Siemens
01 2018
(4872) 700-366
skenergo@mail.ru

Article number

6ES7141-6BF00-0AB0

6ES7141-6BG00-0AB0

6ES7141-6BH00-0AB0

ET200ECO PN, 8DI, DC24V, 4XM12

ET200ECO PN, 8DI, DC24V, 8XM12

ET200ECO PN, 16DI, DC24V, 8XM12

General information

Vendor identification (VendorID)

002AH

002AH

002AH

Device identifier (DeviceID)

0306H

0306H

0306H

Supply voltage

Rated value (DC)

24V

24V

24V

permissible range, lower limit (DC)

20.4V

20.4V

20.4V

permissible range, upper limit (DC)

28.8V

28.8V

28.8V

Reverse polarity protection

Yes

Yes

Yes

Input current

Current consumption, typ.

100mA

100mA

100mA

Encoder supply

Number of outputs

4

8

8

Short-circuit protection

Yes; Electronic

Yes; Electronic

Yes; Electronic

Output current

  • Rated value

100mA; per output

100mA; per output

100mA; per output

Power loss

Power loss, typ.

5.5W

4.5W

6.5W

Digital inputs

Number of digital inputs

8

8

16

  • in groups of

2

1

2

Input characteristic curve in accordance with IEC 61131, type 3

Yes

Yes

Yes

Number of simultaneously controllable inputs

all mounting positions

  • up to 60 C, max.

8

8

16

Input voltage

  • Type of input voltage

DC

DC

DC

  • Rated value (DC)

24V

24V

24V

  • for signal "0"

-3 to +5V

-3 to +5V

-3 to +5V

  • for signal "1"

+11 to +30V

+11 to +30V

+11 to +30V

Input current

  • for signal "1", typ.

7mA

7mA

7mA

Input delay (for rated value of input voltage)

for standard inputs

  • at "0" to "1", max.

typically 3 ms

typically 3 ms

typically 3 ms

  • at "1" to "0", max.

typically 3 ms

typically 3 ms

typically 3 ms

Cable length

  • unshielded, max.

30m

30m

30m

Encoder

Connectable encoders

  • 2-wire sensor

Yes

Yes

Yes

  • permissible quiescent current (2-wire sensor), max.

1.5mA

1.5mA

1.5mA

Interfaces

Transmission procedure

100BASE-TX

100BASE-TX

100BASE-TX

Number of PROFINET interfaces

1

1

1

PROFINET IO

  • Autocrossing

Yes

Yes

Yes

  • automatic detection of transmission rate

Yes

Yes

Yes

  • Transmission rate, max.

100Mbit/s

100Mbit/s

100Mbit/s

  • integrated switch

Yes

Yes

Yes

Protocols

Supports protocol for PROFINET IO

Yes

Yes

Yes

PROFINET CBA

No

No

No

PROFIsafe

No

No

No

Protocols (Ethernet)

  • TCP/IP

No

No

No

  • SNMP

Yes

Yes

Yes

  • DCP

Yes

Yes

Yes

  • LLDP

Yes

Yes

Yes

  • ping

Yes

Yes

Yes

  • ARP

Yes

Yes

Yes

PROFINET IO Device

Services

  • IRT with the option "high flexibility"

Yes

Yes

Yes

  • Prioritized startup

Yes

Yes

Yes

Interrupts/diagnostics/status information

Status indicator

Yes; Green LED

Yes; Green LED

Yes; Green LED

Diagnostic functions

Yes

Yes

Yes

Alarms

  • Diagnostic alarm

Yes

Yes

Yes

Diagnostic messages

  • Diagnostic information readable

Yes

Yes

Yes

  • Monitoring the supply voltage

Yes; Green "ON" LED

Yes; Green "ON" LED

Yes; Green "ON" LED

  • Wire-break in signal transmitter cable

Yes

Yes

Yes

  • Short-circuit encoder supply

Yes; Per channel group

Yes; Per channel group

Yes; Per channel group

  • Group error

Yes; Red/yellow "SF/MT" LED

Yes; Red/yellow "SF/MT" LED

Yes; Red/yellow "SF/MT" LED

Potential separation

between the load voltages

Yes

Yes

Yes

between load voltage and all other switching components

No

No

No

between Ethernet and electronics

Yes

Yes

Yes

Potential separation digital inputs

  • between the channels

No

No

No

Isolation

tested with

  • 24 V DC circuits

707 V DC (type test)

707 V DC (type test)

707 V DC (type test)

  • Interface

1500V; According to IEEE 802.3

1500V; According to IEEE 802.3

1500V; According to IEEE 802.3

Degree and class of protection

IP degree of protection

IP65/67

IP67

IP67

Connection method

Design of electrical connection

4/5-pin M12 circular connectors

4/5-pin M12 circular connectors

4/5-pin M12 circular connectors

Dimensions

Width

30mm

60mm

60mm

Height

200mm

175mm

175mm

Depth

49mm

49mm

49mm

Weights

Weight (without packaging)

550g

910g

910g


Article number

6ES7142-6BF50-0AB0

6ES7142-6BF00-0AB0

6ES7142-6BG00-0AB0

6ES7142-6BR00-0AB0

6ES7142-6BH00-0AB0

ET200ECO PN, 8DO, DC24V/0,5A, 4XM12

ET200ECO PN, 8DO, DC24V/1,3A, 4XM12

ET200ECO PN, 8DO, DC24V/1,3A, 8XM12

ET200ECO PN, 8 DO, DC24V/2A, 8XM12

ET200ECO PN, 16DO DC24V/1,3A, 8XM12

General information

Vendor identification (VendorID)

002AH

002AH

002AH

002AH

002AH

Device identifier (DeviceID)

0306H

0306H

0306H

0306H

0306H

Supply voltage

Rated value (DC)

24V

24V

24V

24V

24V

permissible range, lower limit (DC)

20.4V

20.4V

20.4V

20.4V

20.4V

permissible range, upper limit (DC)

28.8V

28.8V

28.8V

28.8V

28.8V

Reverse polarity protection

Yes

Yes

Yes

Yes

Yes

Load voltage 2L+

  • Rated value (DC)

24V

24V

24V

24V

24V

  • Reverse polarity protection

Yes

Yes

Yes

Yes

Yes

Input current

Current consumption, typ.

100mA

100mA

100mA

100mA

100mA

from supply voltage 1L+, max.

4A

4A

4A

4A

4A

from load voltage 2L+, max.

4A

4A

4A

4A

4A

Power loss

Power loss, typ.

3W

5.5W

5.5W

5W

5.5W

Digital outputs

Number of digital outputs

8

8

8

8

16

  • in groups of

8

4

4

4

8

Short-circuit protection

Yes

Yes

Yes

Yes

Yes

  • Response threshold, typ.

0.7A

1.8A

1.8A

2.8A

1.8A

Limitation of inductive shutdown voltage to

Typ. (L1+, L2+) -47 V

Typ. (L1+, L2+) -47 V

Typ. (L1+, L2+) -47 V

Typ. (L1+, L2+) -47 V

Typ. (L1+, L2+) -47 V

Controlling a digital input

Yes

Yes

Yes

Yes

Yes

Switching capacity of the outputs

  • on lamp load, max.

5W

5W

5W

10W

5W

Output current

  • for signal "1" rated value

0.5A

1.3A; Maximum

1.3A; Maximum

2A

1.3A; Maximum

  • for signal "0" residual current, max.

1.5mA

1.5mA

1.5mA

1.5mA

1.5mA

Parallel switching of two outputs

  • for uprating

No

No

No

No

No

  • for redundant control of a load

Yes

Yes

Yes

Yes

Yes

Switching frequency

  • with resistive load, max.

100Hz

100Hz

100Hz

100Hz

100Hz

  • with inductive load, max.

0.5Hz

0.5Hz

0.5Hz

0.5Hz

0.5Hz

  • on lamp load, max.

1Hz

1Hz

1Hz

1Hz

1Hz

Total current of the outputs (per group)

all mounting positions

  • up to 55 C, max.

3.9A

  • up to 60 C, max.

4A

2.6A

3.9A

3.9A

3.9A

Cable length

  • unshielded, max.

30m

30m

30m

30m

30m

Interfaces

Transmission procedure

100BASE-TX

100BASE-TX

100BASE-TX

100BASE-TX

100BASE-TX

Number of PROFINET interfaces

1

1

1

1

1

PROFINET IO

  • Autocrossing

Yes

Yes

Yes

Yes

Yes

  • automatic detection of transmission rate

Yes

Yes

Yes

Yes

Yes

  • Transmission rate, max.

100Mbit/s

100Mbit/s

100Mbit/s

100Mbit/s

100Mbit/s

  • integrated switch

Yes

Yes

Yes

Yes

Yes

Protocols

Supports protocol for PROFINET IO

Yes

Yes

Yes

Yes

Yes

PROFINET CBA

No

No

No

No

No

PROFIsafe

No

No

No

No

No

Protocols (Ethernet)

  • TCP/IP

No

No

No

No

No

  • SNMP

Yes

Yes

Yes

Yes

Yes

  • DCP

Yes

Yes

Yes

Yes

Yes

  • LLDP

Yes

Yes

Yes

Yes

Yes

  • ping

Yes

Yes

Yes

Yes

Yes

  • ARP

Yes

Yes

Yes

Yes

Yes

PROFINET IO Device

Services

  • IRT with the option "high flexibility"

Yes

Yes

Yes

Yes

Yes

  • Prioritized startup

Yes

Yes

Yes

Yes

Yes

Interrupts/diagnostics/status information

Status indicator

Yes; Green LED

Yes; Green LED

Yes; Green LED

Yes; Green LED

Yes; Green LED

Diagnostic functions

Yes

Yes

Yes

Yes

Yes

Alarms

  • Diagnostic alarm

Yes

Yes

Yes

Yes

Yes

Diagnostic messages

  • Diagnostic information readable

Yes

Yes

Yes

Yes

Yes

  • Monitoring the supply voltage

Yes; Green "ON" LED

Yes; Green "ON" LED

Yes; Green "ON" LED

Yes; Green "ON" LED

Yes; Green "ON" LED

  • Wire-break in actuator cable

Yes

Yes

Yes

Yes

Yes

  • Short-circuit

Yes

Yes

Yes

Yes

Yes

  • Group error

Yes; Red/yellow "SF/MT" LED

Yes; Red/yellow "SF/MT" LED

Yes; Red/yellow "SF/MT" LED

Yes; Red/yellow "SF/MT" LED

Yes; Red/yellow "SF/MT" LED

Potential separation

between the load voltages

Yes

Yes

Yes

Yes

Yes

between load voltage and all other switching components

No

No

No

No

No

between Ethernet and electronics

Yes

Yes

Yes

Yes

Yes

Potential separation digital outputs

  • between the channels

No

No

No

No

No

Isolation

tested with

  • 24 V DC circuits

707 V DC (type test)

707 V DC (type test)

707 V DC (type test)

707 V DC (type test)

707 V DC (type test)

  • Interface

1500V; According to IEEE 802.3

1500V; According to IEEE 802.3

1500V; According to IEEE 802.3

1500V; According to IEEE 802.3

1500V; According to IEEE 802.3

Degree and class of protection

IP degree of protection

IP67

IP65/67

IP67

IP67

IP67

Standards, approvals, certificates

Suitable for safety-oriented group deactivation

Yes

Yes

Yes

Yes

Yes

Highest safety class achievable in safety mode

  • Performance level according to ISO 13849-1

d

d

d

d

d

  • SIL acc. to IEC 61508

2

2

2

2

2

Connection method

Design of electrical connection

4/5-pin M12 circular connectors

4/5-pin M12 circular connectors

4/5-pin M12 circular connectors

4/5-pin M12 circular connectors

4/5-pin M12 circular connectors

Dimensions

Width

30mm

30mm

60mm

60mm

60mm

Height

200mm

200mm

175mm

175mm

175mm

Depth

49mm

49mm

49mm

49mm

49mm

Weights

Weight (without packaging)

550g

550g

910g

910g

910g


Article number

6ES7147-6BG00-0AB0

ET200ECO PN, 8 DIO, DC24V/1,3A, 8XM12

General information

Vendor identification (VendorID)

002AH

Device identifier (DeviceID)

0306H

Supply voltage

Rated value (DC)

24V

permissible range, lower limit (DC)

20.4V

permissible range, upper limit (DC)

28.8V

Reverse polarity protection

Yes

Load voltage 2L+

  • Rated value (DC)

24V

  • Reverse polarity protection

Yes

Input current

Current consumption, typ.

100mA

from supply voltage 1L+, max.

4A

from load voltage 2L+, max.

4A

Encoder supply

Number of outputs

8

Short-circuit protection

Yes; Electronic

Output current

  • Rated value

100mA; per output

Power loss

Power loss, typ.

6.5W

Digital inputs

Number of digital inputs

8

  • in groups of

4

Input characteristic curve in accordance with IEC 61131, type 3

Yes

Number of simultaneously controllable inputs

all mounting positions

  • up to 60 C, max.

8

Input voltage

  • Type of input voltage

DC

  • Rated value (DC)

24V

  • for signal "0"

-3 to +5V

  • for signal "1"

+11 to +30V

Input current

  • for signal "1", typ.

7mA

Input delay (for rated value of input voltage)

for standard inputs

  • at "0" to "1", max.

typically 3 ms

  • at "1" to "0", max.

typically 3 ms

Cable length

  • unshielded, max.

30m

Digital outputs

Number of digital outputs

8

  • in groups of

4

Short-circuit protection

Yes; Electronic

  • Response threshold, typ.

1.8A

Limitation of inductive shutdown voltage to

Typ. (L1+, L2+) -47 V

Controlling a digital input

Yes

Switching capacity of the outputs

  • on lamp load, max.

5W

Output current

  • for signal "1" rated value

1.3A; Maximum

  • for signal "0" residual current, max.

1.5mA

Parallel switching of two outputs

  • for uprating

No

  • for redundant control of a load

Yes

Switching frequency

  • with resistive load, max.

100Hz

  • with inductive load, max.

0.5Hz

  • on lamp load, max.

1Hz

Total current of the outputs (per group)

all mounting positions

  • up to 60 C, max.

3.9A

Cable length

  • unshielded, max.

30m

Encoder

Connectable encoders

  • 2-wire sensor

Yes

  • permissible quiescent current (2-wire sensor), max.

1.5mA

Interfaces

Transmission procedure

100BASE-TX

Number of PROFINET interfaces

1

PROFINET IO

  • Autocrossing

Yes

  • automatic detection of transmission rate

Yes

  • Transmission rate, max.

100Mbit/s

  • integrated switch

Yes

Protocols

Supports protocol for PROFINET IO

Yes

PROFINET CBA

No

PROFIsafe

No

Protocols (Ethernet)

  • TCP/IP

No

  • SNMP

Yes

  • DCP

Yes

  • LLDP

Yes

  • ping

Yes

  • ARP

Yes

PROFINET IO Device

Services

  • IRT with the option "high flexibility"

Yes

  • Prioritized startup

Yes

Interrupts/diagnostics/status information

Status indicator

Yes; Green LED

Diagnostic functions

Yes

Alarms

  • Diagnostic alarm

Yes

Diagnostic messages

  • Diagnostic information readable

Yes

  • Monitoring the supply voltage

Yes; Green "ON" LED

  • Wire-break in actuator cable

Yes

  • Wire-break in signal transmitter cable

Yes

  • Short-circuit

Yes

  • Short-circuit encoder supply

Yes

  • Group error

Yes; Red/yellow "SF/MT" LED

Potential separation

between the load voltages

Yes

between load voltage and all other switching components

No

between Ethernet and electronics

Yes

Potential separation digital inputs

  • between the channels

No

Potential separation digital outputs

  • between the channels

No

Isolation

tested with

  • 24 V DC circuits

707 V DC (type test)

  • Interface

1500V; According to IEEE 802.3

Degree and class of protection

IP degree of protection

IP65/67

Standards, approvals, certificates

Suitable for safety-oriented group deactivation

Yes

Highest safety class achievable in safety mode

  • Performance level according to ISO 13849-1

d

  • SIL acc. to IEC 61508

2

Connection method

Design of electrical connection

4/5-pin M12 circular connectors

Dimensions

Width

60mm

Height

175mm

Depth

49mm

Weights

Weight (without packaging)

910g


Article number

6ES7144-6KD00-0AB0

6ES7144-6KD50-0AB0

ET200ECO PN, 8AI; 4 U/I; 4 RTD/TC 8XM12

ET200ECO PN, 8AI RTD/TC 8XM12

General information

Vendor identification (VendorID)

002AH

002AH

Device identifier (DeviceID)

0306H

0306H

Supply voltage

Rated value (DC)

24V

24V

permissible range, lower limit (DC)

20.4V

20.4V

permissible range, upper limit (DC)

28.8V

28.8V

Reverse polarity protection

Yes

Yes; against destruction

Input current

Current consumption, typ.

110mA

110mA

Encoder supply

Number of outputs

4

Short-circuit protection

Yes; Electronic at 1.4 A

Output current

  • Rated value

1A; Maximum

Power loss

Power loss, typ.

2.8W

2.8W

Analog inputs

Number of analog inputs

8

8

  • For voltage/current measurement

4

  • For resistance/resistance thermometer measurement

4

8

permissible input voltage for voltage input (destruction limit), max.

28.8 V permanent, 35 V for max. 500 ms

Input ranges (rated values), voltages

  • 0 to +10 V

Yes

  • 1 V to 5 V

Yes

  • -10 V to +10 V

Yes

  • -80 mV to +80 mV

Yes

Yes

Input ranges (rated values), currents

  • 0 to 20 mA

Yes

  • -20 mA to +20 mA

Yes

  • 4 mA to 20 mA

Yes

Input ranges (rated values), thermocouples

  • Type E

Yes

Yes

  • Type J

Yes

Yes

  • Type K

Yes

Yes

  • Type N

Yes

Yes

Input ranges (rated values), resistance thermometer

  • Ni 100

Yes

Yes

  • Ni 1000

Yes

Yes

  • Ni 120

Yes

Yes

  • Ni 200

Yes

Yes

  • Ni 500

Yes

Yes

  • Pt 100

Yes

Yes

  • Pt 1000

Yes

Yes

  • Pt 200

Yes

Yes

  • Pt 500

Yes

Yes

Input ranges (rated values), resistors

  • 0 to 150 ohms

Yes

Yes

  • 0 to 300 ohms

Yes

Yes

  • 0 to 600 ohms

Yes

Yes

  • 0 to 3000 ohms

Yes

Yes

Thermocouple (TC)

Temperature compensation

  • parameterizable

Yes

Yes

  • internal temperature compensation

Yes

Yes

  • external temperature compensation with compensations socket

Yes

Yes

  • external temperature compensation with Pt100

Yes

  • dynamic reference temperature value

Yes

  • for definable comparison point temperature

Yes

Cable length

  • shielded, max.

30m

30m

Analog value generation for the inputs

Analog value display

SIMATIC S7 format

SIMATIC S7 format

Measurement principle

integrating

integrating

Integration and conversion time/resolution per channel

  • Resolution (incl. overrange)

15 bit + sign

15 bit + sign

  • Integration time, parameterizable

Yes

Yes

  • Integration time (ms)

2/16.67/20/100 ms

2/16.67/20/100 ms

  • Interference voltage suppression for interference frequency f1 in Hz

500 / 60 / 50 / 10 Hz

500 / 60 / 50 / 10 Hz

  • Conversion time (per channel)

4 / 19 / 22 / 102 ms

4 / 19 / 22 / 102 ms

Smoothing of measured values

  • parameterizable

Yes

Yes

  • Step: None

Yes; 1 x cycle time

Yes; 1 x cycle time

  • Step: low

Yes; 4 x cycle time

Yes; 4 x cycle time

  • Step: Medium

Yes; 16 x cycle time

Yes; 16 x cycle time

  • Step: High

Yes; 64 x cycle time

Yes; 64 x cycle time

Encoder

Number of connectable encoders, max.

8

8

Connection of signal encoders

  • for voltage measurement

Yes

  • for current measurement as 2-wire transducer

Yes

  • for current measurement as 4-wire transducer

Yes

  • for resistance measurement with two-wire connection

Yes

Yes

  • for resistance measurement with three-wire connection

Yes

Yes

  • for resistance measurement with four-wire connection

Yes

Yes

Errors/accuracies

Linearity error (relative to input range), (+/-)

0.01%

0.01%

Temperature error (relative to input range), (+/-)

U: 0.0035%/C; I:0.006%/C; RTD: 0.0005%/C; TC: 0.0035%/C

RTD: 0.0005%/C; TC: 0.0035%/C

Crosstalk between the inputs, min.

85dB

-85dB

Repeat accuracy in steady state at 25 C (relative to input range), (+/-)

0.008%

0.008%

Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency

  • Series mode interference (peak value of interference < rated value of input range), min.

46dB

46dB

  • Common mode interference, min.

70dB

70dB

Interfaces

Transmission procedure

100BASE-TX

100BASE-TX

Number of PROFINET interfaces

1

1

PROFINET IO

  • Autocrossing

Yes

Yes

  • automatic detection of transmission rate

Yes

Yes

  • Transmission rate, max.

100Mbit/s

100Mbit/s

  • integrated switch

Yes

Yes

Protocols

Supports protocol for PROFINET IO

Yes

Yes

PROFINET CBA

No

No

PROFIsafe

No

No

Protocols (Ethernet)

  • TCP/IP

No

No

  • SNMP

Yes

Yes

  • DCP

Yes

Yes

  • LLDP

Yes

Yes

  • ping

Yes

Yes

  • ARP

Yes

Yes

PROFINET IO Device

Services

  • IRT with the option "high flexibility"

Yes

  • Prioritized startup

Yes

Yes

Interrupts/diagnostics/status information

Status indicator

Yes

Diagnostic functions

Yes

Yes

Alarms

  • Diagnostic alarm

Yes

Yes

Diagnostic messages

  • Diagnostic information readable

Yes

Yes

  • Monitoring the supply voltage

Yes; Green "ON" LED

Yes; Green "ON" LED

  • Short-circuit encoder supply

Yes; per module

  • Group error

Yes; Red/yellow "SF/MT" LED

Yes; Red/yellow "SF/MT" LED

  • Overflow/underflow

Yes

Yes

Potential separation

between the load voltages

Yes

Yes

between load voltage and all other switching components

No

No

between Ethernet and electronics

Yes

Yes

Potential separation analog inputs

  • between the channels

No

No

Permissible potential difference

Between the inputs and MANA (UCM)

10 Vpp AC

10 Vpp AC

Isolation

tested with

  • 24 V DC circuits

707 V DC (type test)

707 V DC (type test)

  • Interface

1500V; According to IEEE 802.3

1500V; According to IEEE 802.3

Degree and class of protection

IP degree of protection

IP65/67

IP65/67

Connection method

Design of electrical connection

4/5-pin M12 circular connectors

4/5-pin M12 circular connectors

Dimensions

Width

60mm

60mm

Height

175mm

175mm

Depth

49mm

49mm

Weights

Weight (without packaging)

930g

930g


Article number

6ES7145-6HD00-0AB0

ET200ECO PN, 4AO U/I 4XM12

General information

Vendor identification (VendorID)

002AH

Device identifier (DeviceID)

0306H

Supply voltage

Rated value (DC)

24V

permissible range, lower limit (DC)

20.4V

permissible range, upper limit (DC)

28.8V

Reverse polarity protection

Yes

Input current

Current consumption, typ.

280mA

Actuator supply

Number of outputs

4

Short-circuit protection

Yes; Electronic at 1.4 A

Output current

  • Rated value

1A; Maximum

Power loss

Power loss, typ.

5.5W

Analog outputs

Number of analog outputs

4

Voltage output, short-circuit protection

Yes

Voltage output, short-circuit current, max.

30mA

Current output, no-load voltage, max.

20V

Output ranges, voltage

  • 0 to 10 V

Yes

  • 1 V to 5 V

Yes

  • -10 V to +10 V

Yes

Output ranges, current

  • 0 to 20 mA

Yes

  • -20 mA to +20 mA

Yes

  • 4 mA to 20 mA

Yes

Connection of actuators

  • for voltage output two-wire connection

Yes

  • for current output two-wire connection

Yes

Load impedance (in rated range of output)

  • with voltage outputs, min.

1kΩ

  • with voltage outputs, capacitive load, max.

1F

  • with current outputs, max.

600Ω

  • with current outputs, inductive load, max.

1mH

Destruction limits against externally applied voltages and currents

  • Voltages at the outputs towards MANA

28.8 V permanent, 35 V for max. 500 ms

Cable length

  • shielded, max.

30m

Analog value generation for the outputs

Analog value display

SIMATIC S7 format

Conversion principle

Resistor network

Integration and conversion time/resolution per channel

  • Resolution (incl. overrange)

15 bit + sign

  • Conversion time (per channel)

1ms

Settling time

  • for resistive load

2ms

  • for capacitive load

1.8ms

  • for inductive load

2ms

Errors/accuracies

Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-)

U: 0.6 mVrms; I: 0.4 nArms

Linearity error (relative to output range), (+/-)

0.02%

Temperature error (relative to output range), (+/-)

U: 0.001%/C; I: 0.0025%/C

Crosstalk between the outputs, min.

70dB

Repeat accuracy in steady state at 25 C (relative to output range), (+/-)

0.008%

Interfaces

Transmission procedure

100BASE-TX

Number of PROFINET interfaces

1

PROFINET IO

  • Autocrossing

Yes

  • automatic detection of transmission rate

Yes

  • Transmission rate, max.

100Mbit/s

  • integrated switch

Yes

Protocols

Supports protocol for PROFINET IO

Yes

PROFINET CBA

No

PROFIsafe

No

Protocols (Ethernet)

  • TCP/IP

No

  • SNMP

Yes

  • DCP

Yes

  • LLDP

Yes

  • ping

Yes

  • ARP

Yes

PROFINET IO Device

Services

  • IRT with the option "high flexibility"

Yes

  • Prioritized startup

Yes

Interrupts/diagnostics/status information

Status indicator

Yes

Diagnostic functions

Yes

Substitute values connectable

Yes

Alarms

  • Diagnostic alarm

Yes

Diagnostic messages

  • Diagnostic information readable

Yes

  • Monitoring the supply voltage

Yes; Green "ON" LED

  • Wire-break

Yes; Channel-by-channel with current output

  • Short-circuit

Yes; Channel-by-channel with voltage output

  • Group error

Yes; Red/yellow "SF/MT" LED

Potential separation

between the load voltages

Yes

between load voltage and all other switching components

No

between Ethernet and electronics

Yes

Potential separation analog outputs

  • between the channels

No

Permissible potential difference

between M internally and the outputs

10 Vpp AC

Isolation

tested with

  • 24 V DC circuits

707 V DC (type test)

  • Interface

1500V; According to IEEE 802.3

Degree and class of protection

IP degree of protection

IP65/67

Connection method

Design of electrical connection

4/5-pin M12 circular connectors

Dimensions

Width

60mm

Height

175mm

Depth

49mm

Weights

Weight (without packaging)

930g


Article number

6ES7148-6JA00-0AB0

6ES7148-6JD00-0AB0

ET 200ECO PN: IO-LINK MASTER

ET 200eco PN: IO-Link Master

General information

Vendor identification (VendorID)

002AH

002AH

Device identifier (DeviceID)

0306H

0306H

Supply voltage

Rated value (DC)

24V

24V

permissible range, lower limit (DC)

20.4V

20.4V

permissible range, upper limit (DC)

28.8V

28.8V

Reverse polarity protection

Yes

Yes

Load voltage 2L+

  • Rated value (DC)

24V

24V

  • Reverse polarity protection

Yes

Yes; against destruction; load increasing

Input current

Current consumption, typ.

200mA

100mA

from supply voltage 1L+, max.

4A

4A

from load voltage 2L+, max.

4A

4A

Encoder supply

Number of outputs

6

4

Short-circuit protection

Yes

Yes; per channel, electronic

Output current

  • Rated value

200mA; 100 mA per output to X5-X6

500mA; Per channel

Power loss

Power loss, typ.

8W

4.8W

Digital inputs

Number of digital inputs

8

Input characteristic curve in accordance with IEC 61131, type 3

Yes

Number of simultaneously controllable inputs

all mounting positions

  • up to 60 C, max.

8

Input voltage

  • Rated value (DC)

24V

  • for signal "0"

-3 to +5V

  • for signal "1"

+11 to +30V

Input current

  • for signal "0", max. (permissible quiescent current)

1.5mA

  • for signal "1", typ.

7mA

Input delay (for rated value of input voltage)

for standard inputs

  • at "0" to "1", max.

typically 3 ms

  • at "1" to "0", max.

typically 3 ms

Cable length

  • unshielded, max.

30m

Digital outputs

Number of digital outputs

4

Short-circuit protection

Yes; Electronic

  • Response threshold, typ.

1.8A

Limitation of inductive shutdown voltage to

Typ. (L1+, L2+) -47 V

Controlling a digital input

Yes

Switching capacity of the outputs

  • on lamp load, max.

5W

Output current

  • for signal "1" rated value

1.3A; Maximum

  • for signal "0" residual current, max.

1.5mA

Parallel switching of two outputs

  • for uprating

No

  • for redundant control of a load

Yes

Switching frequency

  • with resistive load, max.

100Hz

  • with inductive load, max.

0.5Hz

  • on lamp load, max.

1Hz

Total current of the outputs (per group)

all mounting positions

  • up to 60 C, max.

3.9A

Cable length

  • unshielded, max.

30m

IO-Link

Number of ports

4

4

  • of which simultaneously controllable

4

4

IO-Link protocol 1.0

Yes

Yes

IO-Link protocol 1.1

Yes

Transmission rate

4.8 kBd (COM1); 38.4 kBd (COM2)

4.8 kBaud (COM1); 38.4 kBaud (COM2), 230 kBaud (COM3)

Size of process data, input per port

32byte

32byte

Size of process data, input per module

32byte

128 bytes + 4 bytes PQI

Size of process data, output per port

32byte

32byte

Size of process data, output per module

32byte

128byte

Memory size for device parameter

2kbyte; for each port

Master backup

Possible with function block IO_LINK_MASTER

Configuration without S7-PCT

Possible; autostart function

Cable length unshielded, max.

20m

20m

Operating modes

  • IO-Link

Yes

Yes

  • DI

Yes

Yes

  • DQ

Yes

Yes; max. 100 mA

Connection of IO-Link devices

  • Port type A

Yes

Yes; via 3-core cable

  • Port type B

Yes; Additional device supply: max. 2 A per port, max. 4 A per module

  • via three-wire connection

Yes

Interfaces

Transmission procedure

100BASE-TX

100BASE-TX

Number of PROFINET interfaces

1

1

PROFINET IO

  • Autocrossing

Yes

Yes

  • automatic detection of transmission rate

Yes

Yes

  • Transmission rate, max.

100Mbit/s

100Mbit/s

  • integrated switch

Yes

Yes

Protocols

Supports protocol for PROFINET IO

Yes

Yes

PROFINET CBA

No

No

PROFIsafe

No

No

Protocols (Ethernet)

  • TCP/IP

No

No

  • SNMP

Yes

Yes

  • DCP

Yes

Yes

  • LLDP

Yes

Yes

  • ping

Yes

Yes

  • ARP

Yes

Yes

PROFINET IO Device

Services

  • IRT with the option "high flexibility"

Yes

Yes

Interrupts/diagnostics/status information

Status indicator

Yes; Green LED

Yes; Green LED

Diagnostic functions

Yes

Yes

Alarms

  • Diagnostic alarm

Yes

Yes

Diagnostic messages

  • Diagnostic information readable

Yes

Yes

  • Monitoring the supply voltage

Yes; Green "ON" LED

Yes; Green "ON" LED

  • Wire-break in actuator cable

Yes

  • Wire-break in signal transmitter cable

Yes

  • Short-circuit

Yes

Yes; Device supply to M

  • Short-circuit encoder supply

Yes

  • Group error

Yes; Red/yellow "SF/MT" LED

Yes; Red/yellow "SF/MT" LED

Potential separation

between the load voltages

Yes

Yes

between load voltage and all other switching components

No

No

between Ethernet and electronics

Yes

Yes

Potential separation digital inputs

  • between the channels

No

Potential separation digital outputs

  • between the channels

No

Isolation

tested with

  • 24 V DC circuits

707 V DC (type test)

707 V DC (type test)

  • Interface

1500V; According to IEEE 802.3

1500V; According to IEEE 802.3

Degree and class of protection

IP degree of protection

IP65/67

IP65/67

Standards, approvals, certificates

Suitable for safety-oriented group deactivation

No

Connection method

Design of electrical connection

3/5-pin M12 round connectors

Dimensions

Width

60mm

30mm

Height

175mm

200mm

Depth

49mm

49mm

Weights

Weight (without packaging)

910g

550g



















  © " " 2007-2022
  (4872) 700-366  skenergo@mail.ru
.