A |
Switch-on current limiting (+25 °C), max. | 40 A |
IІt, max. | 3.5 AІ·s |
Built-in incoming fuse | T 4 A |
Protection in the mains power input (IEC 898) | Required: Circuit breaker 3RV2011-1DA10 or 3RV2711-1DD10 (UL 489) |
Output | |
Output | Controlled, isolated DC voltage |
Rated voltage Vout DC | 24 V |
Total tolerance, static ± | 3 % |
Static mains compensation, approx. | 0.5 % |
Static load balancing, approx. | 0.5 % |
Residual ripple peak-peak, max. | 200 mV |
Spikes peak-peak, max. (bandwidth: 20 MHz) | 250 mV |
Product function Output voltage adjustable | No |
Output voltage setting | - |
Status display | Green LED for 24 V OK |
Signaling | max. 30 V, 10 mA; Power-Good (High-Pegel 1L+ for Vout in range 21.3 ... 29 V); Overtemperature warning at least 30 s before switch-off (high level 1L+ when the max. internal temperature is exceeded) |
On/off behavior | Overshoot of Vout < 2 % |
Startup delay, max. | 1.5 s |
Voltage rise, typ. | 40 ms |
Rated current value Iout rated | 8 A |
Current range | 0 ... 8 A |
Supplied active power typical | 192 W |
Short-term overload current | |
| 50 A |
| 50 A |
Duration of overloading capability for excess current | |
| 100 ms |
| 100 ms |
Parallel switching for enhanced performance | No |
Efficiency | |
Efficiency at Vout rated, Iout rated, approx. | 88 % |
Power loss at Vout rated, Iout rated, approx. | 25 W |
Closed-loop control | |
Dynamic mains compensation (Vin rated ±15 %), max. | 0.5 % |
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ. | 1 % |
Setting time maximum | 2 ms |
Protection and monitoring | |
Output overvoltage protection | < 33 V |
Current limitation, typ. | 9.4 A |
Property of the output Short-circuit proof | Yes |
Short-circuit protection | Electronic shutdown, automatic restart |
Enduring short circuit current RMS value | |
| 10 A |
Overload/short-circuit indicator | - |
Safety | |
Primary/secondary isolation | Yes |
Galvanic isolation | Protective extra low output voltage Vout according to EN 60950-1 and EN 50178 |
Protection class | Class I |
Leakage current | |
| 3.5 mA |
| 0.4 mA |
CE mark | Yes |
UL/cUL (CSA) approval | UL-Listed (UL 508) according to NFPA compatibility (National Fire Protection Association), see operating instructions |
Explosion protection | No |
FM approval | - |
CB approval | Yes |
Marine approval | No |
Degree of protection (EN 60529) | IP67, enclosure type 5 indoor |
EMC | |
Emitted interference | EN 55022 Class A |
Supply harmonics limitation | - |
Noise immunity | EN 61000-6-2 |
Operating data | |
Ambient temperature | |
| -25 ... +55 °C |
| with natural convection |
| -40 ... +70 °C |
| -40 ... +70 °C |
Humidity class according to EN 60721 | Climate class 3K3, no condensation |
Mechanics | |
Connection technology | screw-type terminals |
Connections | |
| L1, L2, L3, PE: Plug connector HAN Q4/2 (counterpart see "Electrical accessories") |
| L+, M: 2 x 1.5 mmІ each (4-pole cable for +/- with open, labeled ends, 4 x 1.5 mmІ) |
| Alarm signals: M12 plug-in connector 5-pin |
Width of the enclosure | 310 mm |
Height of the enclosure | 135 mm |
Depth of the enclosure | 90 mm |
Weight, approx. | 2.8 kg |
Product feature of the enclosure housing for side-by-side mounting | No |
Installation | Can be mounted onto ET200pro mounting rail |
Electrical accessories | Power connector (Input: 3RK1911-2BE30 (6 mmІ)) (Output: 3RK1911-2BF10 (4 mmІ)) |
MTBF at 40 °C | 196 354 h |
Other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |