Article number

6AG1315-2EH14-2AY0

6AG1315-2EH14-7AB0

SIPLUS S7-300 CPU315-2PN/DP EN50155

SIPLUS S7-300 CPU315-2PN/DP

General information

HW functional status

01

01

Firmware version

V3.2

V3.2

Engineering with

  • Programming package

STEP 7 V5.5 or higher

STEP 7 V5.5 or higher

Supply voltage

Rated value (DC)

  • 24 V DC

Yes; A power supply according to EN 50155 shall be used

Yes

permissible range, lower limit (DC)

20.4V

20.4V

permissible range, upper limit (DC)

28.8V

28.8V

external protection for power supply lines (recommendation)

2 A min.

2 A min.

Mains buffering

  • Mains/voltage failure stored energy time

5ms

5ms

  • Repeat rate, min.

1s

1s

Input current

Current consumption (rated value)

750mA

750mA

Current consumption (in no-load operation), typ.

150mA

150mA

Inrush current, typ.

4A

4A

It

1As

1As

Power loss

Power loss, typ.

4.65W

4.65W

Memory

Work memory

  • integrated

384kbyte

384kbyte

  • expandable

No

No

  • Size of retentive memory for retentive data blocks

128kbyte

128kbyte

Load memory

  • Plug-in (MMC)

Yes

Yes

  • Plug-in (MMC), max.

8Mbyte

8Mbyte

  • Data management on MMC (after last programming), min.

10y

10y

Backup

  • present

Yes; Guaranteed by MMC (maintenance-free)

Yes; Guaranteed by MMC (maintenance-free)

  • without battery

Yes; Program and data

Yes; Program and data

CPU processing times

for bit operations, typ.

0.05s

0.05s

for word operations, typ.

0.09s

0.09s

for fixed point arithmetic, typ.

0.12s

0.12s

for floating point arithmetic, typ.

0.45s

0.45s

CPU-blocks

Number of blocks (total)

1024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used.

1024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used.

DB

  • Number, max.

1024; Number range: 1 to 16000

1024; Number range: 1 to 16000

  • Size, max.

64kbyte

64kbyte

FB

  • Number, max.

1024; Number range: 0 to 7999

1024; Number range: 0 to 7999

  • Size, max.

64kbyte

64kbyte

FC

  • Number, max.

1024; Number range: 0 to 7999

1024; Number range: 0 to 7999

  • Size, max.

64kbyte

64kbyte

OB

  • Size, max.

64kbyte

64kbyte

  • Number of free cycle OBs

1; OB 1

1; OB 1

  • Number of time alarm OBs

1; OB 10

1; OB 10

  • Number of delay alarm OBs

2; OB 20, 21

2; OB 20, 21

  • Number of cyclic interrupt OBs

4; OB 32, 33, 34, 35

4; OB 32, 33, 34, 35

  • Number of process alarm OBs

1; OB 40

1; OB 40

  • Number of DPV1 alarm OBs

3; OB 55, 56, 57

3; OB 55, 56, 57

  • Number of isochronous mode OBs

1; OB 61

1; OB 61

  • Number of startup OBs

1; OB 100

1; OB 100

  • Number of asynchronous error OBs

6; OB 80, 82, 83, 85, 86, 87 (OB83 only for PROFINET IO)

6; OB 80, 82, 83, 85, 86, 87 (OB83 only for PROFINET IO)

  • Number of synchronous error OBs

2; OB 121, 122

2; OB 121, 122

Nesting depth

  • per priority class

16

16

  • additional within an error OB

4

4

Counters, timers and their retentivity

S7 counter

  • Number

256

256

Retentivity

  • adjustable

Yes

Yes

  • lower limit

0

0

  • upper limit

255

255

  • preset

Z 0 to Z 7

Z 0 to Z 7

Counting range

  • can be set

Yes

Yes

  • lower limit

0

0

  • upper limit

999

999

IEC counter

  • Number

Unlimited (limited only by RAM capacity)

Unlimited (limited only by RAM capacity)

S7 times

  • Number

256

256

Retentivity

  • adjustable

Yes

Yes

  • lower limit

0

0

  • upper limit

255

255

  • preset

No retentivity

No retentivity

Time range

  • lower limit

10ms

10ms

  • upper limit

9990s

9990s

IEC timer

  • present

Yes

Yes

  • Type

SFB

SFB

  • Number

Unlimited (limited only by RAM capacity)

Unlimited (limited only by RAM capacity)

Data areas and their retentivity

retentive data area in total

All, 128 KB max.

All, 128 KB max.

Flag

  • Number, max.

2048byte

2048byte

  • Retentivity available

Yes; MB 0 to MB 2047

Yes; MB 0 to MB 2047

  • Retentivity preset

MB 0 to MB 15

MB 0 to MB 15

  • Number of clock memories

8; 1 memory byte

8; 1 memory byte

Data blocks

  • Retentivity adjustable

Yes; via non-retain property on DB

Yes; via non-retain property on DB

  • Retentivity preset

Yes

Yes

Local data

  • per priority class, max.

32768byte; Max. 2048 bytes per block

32768byte; Max. 2048 bytes per block

Address area

I/O address area

  • Inputs

2048byte

2048byte

  • Outputs

2048byte

2048byte

of which distributed

  • Inputs

2048byte

2048byte

  • Outputs

2048byte

2048byte

Process image

  • Inputs

2048byte

2048byte

  • Outputs

2048byte

2048byte

  • Inputs, adjustable

2048byte

2048byte

  • Outputs, adjustable

2048byte

2048byte

  • Inputs, default

128byte

128byte

  • Outputs, default

128byte

128byte

Subprocess images

  • Number of subprocess images, max.

1; With PROFINET IO, the length of the user data is limited to 1600 bytes

1; With PROFINET IO, the length of the user data is limited to 1600 bytes

Digital channels

  • Inputs

16384

16384

  • of which central

1024

1024

  • Outputs

16384

16384

  • of which central

1024

1024

Analog channels

  • Inputs

1024

1024

  • of which central

256

256

  • Outputs

1024

1024

  • of which central

256

256

Hardware configuration

Number of expansion units, max.

3

3

Number of DP masters

  • integrated

1

1

  • via CP

4

4

Number of operable FMs and CPs (recommended)

  • FM

8

8

  • CP, PtP

8

8

  • CP, LAN

10

10

Rack

  • Racks, max.

4

4

  • Modules per rack, max.

8

8

Time of day

Clock

  • Hardware clock (real-time)

Yes

Yes

  • retentive and synchronizable

Yes

Yes

  • Backup time

6wk; At 40 C ambient temperature

6wk; At 40 C ambient temperature

  • Deviation per day, max.

10s; Typ.: 2 s

10s; Typ.: 2 s

  • Behavior of the clock following POWER-ON

Clock continues running after POWER OFF

Clock continues running after POWER OFF

  • Behavior of the clock following expiry of backup period

Clock continues to run with the time at which the power failure occurred

Clock continues to run with the time at which the power failure occurred

Operating hours counter

  • Number

1

1

  • Number/Number range

0

0

  • Range of values

0 to 2^31 hours (when using SFC 101)

0 to 2^31 hours (when using SFC 101)

  • Granularity

1 hour

1 hour

  • retentive

Yes; Must be restarted at each restart

Yes; Must be restarted at each restart

Clock synchronization

  • supported

Yes

Yes

  • to MPI, master

Yes

Yes

  • to MPI, slave

Yes

Yes

  • to DP, master

Yes; With DP slave only slave clock

Yes; With DP slave only slave clock

  • to DP, slave

Yes

Yes

  • in AS, master

Yes

Yes

  • in AS, slave

Yes

Yes

  • on Ethernet via NTP

Yes; As client

Yes; As client

Digital inputs

Number of digital inputs

0

0

Digital outputs

Number of digital outputs

0

0

Analog inputs

Number of analog inputs

0

0

Analog outputs

Number of analog outputs

0

0

Interfaces

Number of industrial Ethernet interfaces

1; 2 ports (switch) RJ45

1; 2 ports (switch) RJ45

Number of PROFINET interfaces

1; 2 ports (switch) RJ45

1; 2 ports (switch) RJ45

Number of RS 485 interfaces

1; Combined MPI / PROFIBUS DP

1; Combined MPI / PROFIBUS DP

Number of RS 422 interfaces

0

0

1. Interface

Interface type

Integrated RS 485 interface

Integrated RS 485 interface

Physics

RS 485

RS 485

Isolated

Yes

Yes

Power supply to interface (15 to 30 V DC), max.

200mA

200mA

Functionality

  • MPI

Yes

Yes

  • PROFIBUS DP master

Yes

Yes

  • PROFIBUS DP slave

Yes

Yes

  • Point-to-point connection

No

No

MPI

  • Transmission rate, max.

12Mbit/s

12Mbit/s

Services

  • PG/OP communication

Yes

Yes

  • Routing

Yes

Yes

  • Global data communication

Yes

Yes

  • S7 basic communication

Yes

Yes

  • S7 communication

Yes

Yes

  • S7 communication, as client

No; but via CP and loadable FB

No; but via CP and loadable FB

  • S7 communication, as server

Yes

Yes

DP master

  • Transmission rate, max.

12Mbit/s

12Mbit/s

  • Number of DP slaves, max.

124

124

Services

  • PG/OP communication

Yes

Yes

  • Routing

Yes

Yes

  • Global data communication

No

No

  • S7 basic communication

Yes; I blocks only

Yes; I blocks only

  • S7 communication

Yes

Yes

  • S7 communication, as client

No

No

  • S7 communication, as server

Yes

Yes

  • Equidistance

Yes

Yes

  • Isochronous mode

Yes; OB 61; isochronous mode can only be used alternatively on PROFIBUS DP or PROFINET IO

Yes; OB 61; isochronous mode can only be used alternatively on PROFIBUS DP or PROFINET IO

  • SYNC/FREEZE

Yes

Yes

  • Activation/deactivation of DP slaves

Yes

Yes

  • Number of DP slaves that can be simultaneously activated/deactivated, max.

8

8

  • Direct data exchange (slave-to-slave communication)

Yes; As subscriber

Yes; As subscriber

  • DPV1

Yes

Yes

Address area

  • Inputs, max.

2kbyte

2kbyte

  • Outputs, max.

2kbyte

2kbyte

User data per DP slave

  • Inputs, max.

244byte

244byte

  • Outputs, max.

244byte

244byte

DP slave

  • Transmission rate, max.

12Mbit/s

12Mbit/s

  • automatic baud rate search

Yes; only with passive interface

Yes; only with passive interface

  • Address area, max.

32

32

  • User data per address area, max.

32byte

32byte

Services

  • PG/OP communication

Yes

Yes

  • Routing

Yes; Only with active interface

Yes; Only with active interface

  • Global data communication

No

No

  • S7 basic communication

No

No

  • S7 communication

Yes

Yes

  • S7 communication, as client

No

No

  • S7 communication, as server

Yes; Connection configured on one side only

Yes; Connection configured on one side only

  • Direct data exchange (slave-to-slave communication)

Yes

Yes

  • DPV1

No

No

Transfer memory

  • Inputs

244byte

244byte

  • Outputs

244byte

244byte

2. Interface

Interface type

PROFINET

PROFINET

Physics

Ethernet RJ45

Ethernet RJ45

Isolated

Yes

Yes

automatic detection of transmission rate

Yes; 10/100 Mbit/s

Yes; 10/100 Mbit/s

Autonegotiation

Yes

Yes

Autocrossing

Yes

Yes

Change of IP address at runtime, supported

Yes

Yes

Interface types

  • Number of ports

2

2

  • integrated switch

Yes

Yes

Media redundancy

  • supported

Yes

Yes

  • Switchover time on line break, typ.

200ms; PROFINET MRP

200ms; PROFINET MRP

  • Number of stations in the ring, max.

50

50

Functionality

  • MPI

No

No

  • PROFINET IO Controller

Yes; Also simultaneously with IO-Device functionality

Yes; Also simultaneously with IO-Device functionality

  • PROFINET IO Device

Yes; Also simultaneously with IO Controller functionality

Yes; Also simultaneously with IO Controller functionality

  • PROFINET CBA

Yes

Yes

  • PROFIBUS DP master

No

No

  • PROFIBUS DP slave

No

No

  • Open IE communication

Yes; Via TCP/IP, ISO on TCP, and UDP

Yes; Via TCP/IP, ISO on TCP, and UDP

  • Web server

Yes

Yes

PROFINET IO Controller

  • Transmission rate, max.

100Mbit/s

100Mbit/s

Services

  • PG/OP communication

Yes

Yes

  • Routing

Yes

Yes

  • S7 communication

Yes; With loadable FBs, max. configurable connections: 14, max. number of instances: 32

Yes; With loadable FBs, max. configurable connections: 14, max. number of instances: 32

  • Isochronous mode

Yes; OB 61; isochronous mode can only be used alternatively on PROFIBUS DP or PROFINET IO

Yes; OB 61; isochronous mode can only be used alternatively on PROFIBUS DP or PROFINET IO

  • Open IE communication

Yes; Via TCP/IP, ISO on TCP, and UDP

Yes; Via TCP/IP, ISO on TCP, and UDP

  • IRT

Yes

Yes

  • Shared device

Yes

Yes

  • Prioritized startup

Yes

Yes

  • Number of IO devices with prioritized startup, max.

32

32

  • Number of connectable IO Devices, max.

128

128

  • Of which IO devices with IRT, max.

64

64

  • of which in line, max.

64

64

  • Number of IO Devices with IRT and the option "high flexibility"

128

128

  • of which in line, max.

61

61

  • Number of connectable IO Devices for RT, max.

128

128

  • of which in line, max.

128

128

  • Activation/deactivation of IO Devices

Yes

Yes

  • Number of IO Devices that can be simultaneously activated/deactivated, max.

8

8

  • IO Devices changing during operation (partner ports), supported

Yes

Yes

  • Number of IO Devices per tool, max.

8

8

  • Device replacement without swap medium

Yes

Yes

  • Send cycles

250 μs, 500 μs,1 ms; 2 ms, 4 ms (not in the case of IRT with "high flexibility" option)

250 μs, 500 μs,1 ms; 2 ms, 4 ms (not in the case of IRT with "high flexibility" option)

  • Updating time

250 s to 512 ms (depending on the operating mode, see Manual "S7-300 CPU 31xC and CPU 31x, Technical Data" for more details)

250 s to 512 ms (depending on the operating mode, see Manual "S7-300 CPU 31xC and CPU 31x, Technical Data" for more details)

Address area

  • Inputs, max.

2kbyte

2kbyte

  • Outputs, max.

2kbyte

2kbyte

  • User data consistency, max.

1024byte

1024byte

PROFINET IO Device

Services

  • PG/OP communication

Yes

Yes

  • Routing

Yes

Yes

  • S7 communication

Yes; With loadable FBs, max. configurable connections: 14, max. number of instances: 32

Yes; With loadable FBs, max. configurable connections: 14, max. number of instances: 32

  • Isochronous mode

No

No

  • Open IE communication

Yes; Via TCP/IP, ISO on TCP, and UDP

Yes; Via TCP/IP, ISO on TCP, and UDP

  • IRT

Yes

Yes

  • PROFIenergy

Yes; With SFB 73 / 74 prepared for loadable PROFIenergy standard FB for I-Device

Yes; With SFB 73 / 74 prepared for loadable PROFIenergy standard FB for I-Device

  • Shared device

Yes

Yes

  • Number of IO Controllers with shared device, max.

2

2

Transfer memory

  • Inputs, max.

1440byte; Per IO Controller with shared device

1440byte; Per IO Controller with shared device

  • Outputs, max.

1440byte; Per IO Controller with shared device

1440byte; Per IO Controller with shared device

Submodules

  • Number, max.

64

64

  • User data per submodule, max.

1024byte

1024byte

PROFINET CBA

  • acyclic transmission

Yes

Yes

  • cyclic transmission

Yes

Yes

Open IE communication

  • Number of connections, max.

8

8

  • Local port numbers used at the system end

0, 20, 21, 25, 80, 102, 135, 161, 8080, 34962, 34963, 34964, 65532, 65533, 65534, 65535

0, 20, 21, 25, 80, 102, 135, 161, 8080, 34962, 34963, 34964, 65532, 65533, 65534, 65535

  • Keep-alive function, supported

Yes

Yes

Protocols

Open IE communication

  • TCP/IP

Yes; via integrated PROFINET interface and loadable FBs

Yes; via integrated PROFINET interface and loadable FBs

  • Data length for connection type 01H, max.

1460byte

1460byte

  • Data length for connection type 11H, max.

32768byte

32768byte

  • several passive connections per port, supported

Yes

Yes

  • ISO-on-TCP (RFC1006)

Yes; via integrated PROFINET interface and loadable FBs

Yes; via integrated PROFINET interface and loadable FBs

  • Data length, max.

32768byte

32768byte

  • UDP

Yes; via integrated PROFINET interface and loadable FBs

Yes; via integrated PROFINET interface and loadable FBs

  • Data length, max.

1472byte

1472byte

Web server

  • User-defined websites

Yes

Yes

  • Number of HTTP clients

5

5

Isochronous mode

Isochronous operation (application synchronized up to terminal)

Yes; Via PROFIBUS DP or PROFINET interface

Yes; Via PROFIBUS DP or PROFINET interface

Communication functions

PG/OP communication

Yes

Yes

Data record routing

Yes

Yes

Global data communication

  • supported

Yes

Yes

  • Number of GD loops, max.

8

8

  • Number of GD packets, max.

8

8

  • Number of GD packets, transmitter, max.

8

8

  • Number of GD packets, receiver, max.

8

8

  • Size of GD packets, max.

22byte

22byte

  • Size of GD packet (of which consistent), max.

22byte

22byte

S7 basic communication

  • supported

Yes

Yes

  • User data per job, max.

76byte

76byte

  • User data per job (of which consistent), max.

76byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server)

76byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server)

S7 communication

  • supported

Yes

Yes

  • as server

Yes

Yes

  • as client

Yes; via integrated PROFINET interface and loadable FB or via CP and loadable FB

Yes; via integrated PROFINET interface and loadable FB or via CP and loadable FB

  • User data per job, max.

See online help of STEP 7 (shared parameters of the SFBs/FBs and of the SFCs/FCs of S7 Communication)

See online help of STEP 7 (shared parameters of the SFBs/FBs and of the SFCs/FCs of S7 Communication)

S5 compatible communication

  • supported

Yes; via CP and loadable FC

Yes; via CP and loadable FC

Web server

  • supported

Yes

Yes

PROFINET CBA (at set setpoint communication load)

  • Setpoint for the CPU communication load

50%

50%

  • Number of remote interconnection partners

32

32

  • Number of functions, master/slave

30

30

  • Total of all master/slave connections

1000

1000

  • Data length of all incoming connections master/slave, max.

4000byte

4000byte

  • Data length of all outgoing connections master/slave, max.

4000byte

4000byte

  • Number of device-internal and PROFIBUS interconnections

500

500

  • Data length of device-internal und PROFIBUS interconnections, max.

4000byte

4000byte

  • Data length per connection, max.

1400byte

1400byte

Remote interconnections with acyclic transmission

  • Sampling frequency: Sampling time, min.

500ms

500ms

  • Number of incoming interconnections

100

100

  • Number of outgoing interconnections

100

100

  • Data length of all incoming interconnections, max.

2000byte

2000byte

  • Data length of all outgoing interconnections, max.

2000byte

2000byte

  • Data length per connection, max.

1400byte

1400byte

Remote interconnections with cyclic transmission

  • Transmission frequency: Transmission interval, min.

10ms

10ms

  • Number of incoming interconnections

200

200

  • Number of outgoing interconnections

200

200

  • Data length of all incoming interconnections, max.

2000byte

2000byte

  • Data length of all outgoing interconnections, max.

2000byte

2000byte

  • Data length per connection, max.

450byte

450byte

HMI variables via PROFINET (acyclic)

  • Number of stations that can log on for HMI variables (PN OPC/iMap)

3; 2x PN OPC/1x iMap

3; 2x PN OPC/1x iMap

  • HMI variable updating

500ms

500ms

  • Number of HMI variables

200

200

  • Data length of all HMI variables, max.

2000byte

2000byte

PROFIBUS proxy functionality

  • supported

Yes

Yes

  • Number of linked PROFIBUS devices

16

16

  • Data length per connection, max.

240byte; Slave-dependent

240byte; Slave-dependent

Number of connections

  • overall

16

16

  • usable for PG communication

15

15

  • reserved for PG communication

1

1

  • adjustable for PG communication, min.

1

1

  • adjustable for PG communication, max.

15

15

  • usable for OP communication

15

15

  • reserved for OP communication

1

1

  • adjustable for OP communication, min.

1

1

  • adjustable for OP communication, max.

15

15

  • usable for S7 basic communication

14

14

  • reserved for S7 basic communication

0

0

  • adjustable for S7 basic communication, min.

0

0

  • adjustable for S7 basic communication, max.

14

14

  • usable for S7 communication

14

14

  • reserved for S7 communication

0

0

  • adjustable for S7 communication, min.

0

0

  • adjustable for S7 communication, max.

14

14

  • total number of instances, max.

32

32

  • usable for routing

X1 as MPI: max. 10; X1 as DP master: max. 24; X1 as DP slave (active): max. 14; X2 as PROFINET: 24 max.

X1 as MPI: max. 10; X1 as DP master: max. 24; X1 as DP slave (active): max. 14; X2 as PROFINET: 24 max.

S7 message functions

Number of login stations for message functions, max.

16; Depending on the configured connections for PG/OP and S7 basic communication

16; Depending on the configured connections for PG/OP and S7 basic communication

Process diagnostic messages

Yes

Yes

simultaneously active Alarm-S blocks, max.

300

300

Test commissioning functions

Status block

Yes; Up to 2 simultaneously

Yes; Up to 2 simultaneously

Single step

Yes

Yes

Number of breakpoints

4

4

Status/control

  • Status/control variable

Yes

Yes

  • Variables

Inputs, outputs, memory bits, DB, times, counters

Inputs, outputs, memory bits, DB, times, counters

  • Number of variables, max.

30

30

  • of which status variables, max.

30

30

  • of which control variables, max.

14

14

Forcing

  • Forcing

Yes

Yes

  • Forcing, variables

Inputs, outputs

Inputs, outputs

  • Number of variables, max.

10

10

Diagnostic buffer

  • present

Yes

Yes

  • Number of entries, max.

500

500

  • adjustable

No

No

  • of which powerfail-proof

100; Only the last 100 entries are retained

100; Only the last 100 entries are retained

  • Number of entries readable in RUN, max.

499

499

  • can be set

Yes; From 10 to 499

Yes; From 10 to 499

  • preset

10

10

Service data

  • can be read out

Yes

Yes

Standards, approvals, certificates

CE mark

Yes

Yes

UL approval

Yes; File E239877

Yes; File E239877

FM approval

Yes; CofC 3028431

Yes; CofC 3028431

RCM (formerly C-TICK)

Yes

Yes

KC approval

Yes

Yes

EAC (formerly Gost-R)

Yes

Yes

Railway application

  • EN 50155

Yes; Sections 4, 5 and 12; no further agreements apply; T1, Category 1, Class A/B

Use in hazardous areas

  • ATEX

Yes

Yes

Ambient conditions

Ambient temperature during operation

  • min.

-25C; = Tmin

-25C; = Tmin

  • max.

60C; = Tmax; the rated temperature range of -25 ... +55 C (T1) applies for the use on railway vehicles according to EN50155

70C; = Tmax; 60 C @ UL/cUL, ATEX and FM use

Ambient temperature during storage/transportation

  • min.

-40C

-40C

  • max.

70C

70C

Altitude during operation relating to sea level

  • Ambient air temperature-barometric pressure-altitude

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Relative humidity

  • With condensation, tested in accordance with IEC 60068-2-38, max.

100%; RH incl. condensation/frost (no commissioning under condensation conditions)

100%; RH incl. condensation/frost (no commissioning under condensation conditions)

Resistance

Use in stationary industrial systems

  • to biologically active substances according to EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation in corrosive atmospheres!

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation in corrosive atmospheres!

  • to chemically active substances according to EN 60721-3-3

Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

  • to mechanically active substances according to EN 60721-3-3

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Configuration

Configuration software

  • STEP 7

Yes; V5.5 or higher

Yes; V5.5 or higher

Programming

  • Command set

see instruction list

see instruction list

  • Nesting levels

8

8

  • System functions (SFC)

see instruction list

see instruction list

  • System function blocks (SFB)

see instruction list

see instruction list

Programming language

  • LAD

Yes

Yes

  • FBD

Yes

Yes

  • STL

Yes

Yes

  • SCL

Yes

Yes

  • CFC

Yes

Yes

  • GRAPH

Yes

Yes

  • HiGraph

Yes

Yes

Know-how protection

  • User program protection/password protection

Yes

Yes

  • Block encryption

Yes; With S7 block Privacy

Yes; With S7 block Privacy

Dimensions

Width

40mm

40mm

Height

125mm

125mm

Depth

130mm

130mm

Weights

Weight, approx.

340g

340g


















skener.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
DENDOR

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS -

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK -

  © " " 2007-2022
  (4872) 700-366  skenergo@mail.ru
.