Supply voltage | | | | | |
Rated value (DC) | | | | | |
| Yes | Yes | Yes | Yes | Yes |
permissible range, lower limit (DC) | 20.4V | 20.4V | 20.4V | 20.4V | 20.4V |
permissible range, upper limit (DC) | 28.8V | 28.8V | 28.8V | 28.8V | 28.8V |
Input current | | | | | |
from backplane bus 5 V DC, max. | 145mA | 185mA | 145mA | 180mA | 120mA |
Digital inputs | | | | | |
| 4mA; per channel | 4mA; per channel | 4 mA/input 11 mA/relay | 4 mA/input 11 mA/relay | |
Output voltage | | | | | |
Power supply to the transmitters | | | | | |
| Yes | Yes | Yes | Yes | Yes |
Power loss | | | | | |
Power loss, typ. | 2.5W | 4.5W | 5.5W | 10W | 7.5W |
Digital inputs | | | | | |
Number of digital inputs | 8 | 16 | 8 | 16 | 8 |
| 2 | 2 | 2 | 2 | 4 |
Input characteristic curve in accordance with IEC 61131, type 1 | Yes | Yes | Yes | Yes | Yes |
Number of simultaneously controllable inputs | | | | | |
all mounting positions | | | | | |
| 8 | 16 | 8 | 16 | 8 |
horizontal installation | | | | | |
| 8 | 16 | 8 | 16 | 8 |
| 8 | 16 | 8 | 16 | 8 |
vertical installation | | | | | |
| 8 | 16 | 8 | 16 | 8 |
Input voltage | | | | | |
| DC | DC | DC | DC | AC |
| 24V | 24V | 24V | 24V | |
| | | | | 120/230 V AC |
| 5 V DC at 1 mA | 5 V DC at 1 mA | 5 V DC at 1 mA | 5 V DC at 1 mA | 20 V AC at 1 mA |
| 15 V DC at 2.5 mA | 15 V DC at 2.5 mA | 15 V DC at 2.5 mA | 15 V DC at 2.5 mA | 79 V AC at 2.5 mA |
Input current | | | | | |
| 1mA | 1mA | 1mA | 1mA | 1mA |
| 2.5mA | 2.5mA | 2.5mA | 2.5mA | 2.5mA |
| 4mA | 4mA | 4mA | 4mA | 9mA |
Input delay (for rated value of input voltage) | | | | | |
for standard inputs | | | | | |
| Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four | Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four | Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four | Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four | Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four |
for interrupt inputs | | | | | |
| Yes | Yes | Yes | Yes | Yes |
Cable length | | | | | |
| 500m | 500m | 500m | 500m | 500m |
| 300m | 300m | 300m | 300m | 300m |
Digital outputs | | | | | |
Number of digital outputs | 8 | 16 | 8 | 16 | 8 |
| 1 | 1 | 2 | 4 | 4 |
Short-circuit protection | No; to be provided externally | No; to be provided externally | No; to be provided externally | No; to be provided externally | No; to be provided externally |
Limitation of inductive shutdown voltage to | L+ (-48 V) | L+ (-48 V) | | | |
Switching capacity of the outputs | | | | | |
| 0.5A | 0.5A | 2A | 2A | 2A |
| 5W | 5W | 30 W with DC, 200 W with AC | 30 W with DC, 200 W with AC | 30 W with DC, 200 W with AC |
Output voltage | | | | | |
| 24V | 24V | 5 V DC to 30 V DC | 5 V DC to 30 V DC | 5 V DC to 30 V DC |
| | | 5 V AC to 250 V AC | 5 V AC to 250 V AC | 5 V AC to 250 V AC |
| 0.1V; with 10 kOhm load | 0.1V; with 10 kOhm load | | | |
| 20 V DC | 20 V DC | | | |
Output current | | | | | |
| 0.5A | 0.5A | 2A | 2A | 2A |
| 10A | 10A | | | |
Output delay with resistive load | | | | | |
| 50s | 50s | 10ms | 10ms | 10ms |
| 200s | 200s | 10ms | 10ms | 10ms |
Total current of the outputs (per group) | | | | | |
horizontal installation | | | | | |
| 4A; Current per mass | 8A; Current per mass | 10A; Current per mass | 8A; Current per mass | 8A; Current per mass |
Relay outputs | | | | | |
| | | 8 | 16 | 8 |
| | | 24V | 24V | 24V |
| | | mechanically 10 million, at rated load voltage 100 000 | mechanically 10 million, at rated load voltage 100 000 | mechanically 10 million, at rated load voltage 100 000 |
Switching capacity of contacts | | | | | |
| | 0.5A | 2A | 2A | 2A |
| | 5W | 30 W with DC, 200 W with AC | 30 W with DC, 200 W with AC | 30 W with DC, 200 W with AC |
| | 0.5A | 2A | 2A | 2A |
Cable length | | | | | |
| 500m | 500m | 500m | 500m | 500m |
| 150m | 150m | 150m | 150m | 150m |
Interrupts/diagnostics/status information | | | | | |
Alarms | | | | | |
| Yes | Yes | Yes | Yes | Yes |
Diagnostics indication LED | | | | | |
| Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes |
Potential separation | | | | | |
Potential separation digital inputs | | | | | |
| 2 | 2 | 2 | 2 | 2 |
Potential separation digital outputs | | | | | |
| | | Relays | Relays | Relays |
| 1 | 1 | 2 | 4 | 2 |
| 500 V AC | 500 V AC | 1500 V AC for 1 minute | 1500 V AC for 1 minute | 1500 V AC for 1 minute |
Permissible potential difference | | | | | |
between different circuits | | | 750 V AC for 1 minute | 750 V AC for 1 minute | 750 V AC for 1 minute |
Degree and class of protection | | | | | |
Degree of protection acc. to EN 60529 | | | | | |
| Yes | Yes | Yes | Yes | Yes |
Standards, approvals, certificates | | | | | |
CE mark | Yes | Yes | Yes | Yes | Yes |
CSA approval | Yes | Yes | Yes | Yes | Yes |
UL approval | Yes | Yes | Yes | Yes | Yes |
cULus | Yes | Yes | Yes | Yes | Yes |
FM approval | Yes | Yes | Yes | Yes | Yes |
RCM (formerly C-TICK) | Yes | Yes | Yes | Yes | Yes |
Marine approval | Yes | | Yes | Yes | Yes |
Ambient conditions | | | | | |
Free fall | | | | | |
| 0.3m; five times, in product package | 0.3m; five times, in product package | 0.3m; five times, in product package | 0.3m; five times, in product package | 0.3m; five times, in product package |
Ambient temperature during operation | | | | | |
| -20C | -20C | -20C | -20C | -20C |
| 60C | 60C | 60C | 60C; Number of simultaneously activated outputs: 8 (no adjacent points) at 60 C horizontal or 50 C vertical, 16 at 55 C horizontal or 45 C vertical | 60C; Number of simultaneously activated outputs: 4 (no adjacent points) at 60 C horizontal or 50 C vertical, 8 at 55 C horizontal or 45 C vertical |
| -20C | -20C | -20C | -20C | -20C |
| 60C | 60C | 60C | 60C | 60C |
| -20C | -20C | -20C | -20C | -20C |
| 50C | 50C | 50C | 50C | 50C |
| 5C to 55C, 3C / minute | 5C to 55C, 3C / minute | 5C to 55C, 3C / minute | 5C to 55C, 3C / minute | 5C to 55C, 3C / minute |
Ambient temperature during storage/transportation | | | | | |
| -40C | -40C | -40C | -40C | -40C |
| 70C | 70C | 70C | 70C | 70C |
Air pressure acc. to IEC 60068-2-13 | | | | | |
| 660hPa | 660hPa | 660hPa | 660hPa | 660hPa |
| 1080hPa | 1080hPa | 1080hPa | 1080hPa | 1080hPa |
Relative humidity | | | | | |
| 95% | 95% | 95% | 95% | 95% |
Connection method | | | | | |
required front connector | Yes | Yes | Yes | Yes | Yes |
Mechanics/material | | | | | |
Enclosure material (front) | | | | | |
| Yes | Yes | Yes | Yes | Yes |
Dimensions | | | | | |
Width | 45mm | 70mm | 45mm | 70mm | 45mm |
Height | 100mm | 100mm | 100mm | 100mm | 100mm |
Depth | 75mm | 75mm | 75mm | 75mm | 75mm |
Weights | | | | | |
Weight, approx. | 210g | 310g | 230g | 350g | 230g |