Supply voltage | |
Load voltage L+ | |
| 24 V |
| 20.4 V |
| 28.8 V |
| Yes |
Input current | |
from load voltage L+ (without load), max. | 42 mA |
from backplane bus 3.3 V DC, max. | 10 mA |
Encoder supply | |
24 V encoder supply | |
| Yes; L+ (-0.8 V) |
| Yes |
| 500 mA |
Power loss | |
Power loss, typ. | 1 W |
Hardware configuration | |
Module exchange | |
| Yes |
| Yes |
Digital inputs | |
Number of digital inputs | 1 |
Functions | Gate control, synchronization, latch function |
Input characteristic curve in accordance with IEC 61131, type 2 | Yes |
Input voltage | |
| 24 V |
| -30 to +5V |
| +11 to +30V |
Input current | |
| 2 mA |
| 9 mA |
Input delay (for rated value of input voltage) | |
for standard inputs | |
| 2.5 µs; Filter off: 2.5 µs (200 kHz), filter on: 25 µs (20 kHz) |
Cable length | |
| 100 m; Filter 20 kHz: 100 m, filter 200 kHz: 50 m |
Digital outputs | |
Number of digital outputs | 1 |
Short-circuit protection | Yes |
| 2.6 A to 4 A |
Limitation of inductive shutdown voltage to | L+ (-50 to -60 V) |
Controlling a digital input | Yes |
Switching capacity of the outputs | |
| 5 W |
Output voltage | |
| 24 V |
| 3 V |
| L+ (-1 V) |
Output current | |
| 5 mA |
| 2 000 mA |
| 5 mA |
| 500 mA; 1000 mA at 50 °C |
| 0.5 mA |
Output delay with resistive load | |
| 100 µs |
Switching frequency | |
| 100 Hz |
| 2 Hz |
| 10 Hz |
Cable length | |
| 1 000 m |
| 600 m |
Encoder | |
Number of connectable encoders, max. | 1 |
Connectable encoders | |
| Yes |
| Yes |
| Yes |
Interrupts/diagnostics/status information | |
Diagnostic functions | Yes |
Diagnostics indication LED | |
| Yes |
| Yes |
| Yes |
| Yes |
| Yes |
Integrated Functions | |
Measuring functions | |
Measuring range | |
| 0.1 Hz |
| 100 kHz |
| 10 µs |
| 120 s |
| 1 1/min |
| 25 000 1/min |
Counter | |
Number of counter inputs | 1; 32 bit |
Minimum pulse width | 2.5 µs; Filter off: 2.5 µs (200 kHz), filter on: 25 µs (20 kHz) |
Parameter | |
Remark | 16 byte |
Potential separation | |
Potential separation digital inputs | |
| No; only opposite shielding |
Potential separation counter | |
| Yes |
| No |
Ambient conditions | |
Altitude during operation relating to sea level | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Relative humidity | |
| 100 %; RH incl. condensation/frost permitted (no commissioning in bedewed state) |
Resistance | |
Use in stationary industrial systems | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Dimensions | |
Width | 15 mm |
Height | 81 mm |
Depth | 52 mm |
Weights | |
Weight, approx. | 40 g |