The integration of four conducting paths to a reverse switch combined in one enclosure makes this device a particularly compact solution. Compared to conventional systems, for which two contactors are required, it is possible to save up to 50% in width with the three-phase reversing contactors. Devices with a width of 45 mm cover motors up to 2.2 kW – and those with a width of 90 mm cover motors up to 3 kW.1) 1) In accordance with the product standard IEC 60947‑4‑2, the motor contactors are designed for motors with maximum starting current conditions of I/Ie ≤ 8. For configuring motors with higher starting current conditions (typically I/Ie ≥ 8), the data in the "SIRIUS 3RF34 solid-state switching devices" manual must be taken into account, see https://support.industry.siemens.com/cs/ww/en/view/60298187. |
| Каталог 2018 | Каталог 2017 | Каталог 2016 | Каталог 2015 | Каталог 2014 | Каталог 2013 | Каталог 2012 | Сертификат | Контакты | Карта сайта | Поиск |