General information | | |
Product type designation | CM 1241 RS422/485 | CM 1241 RS232 |
Supply voltage | | |
Rated value (DC) | | |
| Yes | Yes |
permissible range, lower limit (DC) | 20.4 V | 20.4 V |
permissible range, upper limit (DC) | 28.8 V | 28.8 V |
Input current | | |
Current consumption, max. | 220 mA; From backplane bus 5 V DC | 200 mA; From backplane bus 5 V DC |
Power loss | | |
Power loss, typ. | 1.1 W | 1.1 W |
Interfaces | | |
Number of interfaces | 1 | 1 |
Interface physics, RS 232C (V.24) | | Yes |
Interface (physical) RS 422/485 (X.27) | Yes | |
Point-to-point | | |
| 1 000 m | 10 m |
Integrated protocol driver | | |
| Yes | Yes |
| Yes; Available as library function | Yes; Available as library function |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
| Yes; Available as library function | |
Protocols | | |
Integrated protocols | | |
Freeport | | |
| 1 kbyte | 1 kbyte |
| 7 or 8 | 7 or 8 |
| 1 (Standard), 2 | 1 (Standard), 2 |
| No parity (standard); even, uneven, mark (parity bit always 1); space (parity bit always 0) | No parity (standard); even, uneven, mark (parity bit always 1); space (parity bit always 0) |
3964 (R) | | |
| 1 kbyte | 1 kbyte |
| 7 or 8 | 7 or 8 |
| 1 (Standard), 2 | 1 (Standard), 2 |
| No parity (standard); even, uneven, mark (parity bit always 1); space (parity bit always 0) | No parity (standard); even, uneven, mark (parity bit always 1); space (parity bit always 0) |
Modbus RTU master | | |
| 1 through 49 999 (Standard Modbus addressing) | 1 through 49 999 (Standard Modbus addressing) |
| 247; slave numbers 1 through 247, per MODBUS network segment maximum 32 devices, additional repeaters needed to expand the network to maximum configuration | 247; slave numbers 1 through 247, per MODBUS network segment maximum 32 devices, additional repeaters needed to expand the network to maximum configuration |
MODBUS RTU slave | | |
| 1 through 49 999 (Standard Modbus addressing) | 1 through 49 999 (Standard Modbus addressing) |
Interrupts/diagnostics/status information | | |
Diagnostic functions | Yes | Yes |
Diagnostics indication LED | | |
| Yes | Yes |
Degree and class of protection | | |
Degree of protection acc. to EN 60529 | | |
| Yes | Yes |
Standards, approvals, certificates | | |
CE mark | Yes | Yes |
cULus | Yes | Yes |
FM approval | Yes | Yes |
RCM (formerly C-TICK) | Yes | Yes |
KC approval | Yes | Yes |
Ambient conditions | | |
Free fall | | |
| 0.3 m; five times, in product package | 0.3 m; five times, in product package |
Ambient temperature during operation | | |
| -20 °C | -20 °C |
| 60 °C | 60 °C |
| -20 °C | -20 °C |
| 60 °C | 60 °C |
| -20 °C | -20 °C |
| 50 °C | 50 °C |
| 5°C to 55°C, 3°C / minute | 5°C to 55°C, 3°C / minute |
Ambient temperature during storage/transportation | | |
| -40 °C | -40 °C |
| 70 °C | 70 °C |
Air pressure acc. to IEC 60068-2-13 | | |
| 795 hPa | 795 hPa |
| 1 080 hPa | 1 080 hPa |
| 660 hPa | 660 hPa |
| 1 080 hPa | 1 080 hPa |
Relative humidity | | |
| 95 % | 95 % |
Dimensions | | |
Width | 30 mm | 30 mm |
Height | 100 mm | 100 mm |
Depth | 75 mm | 75 mm |
Weights | | |
Weight, approx. | 155 g | 150 g |