Supply voltage | | |
Rated value (DC) | 24 V | |
Rated value (AC) | | 230 V; 120/230 V AC |
Reverse polarity protection | Yes | |
Line frequency | | |
| | 47 Hz |
| | 63 Hz |
Input current | | |
from supply voltage L+, max. | 4 A | |
from supply voltage L1, max. | | 1.04 A; at rated voltage 230 VAC:0.45A at rated voltage 120 VAC:0.75A |
Power loss | | |
Power loss, typ. | 20 W | 5 W; 5 W + 1.2 x total power loss of the electronics modules |
Power loss, max. | | 21.3 W |
Interrupts/diagnostics/status information | | |
Status indicator | Yes | Yes |
Alarms | No | No |
Diagnostic messages | | |
| Yes; via IM 152 | Yes; via IM 152 |
Diagnostics indication LED | | |
| No | No |
Ex(i) characteristics | | |
Maximum values of input circuits (per channel) | | |
| 250 V; DC | 264 V; AC/DC |
Potential separation | | |
primary/secondary | Yes | Yes |
between supply voltage and electronics | Yes | No |
Standards, approvals, certificates | | |
CE mark | Yes | Yes |
Use in hazardous areas | | |
| Ex de [ib]IIC T4 | Ex de [ib]IIC T4 |
| 04 ATEX 2263 | 09 ATEX 0156 |
Dimensions | | |
Width | 60 mm | 60 mm |
Height | 190 mm | 190 mm |
Depth | 136.5 mm | 136.5 mm |
Weights | | |
Weight, approx. | 2 700 g | 2 700 g |