Supply voltage | | | | | |
permissible range, lower limit (DC) | 20.4V | 20.4V | 20.4V | 20.4V | 20.4V |
permissible range, upper limit (DC) | 28.8V | 28.8V | 28.8V | 28.8V | 28.8V |
Input current | | | | | |
from backplane bus 5 V DC, max. | 120mA | 140mA | 120mA | 135mA | 140mA |
Digital outputs | | | | | |
| | | 11 mA/relay coil | 11 mA/relay coil | 16.7 mA/relay coil |
Power loss | | | | | |
Power loss, typ. | 1.5W | 2.5W | 4.5W | 8.5W | 5W |
Digital outputs | | | | | |
Number of digital outputs | 8 | 16 | 8 | 16 | 8 |
| 1 | 1 | 2 | 1 | 1 |
Short-circuit protection | No; to be provided externally | No; to be provided externally | No; to be provided externally | No; to be provided externally | No; to be provided externally |
Limitation of inductive shutdown voltage to | typ. (L+) -48 V | typ. (L+) -48 V | | | |
Switching capacity of the outputs | | | | | |
| 0.5A | 0.5A | 2A | 2A | 2A |
| 5W | 5W | 30 W with DC, 200 W with AC | 30 W with DC, 200 W with AC | 30 W with DC, 200 W with AC |
Output voltage | | | | | |
| 24V | 24V | 5 V DC to 30 V DC | 5 V DC to 30 V DC | 5 V DC to 30 V DC |
| | | 5 V AC to 250 V AC | 5 V AC to 250 V AC | 5 V AC to 250 V AC |
| 0.1V; with 10 kOhm load | 0.1V; with 10 kOhm load | | | |
| 20 V DC | 20 V DC | | | |
Output current | | | | | |
| 0.5A | 0.5A | 2A | 2A | 2A |
| 10A | 10A | | | |
Output delay with resistive load | | | | | |
| 50s | 50s | 10ms | 10ms | 10ms |
| 200s | 200s | 10ms | 10ms | 10ms |
Total current of the outputs (per group) | | | | | |
horizontal installation | | | | | |
| 4A; Current per mass | 8A; Current per mass | 10A; Current per mass | 10A; Current per mass | 2A; Current per mass |
Relay outputs | | | | | |
| | | 8 | 16 | 8 |
| | | 24V | 24V | 24V |
| | | mechanically 10 million, at rated load voltage 100 000 | mechanically 10 million, at rated load voltage 100 000 | mechanically 10 million, at rated load voltage 100 000 |
Switching capacity of contacts | | | | | |
| 0.5A | 0.5A | 2A | 2A | 2A |
| 5W | 5W | 30 W with DC, 200 W with AC | 30 W with DC, 200 W with AC | 30 W with DC, 200 W with AC |
| 0.5A | 0.5A | 2A | 2A | 2A |
Cable length | | | | | |
| 500m | 500m | 500m | 500m | 500m |
| 150m | 150m | 150m | 150m | 150m |
Interrupts/diagnostics/status information | | | | | |
Alarms | | | | | |
| Yes | Yes | Yes | Yes | Yes |
Diagnostics indication LED | | | | | |
| Yes | Yes | Yes | Yes | Yes |
Potential separation | | | | | |
Potential separation digital outputs | | | | | |
| | | Relays | Relays | Relays |
| 1 | 1 | 2 | 4 | 1 |
| 500 V AC | 500 V AC | 1500 V AC for 1 minute | 1500 V AC for 1 minute | 1500 V AC for 1 minute |
Permissible potential difference | | | | | |
between different circuits | | | 750 V AC for 1 minute | 750 V AC for 1 minute | 750 V AC for 1 minute |
Degree and class of protection | | | | | |
Degree of protection acc. to EN 60529 | | | | | |
| Yes | Yes | Yes | Yes | Yes |
Standards, approvals, certificates | | | | | |
CE mark | Yes | Yes | Yes | Yes | Yes |
CSA approval | Yes | Yes | Yes | Yes | Yes |
UL approval | Yes | Yes | Yes | Yes | Yes |
cULus | Yes | Yes | Yes | Yes | Yes |
FM approval | Yes | Yes | Yes | Yes | Yes |
RCM (formerly C-TICK) | Yes | Yes | Yes | Yes | Yes |
Marine approval | Yes | Yes | Yes | Yes | Yes |
Ambient conditions | | | | | |
Free fall | | | | | |
| 0.3m; five times, in product package | 0.3m; five times, in product package | 0.3m; five times, in product package | 0.3m; five times, in product package | 0.3m; five times, in product package |
Ambient temperature during operation | | | | | |
| -20C | -20C | -20C | -20C | -20C |
| 60C | 60C | 60C | 60C; Number of simultaneously activated outputs: 8 (no adjacent points) at 60 C horizontal or 50 C vertical, 16 at 55 C horizontal or 45 C vertical | 60C; Number of simultaneously activated outputs: 4 (no adjacent points) at 60 C horizontal or 50 C vertical, 8 at 55 C horizontal or 45 C vertical |
| -20C | -20C | -20C | -20C | -20C |
| 60C | 60C | 60C | 60C | 60C |
| -20C | -20C | -20C | -20C | -20C |
| 50C | 50C | 50C | 50C | 50C |
| 5C to 55C, 3C / minute | 5C to 55C, 3C / minute | 5C to 55C, 3C / minute | 5C to 55C, 3C / minute | 5C to 55C, 3C / minute |
Ambient temperature during storage/transportation | | | | | |
| -40C | -40C | -40C | -40C | -40C |
| 70C | 70C | 70C | 70C | 70C |
Air pressure acc. to IEC 60068-2-13 | | | | | |
| 660hPa | 660hPa | 660hPa | 660hPa | 660hPa |
| 1080hPa | 1080hPa | 1080hPa | 1080hPa | 1080hPa |
Relative humidity | | | | | |
| 95% | 95% | 95% | 95% | 95% |
Connection method | | | | | |
required front connector | Yes | Yes | Yes | Yes | Yes |
Mechanics/material | | | | | |
Enclosure material (front) | | | | | |
| Yes | Yes | Yes | Yes | Yes |
Dimensions | | | | | |
Width | 45mm | 45mm | 45mm | 45mm | 70mm |
Height | 100mm | 100mm | 100mm | 100mm | 100mm |
Depth | 75mm | 75mm | 75mm | 75mm | 75mm |
Weights | | | | | |
Weight, approx. | 180g | 220g | 190g | 260g | 310g |