Article number

6AG1317-2FK14-2AB0

6AG1317-2FK14-2AY0

SIPLUS S7-300 CPU317F-2PN/DP

SIPLUS S7-300 CPU317F-2PN/DP EN50155

General information

 

 

HW functional status

01

01

Firmware version

V3.2

V3.2

Engineering with

 

 

  • в—Џ Programming package

STEP 7 V5.5 or higher, Distributed Safety V5.4 SP4

STEP 7 V5.5 or higher, Distributed Safety V5.4 SP4

Supply voltage

 

 

Rated value (DC)

  • в—Џ 24 V DC

Yes

Yes; A power supply according to EN 50155 shall be used

permissible range, lower limit (DC)

20.4 V

20.4 V

permissible range, upper limit (DC)

28.8 V

28.8 V

external protection for power supply lines (recommendation)

2 A min.

2 A min.

Mains buffering

 

 

  • в—Џ Mains/voltage failure stored energy time

5 ms

  • в—Џ Repeat rate, min.

1 s

Input current

 

 

Current consumption (rated value)

750 mA

750 mA

Current consumption (in no-load operation), typ.

150 mA

150 mA

Inrush current, typ.

4 A

4 A

IІt

1 AІ·s

1 AІ·s

Power loss

 

 

Power loss, typ.

4.65 W

4.65 W

Memory

 

 

Work memory

 

 

  • в—Џ integrated

1 536 kbyte

1 536 kbyte

  • в—Џ expandable

No

No

  • в—Џ Size of retentive memory for retentive data blocks

256 kbyte

256 kbyte

Load memory

 

 

  • в—Џ Plug-in (MMC)

Yes

Yes

  • в—Џ Plug-in (MMC), max.

8 Mbyte

8 Mbyte

  • в—Џ Data management on MMC (after last programming), min.

10 y

10 y

Backup

 

 

  • в—Џ present

Yes; Guaranteed by MMC (maintenance-free)

Yes; Guaranteed by MMC (maintenance-free)

  • в—Џ without battery

Yes; Program and data

Yes; Program and data

CPU processing times

 

 

for bit operations, typ.

0.025 µs

0.025 µs

for word operations, typ.

0.03 µs

0.03 µs

for fixed point arithmetic, typ.

0.04 µs

0.04 µs

for floating point arithmetic, typ.

0.16 µs

0.16 µs

CPU-blocks

 

 

Number of blocks (total)

2 048; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used.

2 048; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used.

DB

 

 

  • в—Џ Number, max.

2 048; Number range: 1 to 16000

2 048; Number range: 1 to 16000

  • в—Џ Size, max.

64 kbyte

64 kbyte

FB

 

 

  • в—Џ Number, max.

2 048; Number range: 0 to 7999

2 048; Number range: 0 to 7999

  • в—Џ Size, max.

64 kbyte

64 kbyte

FC

 

 

  • в—Џ Number, max.

2 048; Number range: 0 to 7999

2 048; Number range: 0 to 7999

  • в—Џ Size, max.

64 kbyte

64 kbyte

OB

 

 

  • в—Џ Size, max.

64 kbyte

64 kbyte

  • в—Џ Number of free cycle OBs

1; OB 1

1; OB 1

  • в—Џ Number of time alarm OBs

1; OB 10

1; OB 10

  • в—Џ Number of delay alarm OBs

2; OB 20, 21

2; OB 20, 21

  • в—Џ Number of cyclic interrupt OBs

4; OB 32, 33, 34, 35

4; OB 32, 33, 34, 35

  • в—Џ Number of process alarm OBs

1; OB 40

1; OB 40

  • в—Џ Number of DPV1 alarm OBs

3; OB 55, 56, 57

3; OB 55, 56, 57

  • в—Џ Number of isochronous mode OBs

1; OB 61 - isochronous mode is possible either on DP or PROFINET IO (not simultaneously)

1; OB 61 - isochronous mode is possible either on DP or PROFINET IO (not simultaneously)

  • в—Џ Number of startup OBs

1; OB 100

1; OB 100

  • в—Џ Number of asynchronous error OBs

6; OB 80, 82, 83, 85, 86, 87 (OB83 only for PROFINET IO)

6; OB 80, 82, 83, 85, 86, 87 (OB83 only for PROFINET IO)

  • в—Џ Number of synchronous error OBs

2; OB 121, 122

2; OB 121, 122

Nesting depth

 

 

  • в—Џ per priority class

16

16

  • в—Џ additional within an error OB

4

4

Counters, timers and their retentivity

 

 

S7 counter

 

 

  • в—Џ Number

512

512

Retentivity

 

 

  • — adjustable

Yes

Yes

  • — lower limit

0

0

  • — upper limit

511

511

  • — preset

Z 0 to Z 7

Z 0 to Z 7

Counting range

 

 

  • — can be set

Yes

Yes

  • — lower limit

0

0

  • — upper limit

999

999

IEC counter

 

 

  • в—Џ Number

Unlimited (limited only by RAM capacity)

Unlimited (limited only by RAM capacity)

S7 times

 

 

  • в—Џ Number

512

512

Retentivity

 

 

  • — adjustable

Yes

Yes

  • — lower limit

0

0

  • — upper limit

511

511

  • — preset

No retentivity

No retentivity

Time range

 

 

  • — lower limit

10 ms

10 ms

  • — upper limit

9 990 s

9 990 s

IEC timer

 

 

  • в—Џ present

Yes

Yes

  • в—Џ Type

SFB

SFB

  • в—Џ Number

Unlimited (limited only by RAM capacity)

Unlimited (limited only by RAM capacity)

Data areas and their retentivity

 

 

retentive data area in total

All, max. 256 KB

All, max. 256 KB

Flag

 

 

  • в—Џ Number, max.

4 096 byte

4 096 byte

  • в—Џ Retentivity available

Yes; From MB 0 to MB 4095

Yes; From MB 0 to MB 4095

  • в—Џ Retentivity preset

MB 0 to MB 15

MB 0 to MB 15

  • в—Џ Number of clock memories

8; 1 memory byte

8; 1 memory byte

Data blocks

 

 

  • в—Џ Retentivity adjustable

Yes; via non-retain property on DB

Yes; via non-retain property on DB

  • в—Џ Retentivity preset

Yes

Yes

Local data

 

 

  • в—Џ per priority class, max.

32 768 byte; Max. 2048 bytes per block

32 768 byte; Max. 2048 bytes per block

Address area

 

 

I/O address area

 

 

  • в—Џ Inputs

8 192 byte

8 192 byte

  • в—Џ Outputs

8 192 byte

8 192 byte

of which distributed

 

 

  • — Inputs

8 192 byte

8 192 byte

  • — Outputs

8 192 byte

8 192 byte

Process image

 

 

  • в—Џ Inputs

8 192 byte

8 192 byte

  • в—Џ Outputs

8 192 byte

8 192 byte

  • в—Џ Inputs, adjustable

8 192 byte

8 192 byte

  • в—Џ Outputs, adjustable

8 192 byte

8 192 byte

  • в—Џ Inputs, default

256 byte

256 byte

  • в—Џ Outputs, default

256 byte

256 byte

Subprocess images

 

 

  • в—Џ Number of subprocess images, max.

1; With PROFINET IO, the length of the user data is limited to 1600 bytes

1; With PROFINET IO, the length of the user data is limited to 1600 bytes

Digital channels

 

 

  • в—Џ Inputs

65 536

65 536

  • — of which central

1 024

1 024

  • в—Џ Outputs

65 536

65 536

  • — of which central

1 024

1 024

Analog channels

 

 

  • в—Џ Inputs

4 096

4 096

  • — of which central

256

256

  • в—Џ Outputs

4 096

4 096

  • — of which central

256

256

Hardware configuration

 

 

Number of expansion units, max.

3

3

Number of DP masters

 

 

  • в—Џ integrated

1

1

  • в—Џ via CP

4

4

Number of operable FMs and CPs (recommended)

 

 

  • в—Џ FM

8

8

  • в—Џ CP, PtP

8

8

  • в—Џ CP, LAN

10

10

Rack

 

 

  • в—Џ Racks, max.

4

4

  • в—Џ Modules per rack, max.

8

8

Time of day

 

 

Clock

 

 

  • в—Џ Hardware clock (real-time)

Yes

Yes

  • в—Џ retentive and synchronizable

Yes

Yes

  • в—Џ Backup time

6 wk; At 40 °C ambient temperature

6 wk; At 40 °C ambient temperature

  • в—Џ Deviation per day, max.

10 s; Typ.: 2 s

10 s; Typ.: 2 s

  • в—Џ Behavior of the clock following POWER-ON

Clock continues running after POWER OFF

Clock continues running after POWER OFF

  • в—Џ Behavior of the clock following expiry of backup period

Clock continues to run with the time at which the power failure occurred

Clock continues to run with the time at which the power failure occurred

Operating hours counter

 

 

  • в—Џ Number

4

4

  • в—Џ Number/Number range

0 to 3

0 to 3

  • в—Џ Range of values

0 to 2^31 hours (when using SFC 101)

0 to 2^31 hours (when using SFC 101)

  • в—Џ Granularity

1 hour

1 hour

  • в—Џ retentive

Yes; Must be restarted at each restart

Yes; Must be restarted at each restart

Clock synchronization

 

 

  • в—Џ supported

Yes

Yes

  • в—Џ to MPI, master

Yes

Yes

  • в—Џ to MPI, slave

Yes

Yes

  • в—Џ to DP, master

Yes; With DP slave only slave clock

Yes; With DP slave only slave clock

  • в—Џ to DP, slave

Yes

Yes

  • в—Џ in AS, master

Yes

Yes

  • в—Џ in AS, slave

Yes

Yes

  • в—Џ on Ethernet via NTP

Yes; As client

Yes; As client

Digital inputs

 

 

Number of digital inputs

0

0

Digital outputs

 

 

Number of digital outputs

0

0

Analog inputs

 

 

Number of analog inputs

0

0

Analog outputs

 

 

Number of analog outputs

0

0

Interfaces

 

 

Number of industrial Ethernet interfaces

1

1

Number of PROFINET interfaces

1

1

Number of RS 485 interfaces

1

1

Number of RS 422 interfaces

0

0

1. Interface

 

 

Interface type

Integrated RS 485 interface

Integrated RS 485 interface

Physics

RS 485

RS 485

Isolated

Yes

Yes

Power supply to interface (15 to 30 V DC), max.

200 mA

200 mA

Functionality

 

 

  • в—Џ MPI

Yes

Yes

  • в—Џ PROFIBUS DP master

Yes

Yes

  • в—Џ PROFIBUS DP slave

Yes

Yes

  • в—Џ Point-to-point connection

No

No

MPI

 

 

  • в—Џ Transmission rate, max.

12 Mbit/s

12 Mbit/s

Services

 

 

  • — PG/OP communication

Yes

Yes

  • — Routing

Yes

Yes

  • — Global data communication

Yes

Yes

  • — S7 basic communication

Yes

Yes

  • — S7 communication

Yes

Yes

  • — S7 communication, as client

No; but via CP and loadable FB

No; but via CP and loadable FB

  • — S7 communication, as server

Yes

Yes

DP master

 

 

  • в—Џ Transmission rate, max.

12 Mbit/s

12 Mbit/s

  • в—Џ Number of DP slaves, max.

124

124

Services

 

 

  • — PG/OP communication

Yes

Yes

  • — Routing

Yes

Yes

  • — Global data communication

No

No

  • — S7 basic communication

Yes; I blocks only

Yes; I blocks only

  • — S7 communication

Yes

Yes

  • — S7 communication, as client

No

No

  • — S7 communication, as server

Yes

Yes

  • — Equidistance

Yes

Yes

  • — Isochronous mode

Yes; OB 61; isochronous mode can only be used alternatively on PROFIBUS DP or PROFINET IO

Yes; OB 61; isochronous mode can only be used alternatively on PROFIBUS DP or PROFINET IO

  • — SYNC/FREEZE

Yes

Yes

  • — Activation/deactivation of DP slaves

Yes

Yes

  • — Number of DP slaves that can be simultaneously activated/deactivated, max.

8

8

  • — Direct data exchange (slave-to-slave communication)

Yes; As subscriber

Yes; As subscriber

  • — DPV1

Yes

Yes

Address area

 

 

  • — Inputs, max.

8 kbyte

8 kbyte

  • — Outputs, max.

8 kbyte

8 kbyte

User data per DP slave

 

 

  • — Inputs, max.

244 byte

244 byte

  • — Outputs, max.

244 byte

244 byte

DP slave

 

 

  • в—Џ Transmission rate, max.

12 Mbit/s

12 Mbit/s

  • в—Џ automatic baud rate search

Yes; only with passive interface

Yes; only with passive interface

  • в—Џ Address area, max.

32

32

  • в—Џ User data per address area, max.

32 byte

32 byte

Services

 

 

  • — PG/OP communication

Yes

Yes

  • — Routing

Yes; Only with active interface

Yes; Only with active interface

  • — Global data communication

No

No

  • — S7 basic communication

No

No

  • — S7 communication

Yes

Yes

  • — S7 communication, as client

No

No

  • — S7 communication, as server

Yes; Connection configured on one side only

Yes; Connection configured on one side only

  • — Direct data exchange (slave-to-slave communication)

Yes

Yes

  • — DPV1

No

No

Transfer memory

 

 

  • — Inputs

244 byte

244 byte

  • — Outputs

244 byte

244 byte

2. Interface

 

 

Interface type

PROFINET

PROFINET

Physics

Ethernet RJ45

Ethernet RJ45

Isolated

Yes

Yes

automatic detection of transmission rate

Yes; 10/100 Mbit/s

Yes; 10/100 Mbit/s

Autonegotiation

Yes

Yes

Autocrossing

Yes

Yes

Change of IP address at runtime, supported

Yes

Yes

Interface types

 

 

  • в—Џ Number of ports

2

2

  • в—Џ integrated switch

Yes

Yes

Media redundancy

 

 

  • в—Џ supported

Yes

Yes

  • в—Џ Switchover time on line break, typ.

200 ms; PROFINET MRP

200 ms; PROFINET MRP

  • в—Џ Number of stations in the ring, max.

50

50

Functionality

 

 

  • в—Џ MPI

No

No

  • в—Џ PROFINET IO Controller

Yes; Also simultaneously with IO-Device functionality

Yes; Also simultaneously with IO-Device functionality

  • в—Џ PROFINET IO Device

Yes; Also simultaneously with IO Controller functionality

Yes; Also simultaneously with IO Controller functionality

  • в—Џ PROFINET CBA

Yes

Yes

  • в—Џ PROFIBUS DP master

No

No

  • в—Џ PROFIBUS DP slave

No

No

  • в—Џ Open IE communication

Yes; Via TCP/IP, ISO on TCP, and UDP

Yes; Via TCP/IP, ISO on TCP, and UDP

  • в—Џ Web server

Yes

Yes

PROFINET IO Controller

 

 

  • в—Џ Transmission rate, max.

100 Mbit/s

100 Mbit/s

Services

 

 

  • — PG/OP communication

Yes

Yes

  • — Routing

Yes

Yes

  • — S7 communication

Yes; with loadable FBs, max. configurable connections: 16, max. number of instances: 32

Yes; with loadable FBs, max. configurable connections: 16, max. number of instances: 32

  • — Isochronous mode

Yes; OB 61; isochronous mode can only be used alternatively on PROFIBUS DP or PROFINET IO

Yes; OB 61; isochronous mode can only be used alternatively on PROFIBUS DP or PROFINET IO

  • — Open IE communication

Yes; Via TCP/IP, ISO on TCP, and UDP

Yes; Via TCP/IP, ISO on TCP, and UDP

  • — IRT

Yes

Yes

  • — Shared device

Yes

Yes

  • — Prioritized startup

Yes

Yes

  • — Number of IO devices with prioritized startup, max.

32

32

  • — Number of connectable IO Devices, max.

128

128

  • — Of which IO devices with IRT, max.

64

64

  • — of which in line, max.

64

64

  • — Number of IO Devices with IRT and the option "high flexibility"

128

128

  • — of which in line, max.

61

61

  • — Number of connectable IO Devices for RT, max.

128

128

  • — of which in line, max.

128

128

  • — Activation/deactivation of IO Devices

Yes

Yes

  • — Number of IO Devices that can be simultaneously activated/deactivated, max.

8

8

  • — IO Devices changing during operation (partner ports), supported

Yes

Yes

  • — Number of IO Devices per tool, max.

8

8

  • — Device replacement without swap medium

Yes

Yes

  • — Send cycles

250 Ојs, 500 Ојs,1 ms; 2 ms, 4 ms (not in the case of IRT with "high flexibility" option)

250 Ојs, 500 Ојs,1 ms; 2 ms, 4 ms (not in the case of IRT with "high flexibility" option)

  • — Updating time

250 µs to 512 ms (depending on the operating mode, see Manual "S7-300 CPU 31xC and CPU 31x, Technical Data" for more details)

250 µs to 512 ms (depending on the operating mode, see Manual "S7-300 CPU 31xC and CPU 31x, Technical Data" for more details)

Address area

 

 

  • — Inputs, max.

8 kbyte

8 kbyte

  • — Outputs, max.

8 kbyte

8 kbyte

  • — User data consistency, max.

1 024 byte

1 024 byte

PROFINET IO Device

 

 

Services

 

 

  • — PG/OP communication

Yes

Yes

  • — Routing

Yes

Yes

  • — S7 communication

Yes; with loadable FBs, max. configurable connections: 16, max. number of instances: 32

Yes; with loadable FBs, max. configurable connections: 16, max. number of instances: 32

  • — Isochronous mode

No

No

  • — Open IE communication

Yes; Via TCP/IP, ISO on TCP, and UDP

Yes; Via TCP/IP, ISO on TCP, and UDP

  • — IRT

Yes

Yes

  • — PROFIenergy

Yes; With SFB 73 / 74 prepared for loadable PROFIenergy standard FB for I-Device

Yes; With SFB 73 / 74 prepared for loadable PROFIenergy standard FB for I-Device

  • — Shared device

Yes

Yes

  • — Number of IO Controllers with shared device, max.

2

2

Transfer memory

 

 

  • — Inputs, max.

1 440 byte; Per IO Controller with shared device

1 440 byte; Per IO Controller with shared device

  • — Outputs, max.

1 440 byte; Per IO Controller with shared device

1 440 byte; Per IO Controller with shared device

Submodules

 

 

  • — Number, max.

64

64

  • — User data per submodule, max.

1 024 byte

1 024 byte

PROFINET CBA

 

 

  • в—Џ acyclic transmission

Yes

Yes

  • в—Џ cyclic transmission

Yes

Yes

Open IE communication

 

 

  • в—Џ Number of connections, max.

16

16

  • в—Џ Local port numbers used at the system end

0, 20, 21, 25, 80, 102, 135, 161, 8080, 34962, 34963, 34964, 65532, 65533, 65534, 65535

0, 20, 21, 25, 80, 102, 135, 161, 8080, 34962, 34963, 34964, 65532, 65533, 65534, 65535

  • в—Џ Keep-alive function, supported

Yes

Yes

Protocols

 

 

Open IE communication

 

 

  • в—Џ TCP/IP

Yes; via integrated PROFINET interface and loadable FBs

Yes; via integrated PROFINET interface and loadable FBs

  • — Data length for connection type 01H, max.

1 460 byte

1 460 byte

  • — Data length for connection type 11H, max.

32 768 byte

32 768 byte

  • — several passive connections per port, supported

Yes

Yes

  • в—Џ ISO-on-TCP (RFC1006)

Yes; via integrated PROFINET interface and loadable FBs

Yes; via integrated PROFINET interface and loadable FBs

  • — Data length, max.

32 768 byte

32 768 byte

  • в—Џ UDP

Yes; via integrated PROFINET interface and loadable FBs

Yes; via integrated PROFINET interface and loadable FBs

  • — Data length, max.

1 472 byte

1 472 byte

Web server

 

 

  • в—Џ User-defined websites

Yes

Yes

  • в—Џ Number of HTTP clients

5

5

Isochronous mode

 

 

Isochronous operation (application synchronized up to terminal)

Yes; Via PROFIBUS DP or PROFINET interface

Yes; Via PROFIBUS DP or PROFINET interface

Communication functions

 

 

PG/OP communication

Yes

Yes

Data record routing

Yes

Yes

Global data communication

 

 

  • в—Џ supported

Yes

Yes

  • в—Џ Number of GD loops, max.

8

8

  • в—Џ Number of GD packets, max.

8

8

  • в—Џ Number of GD packets, transmitter, max.

8

8

  • в—Џ Number of GD packets, receiver, max.

8

8

  • в—Џ Size of GD packets, max.

22 byte

22 byte

  • в—Џ Size of GD packet (of which consistent), max.

22 byte

22 byte

S7 basic communication

 

 

  • в—Џ supported

Yes

Yes

  • в—Џ User data per job, max.

76 byte

76 byte

  • в—Џ User data per job (of which consistent), max.

76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server)

76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server)

S7 communication

 

 

  • в—Џ supported

Yes

Yes

  • в—Џ as server

Yes

Yes

  • в—Џ as client

Yes; via integrated PROFINET interface and loadable FB or via CP and loadable FB

Yes; via integrated PROFINET interface and loadable FB or via CP and loadable FB

  • в—Џ User data per job, max.

See online help of STEP 7 (shared parameters of the SFBs/FBs and of the SFCs/FCs of S7 Communication)

See online help of STEP 7 (shared parameters of the SFBs/FBs and of the SFCs/FCs of S7 Communication)

S5 compatible communication

 

 

  • в—Џ supported

Yes; via CP and loadable FC

Yes; via CP and loadable FC

Web server

 

 

  • в—Џ supported

Yes

Yes

PROFINET CBA (at set setpoint communication load)

 

 

  • в—Џ Setpoint for the CPU communication load

50 %

50 %

  • в—Џ Number of remote interconnection partners

32

32

  • в—Џ Number of functions, master/slave

30

30

  • в—Џ Total of all master/slave connections

1 000

1 000

  • в—Џ Data length of all incoming connections master/slave, max.

4 000 byte

4 000 byte

  • в—Џ Data length of all outgoing connections master/slave, max.

4 000 byte

4 000 byte

  • в—Џ Number of device-internal and PROFIBUS interconnections

500

500

  • в—Џ Data length of device-internal und PROFIBUS interconnections, max.

4 000 byte

4 000 byte

  • в—Џ Data length per connection, max.

1 400 byte

1 400 byte

Remote interconnections with acyclic transmission

 

 

  • — Sampling frequency: Sampling time, min.

500 ms

500 ms

  • — Number of incoming interconnections

100

100

  • — Number of outgoing interconnections

100

100

  • — Data length of all incoming interconnections, max.

2 000 byte

2 000 byte

  • — Data length of all outgoing interconnections, max.

2 000 byte

2 000 byte

  • — Data length per connection, max.

1 400 byte

1 400 byte

Remote interconnections with cyclic transmission

 

 

  • — Transmission frequency: Transmission interval, min.

10 ms

10 ms

  • — Number of incoming interconnections

200

200

  • — Number of outgoing interconnections

200

200

  • — Data length of all incoming interconnections, max.

2 000 byte

2 000 byte

  • — Data length of all outgoing interconnections, max.

2 000 byte

2 000 byte

  • — Data length per connection, max.

450 byte

450 byte

HMI variables via PROFINET (acyclic)

 

 

  • — Number of stations that can log on for HMI variables (PN OPC/iMap)

3; 2x PN OPC/1x iMap

3; 2x PN OPC/1x iMap

  • — HMI variable updating

500 ms

500 ms

  • — Number of HMI variables

200

200

  • — Data length of all HMI variables, max.

2 000 byte

2 000 byte

PROFIBUS proxy functionality

 

 

  • — supported

Yes

Yes

  • — Number of linked PROFIBUS devices

16

16

  • — Data length per connection, max.

240 byte; Slave-dependent

240 byte; Slave-dependent

Number of connections

 

 

  • в—Џ overall

32

32

  • в—Џ usable for PG communication

31

31

  • — reserved for PG communication

1

1

  • — adjustable for PG communication, min.

1

1

  • — adjustable for PG communication, max.

31

31

  • в—Џ usable for OP communication

31

31

  • — reserved for OP communication

1

1

  • — adjustable for OP communication, min.

1

1

  • — adjustable for OP communication, max.

31

31

  • в—Џ usable for S7 basic communication

30

30

  • — reserved for S7 basic communication

0

0

  • — adjustable for S7 basic communication, min.

0

0

  • — adjustable for S7 basic communication, max.

30

30

  • в—Џ usable for S7 communication

16

16

  • — reserved for S7 communication

0

0

  • — adjustable for S7 communication, min.

0

0

  • — adjustable for S7 communication, max.

16

16

  • в—Џ total number of instances, max.

32

32

  • в—Џ usable for routing

X1 as MPI: max. 10; X1 as DP master: max. 24; X1 as DP slave (active): max. 14; X2 as PROFINET: 24 max.

X1 as MPI: max. 10; X1 as DP master: max. 24; X1 as DP slave (active): max. 14; X2 as PROFINET: 24 max.

S7 message functions

 

 

Number of login stations for message functions, max.

32; Depending on the configured connections for PG/OP and S7 basic communication

32; Depending on the configured connections for PG/OP and S7 basic communication

Process diagnostic messages

Yes

Yes

simultaneously active Alarm-S blocks, max.

300

300

Test commissioning functions

 

 

Status block

Yes; Up to 2 simultaneously

Yes; Up to 2 simultaneously

Single step

Yes

Yes

Number of breakpoints

4

4

Status/control

 

 

  • в—Џ Status/control variable

Yes

Yes

  • в—Џ Variables

Inputs, outputs, memory bits, DB, times, counters

Inputs, outputs, memory bits, DB, times, counters

  • в—Џ Number of variables, max.

30

30

  • — of which status variables, max.

30

30

  • — of which control variables, max.

14

14

Forcing

 

 

  • в—Џ Forcing

Yes

Yes

  • в—Џ Forcing, variables

Inputs, outputs

Inputs, outputs

  • в—Џ Number of variables, max.

10

10

Diagnostic buffer

 

 

  • в—Џ present

Yes

Yes

  • в—Џ Number of entries, max.

500

500

  • — adjustable

No

No

  • — of which powerfail-proof

100; Only the last 100 entries are retained

100; Only the last 100 entries are retained

  • в—Џ Number of entries readable in RUN, max.

499

499

  • — can be set

Yes; From 10 to 499

Yes; From 10 to 499

  • — preset

10

10

Service data

 

 

  • в—Џ can be read out

Yes

Yes

Isolation

 

 

Isolation tested with

500V AC for 1 minute

Standards, approvals, certificates

 

 

CE mark

Yes

Yes

UL approval

Yes; File E239877

Yes; File E239877

FM approval

Yes; CofC 3028431

Yes; CofC 3028431

RCM (formerly C-TICK)

Yes

Yes

KC approval

Yes

Yes

EAC (formerly Gost-R)

Yes

Yes

Railway application

 

 

  • в—Џ EN 50155

No

Yes; Sections 4, 5 and 12; no further agreements apply; T1, Category 1, Class A/B

Use in hazardous areas

 

 

  • в—Џ ATEX

Yes

Yes

Ambient conditions

 

 

Ambient temperature during operation

 

 

  • в—Џ min.

-25 °C; = Tmin

-25 °C; = Tmin

  • в—Џ max.

60 °C; = Tmax

60 °C; = Tmax; the rated temperature range of -25 ... +55 °C (T1) applies for the use on railway vehicles according to EN50155

Ambient temperature during storage/transportation

 

 

  • в—Џ min.

-40 °C

-40 °C

  • в—Џ max.

70 °C

70 °C

Altitude during operation relating to sea level

 

 

  • в—Џ Ambient air temperature-barometric pressure-altitude

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)

Relative humidity

 

 

  • в—Џ With condensation, tested in accordance with IEC 60068-2-38, max.

100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation

100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation

Resistance

 

 

Use in stationary industrial systems

 

 

  • — to biologically active substances according to EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation in corrosive atmospheres!

  • — to chemically active substances according to EN 60721-3-3

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

  • — to mechanically active substances according to EN 60721-3-3

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Configuration

 

 

Configuration software

 

 

  • в—Џ STEP 7

Yes; V5.5 or higher

Yes; V5.5 or higher

Programming

 

 

  • в—Џ Command set

see instruction list

see instruction list

  • в—Џ Nesting levels

8

8

  • в—Џ System functions (SFC)

see instruction list

see instruction list

  • в—Џ System function blocks (SFB)

see instruction list

see instruction list

Programming language

 

 

  • — LAD

Yes

Yes

  • — FBD

Yes

Yes

  • — STL

Yes

Yes

  • — SCL

Yes

Yes

  • — CFC

Yes

Yes

  • — GRAPH

Yes

Yes

  • — HiGraph®

Yes

Yes

Know-how protection

 

 

  • в—Џ User program protection/password protection

Yes

Yes

  • в—Џ Block encryption

Yes; With S7 block Privacy

Yes; With S7 block Privacy

Dimensions

 

 

Width

40 mm

40 mm

Height

125 mm

125 mm

Depth

130 mm

130 mm

Weights

 

 

Weight, approx.

340 g

340 g


















skener.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Арматура DENDOR

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Датчики и измерители

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Регуляторы и регистраторы

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Пневматическое оборудование

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Краны и Клапаны

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Измерительные приборы

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Системы беспроводного управления «умный дом»

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Бесконтактные выключатели Конечные выключатели Оптические датчики Энкодеры

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Установка умягчения

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Установка обезжелезивания

  © ООО "СК ЭНЕРГО" 2007-2022
  (4872) 700-366  skenergo@mail.ru
Рейтинг@Mail.ru Яндекс.Метрика