General information | |
Product type designation | PN/PN coupler |
Firmware version | V4.0 |
| Yes |
Product function | |
| Yes; I&M0 to I&M3 |
Engineering with | |
| V2.3 |
Installation type/mounting | |
Mounting | Mounting rail 7.5 mm and 15 mm |
Supply voltage | |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 19.2 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Mains buffering | |
| 10 ms |
Input current | |
Current consumption, max. | 360 mA; For 19.2 V input voltage at the right-hand supply terminal, including 2 plugged BA 2x LC |
from supply voltage 1L+, max. | 320 mA; For 19.2 V input voltage at the left-hand supply terminal, including 2 plugged BA 2x LC |
Power loss | |
Power loss, typ. | 4 W; For 24 V input voltage and 2 plugged BA 2x RJ45 If BusAdapters with an optical interface are plugged, there is an additional 750 mW per optical interface (3 W with 2 plugged BA 2x LC) |
Address area | |
Address space per module | |
| 254 byte; max. 254 bytes of input data and 253 bytes of output data |
Address space per station | |
| 1 440 byte; per input / output |
Hardware configuration | |
Submodules | |
| 116 |
Interfaces | |
Number of PROFINET interfaces | 2; One PROFINET interface per line side |
With optical interface | Yes; Via SIMATIC BusAdapter |
PROFINET IO | |
| Yes |
| 100 Mbit/s |
| Yes; Via SIMATIC BusAdapter |
1. Interface | |
Interface types | |
| 2; via BusAdapter |
| Yes |
| Yes; Compatible BusAdapter: BA 2x RJ45, BA 2x FC, BA 2x SCRJ, BA SCRJ / RJ45, BA SCRJ / FC, BA 2x LC, BA LC / RJ45, BA LC / FC |
Functionality | |
| Yes |
| Yes |
| Yes; As MRP or MRPD client; max. 50 or 30 devices in the ring |
2. Interface | |
Interface types | |
| 2; via BusAdapter |
| Yes |
Functionality | |
| Yes |
| Yes |
| Yes; As MRP or MRPD client; max. 50 or 30 devices in the ring |
Interface types | |
RJ 45 (Ethernet) | |
| PROFINET with 100 Mbit/s full duplex (100BASE-TX) |
| No |
| Yes; PROFINET with 100 Mbit/s full duplex (100BASE-TX) |
| Yes |
| Yes |
Protocols | |
Supports protocol for PROFINET IO | Yes |
Protocols (Ethernet) | |
| Yes |
| Yes |
| Yes |
| Yes |
| Yes |
PROFINET IO Device | |
Services | |
| No |
| Yes |
| Yes |
| Yes |
| Yes |
| No |
| No |
| Yes |
| Yes |
| 4; per line side |
Open IE communication | |
| Yes |
| Yes |
| Yes |
Isochronous mode | |
Isochronous operation (application synchronized up to terminal) | No; For operation on isochronous bus |
Interrupts/diagnostics/status information | |
Status indicator | Yes |
Alarms | Yes |
Diagnostic functions | Yes |
Diagnostics indication LED | |
| Yes; Green LED |
| Yes; Red LED |
| Yes; yellow LED |
| Yes; green PWR LED |
| Yes; 2x green link LEDs on BusAdapter |
Potential separation | |
between supply voltage and electronics | Yes; to power input 2 |
between Ethernet and electronics | Yes |
Isolation | |
Isolation tested with | 707 V DC (type test) |
Standards, approvals, certificates | |
Network loading class | 3 |
Security level | According to Security Level 1 Test Cases V1.1.4 |
Ambient conditions | |
Ambient temperature during operation | |
| 0 °C |
| 60 °C; = Tmax for horizontal installation; for vertical installation Tmax = 50 °C |
Altitude during operation relating to sea level | |
| Up to max. 2 000 m |
Dimensions | |
Width | 100 mm; Minimized with good handling |
Height | 117 mm |
Depth | 74 mm; with mounting rail |
Weights | |
Weight, approx. | 200 g; without BusAdapter |