General information | | |
Vendor identification (VendorID) | 002AH | 002AH |
Device identifier (DeviceID) | 0306H | 0306H |
Supply voltage | | |
Rated value (DC) | 24 V | 24 V |
permissible range, lower limit (DC) | 20.4 V | 20.4 V |
permissible range, upper limit (DC) | 28.8 V | 28.8 V |
Reverse polarity protection | Yes | Yes |
Load voltage 2L+ | | |
| 24 V | 24 V |
| Yes | Yes; against destruction; load increasing |
Input current | | |
Current consumption, typ. | 200 mA | 100 mA |
from supply voltage 1L+, max. | 4 A | 4 A |
from load voltage 2L+, max. | 4 A | 4 A |
Encoder supply | | |
Number of outputs | 6 | 4 |
Short-circuit protection | Yes | Yes; per channel, electronic |
Output current | | |
| 200 mA; 100 mA per output to X5-X6 | 500 mA; Per channel |
Power loss | | |
Power loss, typ. | 8 W | 4.8 W |
Digital inputs | | |
Number of digital inputs | 8 | |
Input characteristic curve in accordance with IEC 61131, type 3 | Yes | |
Number of simultaneously controllable inputs | | |
all mounting positions | | |
| 8 | |
Input voltage | | |
| 24 V | |
| -3 to +5V | |
| +11 to +30V | |
Input current | | |
| 1.5 mA | |
| 7 mA | |
Input delay (for rated value of input voltage) | | |
for standard inputs | | |
| typically 3 ms | |
| typically 3 ms | |
Cable length | | |
| 30 m | |
Digital outputs | | |
Number of digital outputs | 4 | |
Short-circuit protection | Yes; Electronic | |
| 1.8 A | |
Limitation of inductive shutdown voltage to | Typ. (L1+, L2+) -47 V | |
Controlling a digital input | Yes | |
Switching capacity of the outputs | | |
| 5 W | |
Output current | | |
| 1.3 A; Maximum | |
| 1.5 mA | |
Parallel switching of two outputs | | |
| No | |
| Yes | |
Switching frequency | | |
| 100 Hz | |
| 0.5 Hz | |
| 1 Hz | |
Total current of the outputs (per group) | | |
all mounting positions | | |
| 3.9 A | |
Cable length | | |
| 30 m | |
IO-Link | | |
Number of ports | 4 | 4 |
| 4 | 4 |
IO-Link protocol 1.0 | Yes | Yes |
IO-Link protocol 1.1 | | Yes |
Transmission rate | 4.8 kBd (COM1); 38.4 kBd (COM2) | 4.8 kBaud (COM1); 38.4 kBaud (COM2), 230 kBaud (COM3) |
Size of process data, input per port | 32 byte | 32 byte |
Size of process data, input per module | 32 byte | 128 bytes + 4 bytes PQI |
Size of process data, output per port | 32 byte | 32 byte |
Size of process data, output per module | 32 byte | 128 byte |
Memory size for device parameter | | 2 kbyte; for each port |
Master backup | | Possible with function block IO_LINK_MASTER |
Configuration without S7-PCT | | Possible; autostart function |
Cable length unshielded, max. | 20 m | 20 m |
Operating modes | | |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes; max. 100 mA |
Connection of IO-Link devices | | |
| Yes | Yes; via 3-core cable |
| | Yes; Additional device supply: max. 2 A per port, max. 4 A per module |
| Yes | |
Interfaces | | |
Transmission procedure | 100BASE-TX | 100BASE-TX |
Number of PROFINET interfaces | 1 | 1 |
PROFINET IO | | |
| Yes | Yes |
| Yes | Yes |
| 100 Mbit/s | 100 Mbit/s |
| Yes | Yes |
Protocols | | |
Supports protocol for PROFINET IO | Yes | Yes |
PROFINET CBA | No | No |
PROFIsafe | No | No |
Protocols (Ethernet) | | |
| No | No |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
PROFINET IO Device | | |
Services | | |
| Yes | Yes |
Interrupts/diagnostics/status information | | |
Status indicator | Yes; Green LED | Yes; Green LED |
Diagnostic functions | Yes | Yes |
Alarms | | |
| Yes | Yes |
Diagnostic messages | | |
| Yes | Yes |
| Yes; Green "ON" LED | Yes; Green "ON" LED |
| Yes | |
| Yes | |
| Yes | Yes; Device supply to M |
| Yes | |
| Yes; Red/yellow "SF/MT" LED | Yes; Red/yellow "SF/MT" LED |
Potential separation | | |
between the load voltages | Yes | Yes |
between load voltage and all other switching components | No | No |
between Ethernet and electronics | Yes | Yes |
Potential separation digital inputs | | |
| No | |
Potential separation digital outputs | | |
| No | |
Isolation | | |
tested with | | |
| 707 V DC (type test) | 707 V DC (type test) |
| 1 500 V; According to IEEE 802.3 | 1 500 V; According to IEEE 802.3 |
Degree and class of protection | | |
IP degree of protection | IP65/67 | IP65/67 |
Standards, approvals, certificates | | |
Suitable for safety-oriented group deactivation | | No |
Connection method | | |
Design of electrical connection | | 3/5-pin M12 round connectors |
Dimensions | | |
Width | 60 mm | 30 mm |
Height | 175 mm | 200 mm |
Depth | 49 mm | 49 mm |
Weights | | |
Weight (without packaging) | 910 g | 550 g |