Siemens
01 2018
(4872) 700-366
skenergo@mail.ru

Article number

6AG1052-1CC01-7BA8

6AG1052-1MD00-7BA8

6AG1052-1HB00-7BA8

6AG1052-1FB00-7BA8

SIPLUS LOGO! 24CE

SIPLUS LOGO! 12/24RCE

SIPLUS LOGO! 24RCE

SIPLUS LOGO! 230RCE

Display

with display

Yes; The legibility and response time of the display may be reduced or lengthened at temperatures outside 0 ... +55 C. These effects are self-reversing on return to the normal temperature range of 0 ... +55 C.

Yes; The legibility and response time of the display may be reduced or lengthened at temperatures outside 0 ... +55 C. These effects are self-reversing on return to the normal temperature range of 0 ... +55 C.

Yes; The legibility and response time of the display may be reduced or lengthened at temperatures outside 0 ... +55 C. These effects are self-reversing on return to the normal temperature range of 0 ... +55 C.

Yes; The legibility and response time of the display may be reduced or lengthened at temperatures outside 0 ... +55 C. These effects are self-reversing on return to the normal temperature range of 0 ... +55 C.

Installation type/mounting

Mounting

on 35 mm DIN rail, 4 spacing units wide

on 35 mm DIN rail, 4 spacing units wide

on 35 mm DIN rail, 4 spacing units wide

on 35 mm DIN rail, 4 spacing units wide

Supply voltage

Rated value (DC)

  • 12 V DC

Yes

  • 24 V DC

Yes

Yes

Yes

  • 115 V DC

Yes

  • 230 V DC

Yes

permissible range, lower limit (DC)

20.4V

10.8V

20.4V

100V

permissible range, upper limit (DC)

28.8V

28.8V

28.8V

253V

Rated value (AC)

  • 24 V AC

Yes

  • 115 V AC

Yes

  • 230 V AC

Yes

Line frequency

  • permissible range, lower limit

47Hz

47Hz

  • permissible range, upper limit

63Hz

63Hz

Time of day

Time switching clocks

  • Number

190

190

190

190

  • Power reserve

480h

480h

480h

480h

Digital inputs

Number of digital inputs

8; Of which 4 can be used in analog mode (0 to 10 V)

8; Of which 4 can be used in analog mode (0 to 10 V)

8

8

Digital outputs

Number of digital outputs

4; Transistor

4; Relays

4; Relays

4; Relays

Short-circuit protection

Yes; electrical (1 A)

No; external fusing necessary

No; external fusing necessary

No; external fusing necessary

Output current

  • for signal "1" permissible range for 0 to 55 C, max.

0.3A

10A

Relay outputs

Switching capacity of contacts

  • with inductive load, max.

3A

3A

3A

  • with resistive load, max.

10A

10A

10A

EMC

Emission of radio interference acc. to EN 55 011

  • Limit class B, for use in residential areas

Yes; Radio interference suppression according to EN55011, Limit Value Class B

Yes

Yes

Yes

Degree and class of protection

Degree of protection acc. to EN 60529

  • IP20

Yes

Yes

Yes

Yes

Standards, approvals, certificates

CE mark

Yes

Yes

Yes

Yes

developed in accordance with IEC 61131

Yes

Yes

Yes

Yes

according to VDE 0631

Yes

Yes

Yes

Yes

Ambient conditions

Ambient temperature during operation

  • min.

-20C; = Tmin; Startup @ -20 C

-20C; = Tmin; Startup @ -20 C

-20C; = Tmin; Startup @ -20 C

-20C; = Tmin; Startup @ -20 C

  • max.

60C; Tmax; Tmax > +55 C max. load 0.2 A per output

60C; Tmax; Tmax > +55 C max. load 1 A per relay or max. load 3 A per relay and half the number of DIs (no adjacent points)

60C; Tmax; Tmax > +55 C max. load 1 A per relay or max. load 3 A per relay and half the number of DIs (no adjacent points)

60C; Tmax; Tmax > +55 C max. load 1 A per relay

  • At cold restart, min.

0C

0C

0C

0C

Ambient temperature during storage/transportation

  • min.

-40C

-40C

-40C

-40C

  • max.

70C

70C

70C

70C

Altitude during operation relating to sea level

  • Ambient air temperature-barometric pressure-altitude

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... Tmax -5K) at 795 hPa ... 701 hPa (+2 000 m ... +3 000 m)

Relative humidity

  • With condensation, tested in accordance with IEC 60068-2-38, max.

100%; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation

100%; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation

100%; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation

100%; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation

Use in stationary industrial systems

  • to biologically active substances according to EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

  • to chemically active substances according to EN 60721-3-3

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

  • to mechanically active substances according to EN 60721-3-3

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Dimensions

Width

71.5mm

71.5mm

71.5mm

71.5mm

Height

90mm

90mm

90mm

90mm

Depth

60mm

60mm

60mm

60mm


Article number

6AG1052-1MD00-2BA7

6AG1052-1FB00-2BA7

SIPLUS LOGO!12/24RCE

SIPLUS LOGO! 230RCE

Display

with display

Yes

Yes

Installation type/mounting

Mounting

on 35mm DIN rail, 6 spacing units wide

on 35mm DIN rail, 6 spacing units wide

Supply voltage

Rated value (DC)

  • 12 V DC

Yes

  • 24 V DC

Yes

  • 115 V DC

Yes

  • 230 V DC

Yes

permissible range, lower limit (DC)

10.8V

100V

permissible range, upper limit (DC)

28.8V

253V

Rated value (AC)

  • 115 V AC

Yes

  • 230 V AC

Yes

Time of day

Time switching clocks

  • Number

333

333

  • Power reserve

480h

480h

Digital inputs

Number of digital inputs

8; of which 4 can be used in analog mode (0 to 10 V); max. load 9 A per relay @ all DI @ +55 C to +60 C; max. load 1 A per relay @ all DI @ > +60 C; max. load 3 A per relay @ half the number of DI @ > +60 C

8; half the number of DI @ max. load 1A per relay @ > +60 C

Digital outputs

Number of digital outputs

4; Relays

4; Relays

Short-circuit protection

No; external fusing necessary

No; external fusing necessary

Relay outputs

Switching capacity of contacts

  • with inductive load, max.

3A

3A

  • with resistive load, max.

10A; max. last 9 A per relay @ all DI @ +55 C to +60 C; max. load 1 A per relay @ all DI @ > +60 C; max. load 3 A per relay @ half the number of DI @ > +60 C

10A; max. load 1A per relay @ half the number of DI @ > +60 C

EMC

Emission of radio interference acc. to EN 55 011

  • Limit class B, for use in residential areas

Yes; Radio interference suppression according to EN55011, Limit Value Class B

Yes; Radio interference suppression according to EN55011, Limit Value Class B

Degree and class of protection

Degree of protection acc. to EN 60529

  • IP20

Yes

Yes

Standards, approvals, certificates

CSA approval

Yes

UL approval

Yes

Yes

FM approval

Yes

developed in accordance with IEC 61131

Yes

Yes

according to VDE 0631

Yes

Yes

Marine approval

Yes

Ambient conditions

Ambient temperature during operation

  • min.

-25C; = Tmin

-25C; = Tmin

  • max.

70C; = Tmax

70C; = Tmax

Altitude during operation relating to sea level

  • Ambient air temperature-barometric pressure-altitude

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)

Relative humidity

  • With condensation, tested in accordance with IEC 60068-2-38, max.

100%; RH incl. condensation/frost permitted (no commissioning in bedewed state)

100%; RH incl. condensation/frost permitted (no commissioning in bedewed state)

Use in stationary industrial systems

  • to biologically active substances according to EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

  • to chemically active substances according to EN 60721-3-3

Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

  • to mechanically active substances according to EN 60721-3-3

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Dimensions

Width

107mm

107mm

Height

90mm

90mm

Depth

55mm

55mm


Article number

6AG1052-1CC01-2BA6

6AG1052-1MD00-2BA6

6AG1052-1HB00-2BA6

6AG1052-1FB00-2BA6

SIPLUS LOGO! 24C

SIPLUS LOGO! 12/24RC

SIPLUS LOGO! 24RC

SIPLUS LOGO! 230RC

Display

with display

Yes; The display is bright at temperatures below 0 C and dark at temperatures over +55 C. This procedure is self-reversing on returning to the standard temperature range (0 C to +55 C).

Yes; The display is bright at temperatures below 0 C and dark at temperatures over +55 C. This procedure is self-reversing on returning to the standard temperature range (0 C to +55 C).

Yes; The display is bright at temperatures below 0 C and dark at temperatures over +55 C. This procedure is self-reversing on returning to the standard temperature range (0 C to +55 C).

Yes; The display is bright at temperatures below 0 C and dark at temperatures over +55 C. This procedure is self-reversing on returning to the standard temperature range (0 C to +55 C).

Installation type/mounting

Mounting

on 35 mm DIN rail, 4 spacing units wide

on 35 mm DIN rail, 4 spacing units wide

on 35 mm DIN rail, 4 spacing units wide

on 35 mm DIN rail, 4 spacing units wide

Supply voltage

Rated value (DC)

  • 12 V DC

Yes

  • 24 V DC

Yes

Yes

Yes

  • 115 V DC

Yes

  • 230 V DC

Yes

permissible range, lower limit (DC)

20.4V; 22 V @ >55 C

10.8V; 11 V @ >55 C

20.4V; 22 V @ >55 C

100V

permissible range, upper limit (DC)

28.8V; 27.5 V @ >55 C

28.8V; 27.5 V @ >55 C

28.8V; 27.5 V @ >55 C

253V

Rated value (AC)

  • 24 V AC

Yes

  • 115 V AC

Yes

  • 230 V AC

Yes

Time of day

Time switching clocks

  • Number

190

8

  • Power reserve

80h

80h

80h

80h

Digital inputs

Number of digital inputs

8; Of which 4 can be used in analog mode (0 to 10 V)

8; Of which 4 can be used in analog mode (0 to 10 V)

8

8

Digital outputs

Number of digital outputs

4; Transistor

4; Relays

4; Relays

4; Relays

Short-circuit protection

Yes; electrical (1 A)

No; external fusing necessary

No; external fusing necessary

No; external fusing necessary

Output current

  • for signal "1" permissible range for 0 to 55 C, max.

0.3A; 0.2 A @ > 55 C; 0.3 A @ > 55 C & < 15 s

Relay outputs

Switching capacity of contacts

  • with inductive load, max.

3A; 1 A per relay @ > 55 C; 3 A per relay @ > 55 C & < 15 s

3A; 1 A per relay @ > 55 C; 3 A per relay @ > 55 C & < 15 s

3A; 1 A per relay @ > 55 C; 3 A per relay @ > 55 C & < 15 s

  • with resistive load, max.

10A; 3 A per relay @ > 55 C; 10 A per relay @ > 55 C & < 15 s

10A; 3 A per relay @ > 55 C; 10 A per relay @ > 55 C & < 15 s

10A; 3 A per relay @ > 55 C; 10 A per relay @ > 55 C & < 15 s

EMC

Emission of radio interference acc. to EN 55 011

  • Limit class B, for use in residential areas

Yes; Radio interference suppression according to EN55011, Limit Value Class B

Yes

Yes

Yes

Degree and class of protection

Degree of protection acc. to EN 60529

  • IP20

Yes

Yes

Yes

Yes

Standards, approvals, certificates

CSA approval

No

No

No

No

UL approval

Yes; File: E120869 // Tmax = 55 C

Yes; File: E120869 // Tmax = 55 C

Yes; File: E120869 // Tmax = 55 C

Yes; File: E120869 // Tmax = 55 C

FM approval

No

No

No

No

developed in accordance with IEC 61131

Yes

Yes

Yes

Yes

according to VDE 0631

Yes

Yes

Yes

Yes

Marine approval

No

No

No

No

Ambient conditions

Ambient temperature during operation

  • min.

-25C; = Tmin

-25C; = Tmin

-25C; = Tmin

-25C; = Tmin

  • max.

70C; = Tmax; 55 C @ UL/cUL use

70C; = Tmax; 55 C @ UL/cUL use

70C; = Tmax; 55 C @ UL/cUL use

70C; = Tmax; 55 C @ UL/cUL use

Altitude during operation relating to sea level

  • Ambient air temperature-barometric pressure-altitude

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)

Relative humidity

  • With condensation, tested in accordance with IEC 60068-2-38, max.

100%; RH incl. condensation/frost permitted (no commissioning in bedewed state)

100%; RH incl. condensation/frost permitted (no commissioning in bedewed state)

100%; RH incl. condensation/frost permitted (no commissioning in bedewed state)

100%; RH incl. condensation/frost permitted (no commissioning in bedewed state)

Use in stationary industrial systems

  • to biologically active substances according to EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

  • to chemically active substances according to EN 60721-3-3

Yes; Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation!

  • to mechanically active substances according to EN 60721-3-3

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Dimensions

Width

72mm

72mm

72mm

72mm

Height

90mm

90mm

90mm

90mm

Depth

55mm

55mm

55mm

55mm