Siemens
01 2018
(4872) 700-366
skenergo@mail.ru

Article number

6AG1314-6CH04-2AY0

6AG1314-6CH04-7AB0

SIPLUS S7-300 CPU314C-2DP EN50155

SIPLUS S7-300 CPU314C-2DP

General information

HW functional status

01

01

Firmware version

V3.3

V3.3

Engineering with

  • Programming package

STEP 7 V5.5 + SP1 or higher or STEP 7 V5.3 + SP2 or higher with HSP 203

STEP 7 V5.5 + SP1 or higher or STEP 7 V5.3 + SP2 or higher with HSP 203

Supply voltage

Rated value (DC)

  • 24 V DC

Yes; A power supply according to EN 50155 shall be used

Yes

permissible range, lower limit (DC)

19.2V

19.2V

permissible range, upper limit (DC)

28.8V

28.8V

external protection for power supply lines (recommendation)

Miniature circuit breaker, type C; min. 2 A; miniature circuit breaker type B, min. 4 A

Miniature circuit breaker, type C; min. 2 A; miniature circuit breaker type B, min. 4 A

Mains buffering

  • Mains/voltage failure stored energy time

5ms

5ms

  • Repeat rate, min.

1s

1s

Load voltage L+

Digital inputs

  • Rated value (DC)

24V

24V

  • Reverse polarity protection

Yes

Yes

Digital outputs

  • Rated value (DC)

24V

24V

  • Reverse polarity protection

No

No

Input current

Current consumption (rated value)

880mA

880mA

Current consumption (in no-load operation), typ.

150mA

150mA

Inrush current, typ.

5A

5A

It

0.7As

0.7As

Digital inputs

  • from load voltage L+ (without load), max.

80mA

80mA

Digital outputs

  • from load voltage L+, max.

50mA

50mA

Power loss

Power loss, typ.

13W

13W

Memory

Work memory

  • integrated

192kbyte

192kbyte

  • expandable

No

No

  • Size of retentive memory for retentive data blocks

64kbyte

64kbyte

Load memory

  • Plug-in (MMC)

Yes

Yes

  • Plug-in (MMC), max.

8Mbyte

8Mbyte

  • Data management on MMC (after last programming), min.

10y

10y

Backup

  • present

Yes; Guaranteed by MMC (maintenance-free)

Yes; Guaranteed by MMC (maintenance-free)

  • without battery

Yes; Program and data

Yes; Program and data

CPU processing times

for bit operations, typ.

0.06s

0.06s

for word operations, typ.

0.12s

0.12s

for fixed point arithmetic, typ.

0.16s

0.16s

for floating point arithmetic, typ.

0.59s

0.59s

CPU-blocks

Number of blocks (total)

1024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used.

1024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used.

DB

  • Number, max.

1024; Number range: 1 to 16000

1024; Number range: 1 to 16000

  • Size, max.

64kbyte

64kbyte

FB

  • Number, max.

1024; Number range: 0 to 7999

1024; Number range: 0 to 7999

  • Size, max.

64kbyte

64kbyte

FC

  • Number, max.

1024; Number range: 0 to 7999

1024; Number range: 0 to 7999

  • Size, max.

64kbyte

64kbyte

OB

  • Description

see instruction list

see instruction list

  • Size, max.

64kbyte

64kbyte

  • Number of free cycle OBs

1; OB 1

1; OB 1

  • Number of time alarm OBs

1; OB 10

1; OB 10

  • Number of delay alarm OBs

2; OB 20, 21

2; OB 20, 21

  • Number of cyclic interrupt OBs

4; OB 32, 33, 34, 35

4; OB 32, 33, 34, 35

  • Number of process alarm OBs

1; OB 40

1; OB 40

  • Number of DPV1 alarm OBs

3; OB 55, 56, 57

3; OB 55, 56, 57

  • Number of startup OBs

1; OB 100

1; OB 100

  • Number of asynchronous error OBs

5; OB 80, 82, 85, 86, 87

5; OB 80, 82, 85, 86, 87

  • Number of synchronous error OBs

2; OB 121, 122

2; OB 121, 122

Nesting depth

  • per priority class

16

16

  • additional within an error OB

4

4

Counters, timers and their retentivity

S7 counter

  • Number

256

256

Retentivity

  • adjustable

Yes

Yes

  • lower limit

0

0

  • upper limit

255

255

  • preset

Z 0 to Z 7

Z 0 to Z 7

Counting range

  • lower limit

0

0

  • upper limit

999

999

IEC counter

  • Number

Unlimited (limited only by RAM capacity)

Unlimited (limited only by RAM capacity)

S7 times

  • Number

256

256

Retentivity

  • adjustable

Yes

Yes

  • lower limit

0

0

  • upper limit

255

255

  • preset

No retentivity

No retentivity

Time range

  • lower limit

10ms

10ms

  • upper limit

9990s

9990s

IEC timer

  • present

Yes

Yes

  • Type

SFB

SFB

  • Number

Unlimited (limited only by RAM capacity)

Unlimited (limited only by RAM capacity)

Data areas and their retentivity

retentive data area in total

All, max. 64 KB

All, max. 64 KB

Flag

  • Number, max.

256byte

256byte

  • Retentivity available

Yes; MB 0 to MB 255

Yes; MB 0 to MB 255

  • Retentivity preset

MB 0 to MB 15

MB 0 to MB 15

  • Number of clock memories

8; 1 memory byte

8; 1 memory byte

Data blocks

  • Retentivity adjustable

Yes; via non-retain property on DB

Yes; via non-retain property on DB

  • Retentivity preset

Yes

Yes

Local data

  • per priority class, max.

32kbyte; Max. 2048 bytes per block

32kbyte; Max. 2048 bytes per block

Address area

I/O address area

  • Inputs

2048byte

2048byte

  • Outputs

2048byte

2048byte

of which distributed

  • Inputs

2003byte

2003byte

  • Outputs

2010byte

2010byte

Process image

  • Inputs

2048byte

2048byte

  • Outputs

2048byte

2048byte

  • Inputs, adjustable

2048byte

2048byte

  • Outputs, adjustable

2048byte

2048byte

  • Inputs, default

128byte

128byte

  • Outputs, default

128byte

128byte

Default addresses of the integrated channels

  • Digital inputs

124.0 to 126.7

124.0 to 126.7

  • Digital outputs

124.0 to 125.7

124.0 to 125.7

  • Analog inputs

752 to 761

752 to 761

  • Analog outputs

752 to 755

752 to 755

Digital channels

  • Inputs

16048

16048

  • of which central

1016

1016

  • Outputs

16096

16096

  • of which central

1008

1008

Analog channels

  • Inputs

1006

1006

  • of which central

253

253

  • Outputs

1007

1007

  • of which central

250

250

Hardware configuration

Number of expansion units, max.

3

3

Number of DP masters

  • integrated

1

1

  • via CP

4

4

Number of operable FMs and CPs (recommended)

  • FM

8

8

  • CP, PtP

8

8

  • CP, LAN

10

10

Rack

  • Racks, max.

4

4

  • Modules per rack, max.

8; In rack 3 max. 7

8; In rack 3 max. 7

Time of day

Clock

  • Hardware clock (real-time)

Yes

Yes

  • retentive and synchronizable

Yes

Yes

  • Backup time

6wk; At 40 C ambient temperature

6wk; At 40 C ambient temperature

  • Deviation per day, max.

10s; Typ.: 2 s

10s; Typ.: 2 s

  • Behavior of the clock following POWER-ON

Clock continues running after POWER OFF

Clock continues running after POWER OFF

  • Behavior of the clock following expiry of backup period

Clock continues to run with the time at which the power failure occurred

Clock continues to run with the time at which the power failure occurred

Operating hours counter

  • Number

1

1

  • Number/Number range

0

0

  • Range of values

0 to 2^31 hours (when using SFC 101)

0 to 2^31 hours (when using SFC 101)

  • Granularity

1 hour

1 hour

  • retentive

Yes; Must be restarted at each restart

Yes; Must be restarted at each restart

Clock synchronization

  • supported

Yes

Yes

  • to MPI, master

Yes

Yes

  • to MPI, slave

Yes

Yes

  • to DP, master

Yes; With DP slave only slave clock

Yes; With DP slave only slave clock

  • to DP, slave

Yes

Yes

  • in AS, master

Yes

Yes

  • in AS, slave

No

No

Digital inputs

Number of digital inputs

24

24

  • of which inputs usable for technological functions

16

16

integrated channels (DI)

24

24

Input characteristic curve in accordance with IEC 61131, type 1

Yes

Yes

horizontal installation

  • up to 40 C, max.

24

24

  • up to 60 C, max.

12

12; up to 70 C

vertical installation

  • up to 40 C, max.

12

12

Input voltage

  • Rated value (DC)

24V

24V

  • for signal "0"

-3 to +5V

-3 to +5V

  • for signal "1"

+15 to +30V

+15 to +30V

Input current

  • for signal "1", typ.

8mA

8mA

Input delay (for rated value of input voltage)

for standard inputs

  • parameterizable

Yes; 0.1 / 0.3 / 3 / 15 ms (You can reconfigure the input delay of the standard inputs during program runtime. Please note that under certain circumstances your newly set filter time may not be effective until the next filter cycle.)

Yes; 0.1 / 0.3 / 3 / 15 ms (You can reconfigure the input delay of the standard inputs during program runtime. Please note that under certain circumstances your newly set filter time may not be effective until the next filter cycle.)

  • Rated value

3ms

3ms

for counter/technological functions

  • at "0" to "1", max.

8s; Minimum pulse width/minimum pause between pulses at maximum counting frequency

8s; Minimum pulse width/minimum pause between pulses at maximum counting frequency

Cable length

  • shielded, max.

1000m; 50 m for technological functions

1000m; 50 m for technological functions

  • unshielded, max.

600m; For technological functions: No

600m; For technological functions: No

for technological functions

  • shielded, max.

50m; at maximum count frequency

50m; at maximum count frequency

  • unshielded, max.

not allowed

not allowed

Digital outputs

Number of digital outputs

16

16

  • of which high-speed outputs

4; Notice: You cannot connect the fast outputs of your CPU in parallel

4; Notice: You cannot connect the fast outputs of your CPU in parallel

integrated channels (DO)

16

16

Short-circuit protection

Yes; Clocked electronically

Yes; Clocked electronically

  • Response threshold, typ.

1A

1A

Limitation of inductive shutdown voltage to

L+ (-48 V)

L+ (-48 V)

Controlling a digital input

Yes

Yes

Switching capacity of the outputs

  • on lamp load, max.

5W

5W

Load resistance range

  • lower limit

48Ω

48Ω

  • upper limit

4kΩ

4kΩ

Output voltage

  • for signal "1", min.

L+ (-0.8 V)

L+ (-0.8 V)

Output current

  • for signal "1" rated value

500mA

500mA

  • for signal "1" permissible range, min.

5mA

5mA

  • for signal "1" permissible range, max.

0.6A

0.6A

  • for signal "1" minimum load current

5mA

5mA

  • for signal "0" residual current, max.

0.5mA

0.5mA

Parallel switching of two outputs

  • for uprating

No

No

  • for redundant control of a load

Yes

Yes

Switching frequency

  • with resistive load, max.

100Hz

100Hz

  • with inductive load, max.

0.5Hz

0.5Hz

  • on lamp load, max.

100Hz

100Hz

  • of the pulse outputs, with resistive load, max.

2.5kHz

2.5kHz

horizontal installation

  • up to 40 C, max.

3A

3A

  • up to 60 C, max.

2A

2A; 1.5 A @ > 60 C

vertical installation

  • up to 40 C, max.

2A

2A

Cable length

  • shielded, max.

1000m

1000m

  • unshielded, max.

600m

600m

Analog inputs

Number of analog inputs

5

5

  • For voltage/current measurement

4

4

  • For resistance/resistance thermometer measurement

1

1

integrated channels (AI)

5; 4 x current/voltage, 1 x resistance

5; 4 x current/voltage, 1 x resistance

permissible input voltage for current input (destruction limit), max.

5V; Permanent

5V; Permanent

permissible input voltage for voltage input (destruction limit), max.

30V; Permanent

30V; Permanent

permissible input current for voltage input (destruction limit), max.

0.5mA; Permanent

0.5mA; Permanent

permissible input current for current input (destruction limit), max.

50mA; Permanent

50mA; Permanent

No-load voltage, typ.

3.3V

3.3V

Constant measurement current for resistance-type transmitter, typ.

1.25mA

1.25mA

Technical unit for temperature measurement adjustable

Yes; Degrees Celsius / degrees Fahrenheit / Kelvin

Yes; Degrees Celsius / degrees Fahrenheit / Kelvin

Input ranges

  • Voltage

Yes; 10 V / 100 kΩ; 0 V to 10 V / 100 kΩ

Yes; 10 V / 100 kΩ; 0 V to 10 V / 100 kΩ

  • Current

Yes; 20 mA / 100 Ω; 0 mA to 20 mA / 100 Ω; 4 mA to 20 mA / 100 Ω

Yes; 20 mA / 100 Ω; 0 mA to 20 mA / 100 Ω; 4 mA to 20 mA / 100 Ω

  • Resistance thermometer

Yes; Pt 100 / 10 MΩ

Yes; Pt 100 / 10 MΩ

  • Resistance

Yes; 0 Ω to 600 Ω / 10 MΩ

Yes; 0 Ω to 600 Ω / 10 MΩ

Input ranges (rated values), voltages

  • 0 to +10 V

Yes

Yes

  • Input resistance (0 to 10 V)

100kΩ

100kΩ

Input ranges (rated values), currents

  • 0 to 20 mA

Yes

Yes

  • Input resistance (0 to 20 mA)

100Ω

100Ω

  • -20 mA to +20 mA

Yes

Yes

  • Input resistance (-20 mA to +20 mA)

100Ω

100Ω

  • 4 mA to 20 mA

Yes

Yes

  • Input resistance (4 mA to 20 mA)

100Ω

100Ω

Input ranges (rated values), resistance thermometer

  • Pt 100

Yes

Yes

  • Input resistance (Pt 100)

10MΩ

10MΩ

Input ranges (rated values), resistors

  • 0 to 600 ohms

Yes

Yes

  • Input resistance (0 to 600 ohms)

10MΩ

10MΩ

Thermocouple (TC)

Temperature compensation

  • parameterizable

No

No

Characteristic linearization

  • parameterizable

Yes; by software

Yes; by software

  • for resistance thermometer

Pt 100

Pt 100

Cable length

  • shielded, max.

100m

100m

Analog outputs

Number of analog outputs

2

2

integrated channels (AO)

2

2

Voltage output, short-circuit protection

Yes

Yes

Voltage output, short-circuit current, max.

55mA

55mA

Current output, no-load voltage, max.

14V

14V

Output ranges, voltage

  • 0 to 10 V

Yes

Yes

  • -10 V to +10 V

Yes

Yes

Output ranges, current

  • 0 to 20 mA

Yes

Yes

  • -20 mA to +20 mA

Yes

Yes

  • 4 mA to 20 mA

Yes

Yes

Connection of actuators

  • for voltage output two-wire connection

Yes; Without compensation of the line resistances

Yes; Without compensation of the line resistances

  • for voltage output four-wire connection

No

No

  • for current output two-wire connection

Yes

Yes

Load impedance (in rated range of output)

  • with voltage outputs, min.

1kΩ

1kΩ

  • with voltage outputs, capacitive load, max.

0.1F

0.1F

  • with current outputs, max.

300Ω

300Ω

  • with current outputs, inductive load, max.

0.1mH

0.1mH

Destruction limits against externally applied voltages and currents

  • Voltages at the outputs towards MANA

16V; Permanent

16V; Permanent

  • Current, max.

50mA; Permanent

50mA; Permanent

Cable length

  • shielded, max.

200m

200m

Analog value generation for the inputs

Measurement principle

Actual value encryption (successive approximation)

Actual value encryption (successive approximation)

Integration and conversion time/resolution per channel

  • Resolution with overrange (bit including sign), max.

12bit

12bit

  • Integration time, parameterizable

Yes; 16.6 / 20 ms

Yes; 16.6 / 20 ms

  • Interference voltage suppression for interference frequency f1 in Hz

50 / 60 Hz

50 / 60 Hz

  • permissible input frequency, max.

400Hz

400Hz

  • Time constant of the input filter

0.38ms

0.38ms

  • Basic execution time of the module (all channels released)

1ms

1ms

Analog value generation for the outputs

Integration and conversion time/resolution per channel

  • Resolution with overrange (bit including sign), max.

12bit

12bit

  • Conversion time (per channel)

1ms

1ms

Settling time

  • for resistive load

0.6ms

0.6ms

  • for capacitive load

1ms

1ms

  • for inductive load

0.5ms

0.5ms

Encoder

Connection of signal encoders

  • for voltage measurement

Yes

Yes

  • for current measurement as 2-wire transducer

Yes; with external supply

Yes; with external supply

  • for current measurement as 4-wire transducer

Yes

Yes

  • for resistance measurement with two-wire connection

Yes; Without compensation of the line resistances

Yes; Without compensation of the line resistances

  • for resistance measurement with three-wire connection

No

No

  • for resistance measurement with four-wire connection

No

No

Connectable encoders

  • 2-wire sensor

Yes

Yes

  • permissible quiescent current (2-wire sensor), max.

1.5mA

1.5mA

Errors/accuracies

Temperature error (relative to input range), (+/-)

0.006%/K

0.006%/K

Crosstalk between the inputs, min.

60dB

60dB

Repeat accuracy in steady state at 25 C (relative to input range), (+/-)

0.06%

0.06%

Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-)

0.1%

0.1%

Linearity error (relative to output range), (+/-)

0.15%

0.15%

Temperature error (relative to output range), (+/-)

0.01%/K

0.01%/K

Crosstalk between the outputs, min.

60dB

60dB

Repeat accuracy in steady state at 25 C (relative to output range), (+/-)

0.06%

0.06%

Operational error limit in overall temperature range

  • Voltage, relative to input range, (+/-)

1%

1%

  • Current, relative to input range, (+/-)

1%

1%

  • Resistance, relative to input range, (+/-)

1%

1%

  • Voltage, relative to output range, (+/-)

1%

1%

  • Current, relative to output range, (+/-)

1%

1%

Basic error limit (operational limit at 25 C)

  • Voltage, relative to input range, (+/-)

0.8%; Linearity error 0.06 %

0.8%; Linearity error 0.06 %

  • Current, relative to input range, (+/-)

0.8%; Linearity error 0.06 %

0.8%; Linearity error 0.06 %

  • Resistance, relative to input range, (+/-)

0.8%; Linearity error 0.2 %

0.8%; Linearity error 0.2 %

  • Resistance thermometer, relative to input range, (+/-)

0.8%

0.8%

  • Voltage, relative to output range, (+/-)

0.8%

0.8%

  • Current, relative to output range, (+/-)

0.8%

0.8%

Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency

  • Series mode interference (peak value of interference < rated value of input range), min.

30dB

30dB

  • Common mode interference, min.

40dB

40dB

Interfaces

Number of industrial Ethernet interfaces

0

0

Number of PROFINET interfaces

0

0

Number of RS 485 interfaces

2; MPI and PROFIBUS DP

2; MPI and PROFIBUS DP

Number of RS 422 interfaces

0

0

1. Interface

Interface type

Integrated RS 485 interface

Integrated RS 485 interface

Physics

RS 485

RS 485

Isolated

No

No

Power supply to interface (15 to 30 V DC), max.

200mA

200mA

Functionality

  • MPI

Yes

Yes

  • PROFIBUS DP master

No

No

  • PROFIBUS DP slave

No

No

  • Point-to-point connection

No

No

MPI

  • Transmission rate, max.

187.5kbit/s

187.5kbit/s

Services

  • PG/OP communication

Yes

Yes

  • Routing

Yes

Yes

  • Global data communication

Yes

Yes

  • S7 basic communication

Yes

Yes

  • S7 communication

Yes; Only server, configured on one side

Yes; Only server, configured on one side

  • S7 communication, as client

No; but via CP and loadable FB

No; but via CP and loadable FB

  • S7 communication, as server

Yes

Yes

2. Interface

Interface type

Integrated RS 485 interface

Integrated RS 485 interface

Physics

RS 485

RS 485

Isolated

Yes

Yes

Power supply to interface (15 to 30 V DC), max.

200mA

200mA

Functionality

  • MPI

No

No

  • PROFINET IO Controller

No

No

  • PROFINET IO Device

No

No

  • PROFINET CBA

No

No

  • PROFIBUS DP master

Yes

Yes

  • PROFIBUS DP slave

Yes

Yes

  • Point-to-point connection

No

No

DP master

  • Transmission rate, max.

12Mbit/s

12Mbit/s

  • Number of DP slaves, max.

124

124

Services

  • PG/OP communication

Yes

Yes

  • Routing

Yes

Yes

  • Global data communication

No

No

  • S7 basic communication

Yes; I blocks only

Yes; I blocks only

  • S7 communication

Yes; Only server, configured on one side

Yes; Only server, configured on one side

  • S7 communication, as client

No

No

  • S7 communication, as server

Yes

Yes

  • Equidistance

Yes

Yes

  • Isochronous mode

No

No

  • SYNC/FREEZE

Yes

Yes

  • Activation/deactivation of DP slaves

Yes

Yes

  • Number of DP slaves that can be simultaneously activated/deactivated, max.

8

8

  • Direct data exchange (slave-to-slave communication)

Yes; As subscriber

Yes; As subscriber

  • DPV1

Yes

Yes

Address area

  • Inputs, max.

2kbyte

2kbyte

  • Outputs, max.

2kbyte

2kbyte

User data per DP slave

  • Inputs, max.

244byte

244byte

  • Outputs, max.

244byte

244byte

DP slave

  • GSD file

The latest GSD file is available on the Internet (http://www.siemens.com/profibus-gsd)

The latest GSD file is available on the Internet (http://www.siemens.com/profibus-gsd)

  • Transmission rate, max.

12Mbit/s

12Mbit/s

  • automatic baud rate search

Yes; only with passive interface

Yes; only with passive interface

  • Address area, max.

32

32

  • User data per address area, max.

32byte

32byte

Services

  • PG/OP communication

Yes

Yes

  • Routing

Yes; Only with active interface

Yes; Only with active interface

  • Global data communication

No

No

  • S7 basic communication

No

No

  • S7 communication

Yes; Only server, configured on one side

Yes; Only server, configured on one side

  • S7 communication, as client

No

No

  • S7 communication, as server

Yes

Yes

  • Direct data exchange (slave-to-slave communication)

Yes

Yes

  • DPV1

No

No

Transfer memory

  • Inputs

244byte

244byte

  • Outputs

244byte

244byte

Communication functions

PG/OP communication

Yes

Yes

Data record routing

Yes

Yes

Global data communication

  • supported

Yes

Yes

  • Number of GD loops, max.

8

8

  • Number of GD packets, max.

8

8

  • Number of GD packets, transmitter, max.

8

8

  • Number of GD packets, receiver, max.

8

8

  • Size of GD packets, max.

22byte

22byte

  • Size of GD packet (of which consistent), max.

22byte

22byte

S7 basic communication

  • supported

Yes

Yes

  • User data per job, max.

76byte

76byte

  • User data per job (of which consistent), max.

76byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server)

76byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server)

S7 communication

  • supported

Yes

Yes

  • as server

Yes

Yes

  • as client

Yes; Via CP and loadable FB

Yes; Via CP and loadable FB

  • User data per job, max.

180kbyte; With PUT/GET

180kbyte; With PUT/GET

  • User data per job (of which consistent), max.

240byte; as server

240byte; as server

S5 compatible communication

  • supported

Yes; via CP and loadable FC

Yes; via CP and loadable FC

Number of connections

  • overall

12

12

  • usable for PG communication

11

11

  • reserved for PG communication

1

1

  • adjustable for PG communication, min.

1

1

  • adjustable for PG communication, max.

11

11

  • usable for OP communication

11

11

  • reserved for OP communication

1

1

  • adjustable for OP communication, min.

1

1

  • adjustable for OP communication, max.

11

11

  • usable for S7 basic communication

8

8

  • reserved for S7 basic communication

0

0

  • adjustable for S7 basic communication, min.

0

0

  • adjustable for S7 basic communication, max.

8

8

  • usable for routing

4; max.

4; max.

S7 message functions

Number of login stations for message functions, max.

12; Depending on the configured connections for PG/OP and S7 basic communication

12; Depending on the configured connections for PG/OP and S7 basic communication

Process diagnostic messages

Yes

Yes

simultaneously active Alarm-S blocks, max.

300

300

Test commissioning functions

Status block

Yes; Up to 2 simultaneously

Yes; Up to 2 simultaneously

Single step

Yes

Yes

Number of breakpoints

4

4

Status/control

  • Status/control variable

Yes

Yes

  • Variables

Inputs, outputs, memory bits, DB, times, counters

Inputs, outputs, memory bits, DB, times, counters

  • Number of variables, max.

30

30

  • of which status variables, max.

30

30

  • of which control variables, max.

14

14

Forcing

  • Forcing

Yes

Yes

  • Forcing, variables

Inputs, outputs

Inputs, outputs

  • Number of variables, max.

10

10

Diagnostic buffer

  • present

Yes

Yes

  • Number of entries, max.

500

500

  • adjustable

No

No

  • of which powerfail-proof

100; Only the last 100 entries are retained

100; Only the last 100 entries are retained

  • Number of entries readable in RUN, max.

499

499

  • can be set

Yes; From 10 to 499

Yes; From 10 to 499

  • preset

10

10

Service data

  • can be read out

Yes

Yes

Interrupts/diagnostics/status information

Diagnostics indication LED

  • Status indicator digital input (green)

Yes

Yes

  • Status indicator digital output (green)

Yes

Yes

Integrated Functions

Number of counters

4; See "Technological Functions" manual

4; See "Technological Functions" manual

Counting frequency (counter) max.

60kHz

60kHz

Frequency measurement

Yes

Yes

Number of frequency meters

4; up to 60 kHz (see "Technological Functions" manual)

4; up to 60 kHz (see "Technological Functions" manual)

controlled positioning

Yes

Yes

integrated function blocks (closed-loop control)

Yes; PID controller (see "Technological Functions" manual)

Yes; PID controller (see "Technological Functions" manual)

PID controller

Yes

Yes

Number of pulse outputs

4; Pulse width modulation up to 2.5 kHz (see "Technological Functions" Manual)

4; Pulse width modulation up to 2.5 kHz (see "Technological Functions" Manual)

Limit frequency (pulse)

2.5kHz

2.5kHz

Potential separation

Potential separation digital inputs

  • Potential separation digital inputs

Yes

Yes

  • between the channels

No

No

  • between the channels and backplane bus

Yes

Yes

Potential separation digital outputs

  • Potential separation digital outputs

Yes

Yes

  • between the channels

Yes

Yes

  • between the channels, in groups of

8

8

  • between the channels and backplane bus

Yes

Yes

Potential separation analog inputs

  • Potential separation analog inputs

Yes; common for analog I/O

Yes; common for analog I/O

  • between the channels

No

No

  • between the channels and backplane bus

Yes

Yes

Potential separation analog outputs

  • Potential separation analog outputs

Yes; common for analog I/O

Yes; common for analog I/O

  • between the channels

No

No

  • between the channels and backplane bus

Yes

Yes

Permissible potential difference

between different circuits

75 V DC/60 V AC

75 V DC/60 V AC

Between the inputs and MANA (UCM)

8 V DC

8 V DC

between MANA and M internally (UISO)

75 V DC/60 V AC

75 V DC/60 V AC

Isolation

Isolation tested with

500V AC for 1 minute

600 V DC

Standards, approvals, certificates

CE mark

Yes

Yes

UL approval

Yes

Yes

FM approval

No

No

RCM (formerly C-TICK)

Yes

Yes

KC approval

Yes

Yes

EAC (formerly Gost-R)

Yes

Yes

Railway application

  • EN 50155

Yes; Sections 4, 5 and 12; no further agreements apply; T1, Category 1, Class A/B

Use in hazardous areas

  • ATEX

No

Yes

Ambient conditions

Ambient temperature during operation

  • min.

-25C; = Tmin

-25C; = Tmin

  • max.

60C; = Tmax; the rated temperature range of -25 ... +55 C (T1) applies for the use on railway vehicles according to EN50155

70C; = Tmax; 60 C @ UL/cUL, ATEX and FM use

Ambient temperature during storage/transportation

  • min.

-40C

-40C

  • max.

70C

70C

Altitude during operation relating to sea level

  • Ambient air temperature-barometric pressure-altitude

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Relative humidity

  • With condensation, tested in accordance with IEC 60068-2-38, max.

100%; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation

100%; RH incl. condensation/frost (no commissioning under condensation conditions)

Resistance

Use in stationary industrial systems

  • to biologically active substances according to EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation in corrosive atmospheres!

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

  • to chemically active substances according to EN 60721-3-3

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

  • to mechanically active substances according to EN 60721-3-3

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Configuration

Configuration software

  • STEP 7

Yes; STEP 7 V5.5 + SP1 or higher or STEP 7 V5.3 + SP2 or higher with HSP 203

Yes; STEP 7 V5.5 + SP1 or higher or STEP 7 V5.3 + SP2 or higher with HSP 203

  • STEP 7 Lite

No

No

Programming

  • Command set

see instruction list

see instruction list

  • Nesting levels

8

8

  • System functions (SFC)

see instruction list

see instruction list

  • System function blocks (SFB)

see instruction list

see instruction list

Programming language

  • LAD

Yes

Yes

  • FBD

Yes

Yes

  • STL

Yes

Yes

  • SCL

Yes

Yes

  • CFC

Yes

Yes

  • GRAPH

Yes

Yes

  • HiGraph

Yes

Yes

Know-how protection

  • User program protection/password protection

Yes

Yes

  • Block encryption

Yes; With S7 block Privacy

Yes; With S7 block Privacy

Dimensions

Width

120mm

120mm

Height

125mm

125mm

Depth

130mm

130mm

Weights

Weight, approx.

680g

680g


















skener.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
DENDOR

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS -

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK -

  © " " 2007-2022
  (4872) 700-366  skenergo@mail.ru
.