Mode of operation
| |
Measuring principle | Controller for acoustic sensing (SITRANS AS100) |
Typical application | Connects to SITRANS AS100 to detect burst filter bag |
Input | 0 … 10 V DC, from sensor |
Output | |
Output signal | 4 … 20 mA isolated output, 2 Form C relays - latching or non-latching - 5 amp at 250 V AC non-inductive |
Sensor excitation | 26 V DC |
Max. load | 750 О© |
Rated operating conditions | |
Installation conditions | |
| Indoor |
Ambient conditions | |
- Ambient temperature for enclosure
| -20 … +50 °C (-4 … +122 °F) |
| 80 % for temperatures up to 50 °C (122 °F) |
| IP20 |
| II |
| 2 |
Design | |
Weight | 550 g (18 oz) |
Dimensions (W x H x D) | 55 x 75 x 110 mm (2.2 x 3 x 4.4 inch) |
Material enclosure | Polycarbonate |
Mounting | DIN Rail (DIN 46277 or DIN EN 50022), or wall mount, up to 500 m (1 500 ft) from sensor |
Cable | 2 twisted pair, 24 AWG (22 mmІ), shielded. Mount up to 500 m (1 500 ft) from sensor |
Display | Liquid crystal, three digits, 9 mm (0.35 inch), high and multi-segment graphic symbols for operation status |
Power supply | |
Supply voltage | 100, 115, 200, 230 V AC ± 15 %, 50/60 Hz, factory set |
Power consumption | Max. 10 VA |
Approvals | CSAUS/C, CE, RCM, EAC, KCC |