Article number

6AG1153-1AA03-2XB0

6AG1153-2BA10-2XY0

6AG1153-2BA10-7XB0

SIPLUS IM153-1

SIPLUS ET200M IM153-2 EN50155

SIPLUS ET200M IM153-2 HF

General information

Product type designation

IM 153-1 DP ST

IM 153-2

IM 153-2 HF

Firmware version

V6.0.0

V6.0.0

Vendor identification (VendorID)

801Dh

801Eh

801Eh

Supply voltage

Rated value (DC)

  • 24 V DC

Yes

Yes

Yes

permissible range, lower limit (DC)

20.4V

20.4V

20.4V

permissible range, upper limit (DC)

28.8V

28.8V

28.8V

external protection for power supply lines (recommendation)

not necessary

2,5 A

2,5 A

Mains buffering

  • Mains/voltage failure stored energy time

5ms

5ms

5ms

Input current

Current consumption, max.

350mA; at 24 V DC

650mA; with 24 V DC supply

650mA; with 24 V DC supply

Inrush current, typ.

2.5A

3A

3A

It

0.1As

0.1As

0.1As

Output voltage

Rated value (DC)

5V

Output current

for backplane bus (5 V DC), max.

1A

1.5A

1.5A

Power loss

Power loss, typ.

3W

5.5W

5.5W

Address area

Addressing volume

  • Inputs

128byte

244byte

244byte

  • Outputs

128byte

244byte

244byte

Hardware configuration

Number of modules per DP slave interface, max.

8

12

12

Time stamping

Accuracy

1ms; 1ms at up to 8 modules; 10ms at up to 12 modules

1ms; 1ms at up to 8 modules; 10ms at up to 12 modules

Number of message buffers

15

15

Messages per message buffer

20

20

Number of stampable digital inputs, max.

128; Max. 128 signals/station; max. 32 signals/slot

128; Max. 128 signals/station; max. 32 signals/slot

Time format

RFC 1119

RFC 1119

Time resolution

0.466ns

0.466ns

Time interval for transmitting the message buffer if a message is present

1000ms

1000ms

Time stamp on signal change

rising / falling edge as signal entering or exiting

rising / falling edge as signal entering or exiting

Interfaces

Transmission procedure

RS 485

RS 485

RS 485

Interface physics, RS 485

Yes

Yes

Yes

Interface physics, FOC

No

No

No

PROFIBUS DP

  • Node addresses

1 to 125 permitted

1 to 125 permitted

1 to 125 permitted

  • automatic detection of transmission rate

Yes

Yes

Yes

  • Output current, max.

90mA

70mA

70mA

  • Transmission rate, max.

12Mbit/s

12Mbit/s

12Mbit/s

  • SYNC capability

Yes

Yes

Yes

  • FREEZE capability

Yes

Yes

Yes

  • Direct data exchange (slave-to-slave communication)

Yes; Sender

Yes; as publisher with all IO, as subscriber with F-IO only

Yes; as publisher with all IO, as subscriber with F-IO only

  • Design of electrical connection of PROFIBUS interface

9-pin sub D socket

9-pin sub D

9-pin sub D

1. Interface

DP slave

  • GSD file

(for DPV1) SIEM801D.GSD; SI01801D.GSG

SI05801E.GSG

SI05801E.GSG

  • automatic baud rate search

Yes

Yes

Yes

Protocols

Bus protocol/transmission protocol

PROFIBUS DP to EN 50170

PROFIBUS DP to EN 50170

PROFIBUS DP to EN 50170

Potential separation

Potential separation exists

Yes

Yes

Yes

Isolation

Isolation tested with

Isolation voltage 500 V

Isolation voltage 500 V

Isolation voltage 500 V

Degree and class of protection

IP degree of protection

IP20

IP20

IP20

Standards, approvals, certificates

CE mark

Yes

Yes

Yes

UL approval

Yes; File E239877

FM approval

Yes; CofC 3028431

RCM (formerly C-TICK)

Yes

KC approval

Yes

EAC (formerly Gost-R)

Yes

Railway application

  • EN 50155

Yes; T1 Category 1 Class A/B horizontal mounting position

Ambient conditions

Ambient temperature during operation

  • min.

-40C; = Tmin

-25C; = Tmin

-40C; = Tmin; Startup @ -25 C

  • max.

70C; = Tmax; 60 C @ UL/cUL, ATEX and FM use

60C; = Tmax; the rated temperature range of -25 ... +55 C (T1) applies for the use on railway vehicles according to EN50155

70C; = Tmax

  • At cold restart, min.

-25C

-25C

-25C

Ambient temperature during storage/transportation

  • min.

-40C

-40C

-40C

  • max.

70C

70C

70C

Altitude during operation relating to sea level

  • Ambient air temperature-barometric pressure-altitude

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Relative humidity

  • With condensation, tested in accordance with IEC 60068-2-38, max.

100%; RH incl. condensation/frost (no commissioning under condensation conditions)

100%; RH incl. condensation/frost (no commissioning under condensation conditions)

100%; RH incl. condensation/frost (no commissioning under condensation conditions)

Resistance

Use in stationary industrial systems

  • to biologically active substances according to EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

  • to chemically active substances according to EN 60721-3-3

Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

  • to mechanically active substances according to EN 60721-3-3

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Configuration

Configuration software

  • STEP 7

STEP 7 / COM PROFIBUS / non-Siemens tools via GSD file

Yes; STEP 7 / COM PROFIBUS / non-Siemens tools via GSD file

Yes; STEP 7 / COM PROFIBUS / non-Siemens tools via GSD file

Dimensions

Width

40mm

40mm

40mm

Height

125mm

125mm

125mm

Depth

117mm

117mm

117mm

Weights

Weight, approx.

360g

360g

360g


Article number

6AG1195-7HA00-2XA0

6AG1195-7HB00-7XA0

6AG1195-7HC00-2XA0

6AG1195-7HD10-2XA0

SIPLUS ET200M DP Busmodul

SIPLUS DP Busmodul ET200M 2X40

SIPLUS ET200M Busmodul

SIPLUS_ET200M_DP_Busmodul

Standards, approvals, certificates

CE mark

Yes

Yes

Yes

Yes

UL approval

Yes; File E239877

Yes; File E239877

Yes; File E239877

Yes; File E239877

FM approval

Yes; CofC 3028431

Yes; CofC 3028431

Yes; CofC 3028431

Yes; CofC 3028431

RCM (formerly C-TICK)

Yes

Yes

Yes

Yes

KC approval

Yes

Yes

Yes

Yes

EAC (formerly Gost-R)

Yes

Yes

Yes

Yes

Ambient conditions

Ambient temperature during operation

  • min.

-40C; = Tmin

-40C; = Tmin

-40C; = Tmin

-40C; = Tmin

  • max.

70C; = Tmax; 60 C @ UL/cUL, ATEX and FM use

70C; = Tmax; 60 C @ UL/cUL, ATEX and FM use

70C; = Tmax; 60 C @ UL/cUL, ATEX and FM use

70C; = Tmax; 60 C @ UL/cUL, ATEX and FM use

Ambient temperature during storage/transportation

  • min.

-40C

-40C

-40C

  • max.

70C

70C

70C

Altitude during operation relating to sea level

  • Ambient air temperature-barometric pressure-altitude

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)

Relative humidity

  • With condensation, tested in accordance with IEC 60068-2-38, max.

100%; RH incl. condensation/frost (no commissioning under condensation conditions)

100%; RH incl. condensation/frost (no commissioning under condensation conditions)

100%; RH incl. condensation/frost (no commissioning under condensation conditions)

100%; RH incl. condensation/frost (no commissioning under condensation conditions)

Resistance

Use in stationary industrial systems

  • to biologically active substances according to EN 60721-3-3

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request

  • to chemically active substances according to EN 60721-3-3

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!

  • to mechanically active substances according to EN 60721-3-3

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Dimensions

Width

97mm

97mm

97mm

97mm

Height

92mm

92mm

92mm

92mm

Depth

30mm

30mm

30mm

30mm

Weights

Weight, approx.

111g

140g

127g

133g