Mode of operation and design | |
Measuring principle | Electromagnetic with pulsed constant field |
Empty pipe | Detection of empty pipe (special cable required in remote mounted installation) |
Excitation frequency | Depend on sensor size |
Electrode input impedance | > 1 x 1014 О© |
Input | |
Digital input | 11 ... 30 V DC, Ri = 4. 4 KО© |
| 50 ms |
| I11 V DC = 2.5 mA, I30 V DC = 7 mA |
Output | |
Current output | |
| 0 ... 20 mA or 4 ... 20 mA |
| < 800 О© |
| 0.1 … 30 s, adjustable |
Digital output | |
| 0 ... 10 kHz, 50 % duty cycle (uni/bidirectional) |
| 24 V DC, 30 mA, 1 kΩ ≤ Ri ≤ 10 kΩ, short-circuit-protected (power supplied from flowmeter) |
| 3 … 30 V DC, max. 110 mA, 200 Ω ≤ Ri ≤ 10 kΩ powered from connected equipment) |
| 0.1 … 30 s, adjustable |
Relay output | |
| Changeover relay, same as current output |
| 42 V AC/2 A, 24 V DC/1 A |
Low flow cut off | 0 ... 9.9 % of maximum flow |
Galvanic isolation | All inputs and outputs are galvanically isolated |
Max. measuring error (incl. sensor and zero point) (for detailed accuracy specifications see "System information") | |
| ± 0.4 % ± 1 mm/s |
| ± 0.2 % ± 1 mm/s |
Rated operation conditions | |
Ambient temperature | |
| - Display version:
-20 ... +60 C (-4 ... +140 F) - Blind version:
-20 ... +60 C (-4 ... +140 F) - MI-001 version
-25 ... +55 єC (-13 ... +131 єF) - Custody transfer (CT) version
-20 ... +50 єC (-4 ... +122 єF)
|
| -40 ... +70 C (-40 ... +158 F°) |
Mechanical load (vibration) | |
Compact version | 18 ... 1000 Hz, 3.17 g RMS, sinusoidal in all directions to IEC 68-2-36 |
19“ insert | 1 ... 800 Hz, 1 G, sinusoidal in all directions to IEC 68-2-36 |
Degree of protection | |
Compact version | IP67/NEMA 4X/6 to IEC 529 and DIN 40050 (1 mH2O 30 min.) |
19“ insert | IP20/NEMA 1 to IEC 529 and DIN 40050 |
EMC performance | IEC/EN 61326-1 (all environments) IEC/EN 61326-2-5 |
Display and keypad | |
Totalizer | Two eight-digit counters for forward, net or reverse flow |
Display | Background illumination with alphanumeric text, 3 x 20 characters to indicate flow rate, totalized values, settings and faults; Reverse flow indicated by negative sign |
Time constant | Time constant as current output time constant |
Design | |
Enclosure material | |
| Fiber glass reinforced polyamide; stainless steel AISI 316/1.4436 (IP65) |
| Standard 19“ insert of aluminium/steel (DIN 41494), width: 21 TE, height: 3 HE |
| IP20/NEMA 1; Aluminium |
| IP20/NEMA 1 (prepared for IP65/NEMA 2 display side); ABS plastic |
| IP66/NEMA 4X; ABS plastic |
Dimensions | |
| See dimensional drawings |
| See dimensional drawings |
Weight | |
| 0.75 kg (2 lbs) |
| See dimensional drawings |
Power supply | - 115 ... 230 V AC +10 % -15 %, 50 ... 60 Hz
- 11 ... 30 V DC or 11 ... 24 V AC
|
Power consumption | - 230 V AC: 17 VA
- 24 V AC: 9 VA, IN = 380 mA,
IST = 8 A (30 ms) - 12 V DC: 11 W, IN = 920 mA,
IST = 4 A (250 ms) - 24 V DC: 8.4 VA, IN = 350 mA,
IST = 4 A (10 ms)
IST= 4 A (250 ms): For solar panel please securestable current supply |
Certificates and approvals | |
General purpose | - CE (LVD, EMC, PED, RoHS)
- UL (c-UL-us)
|
Hazardous area | - NI Class I Div. 2 Groups A, B, C, D
|
Custody transfer | - Cold water: MI-001
- Chilled water
- PTB K 7.2 (Germany)
- OE 12/C 040 (Austria)
- TS 27.02 008 (Denmark)
|
Marine (only for remote version with MAG 5100 W, DN 50 ... DN 300) | - ABS
- Bureau Veritas
- DNV
- GL
- Lloyd's Register of Shipping
|
Others | - CMC/CPA (China)
- C-TICK (Australia andNew Zealand EMC)
- EAC (Russia, Belarus, Kazakhstan)
- KCC (South Korea)
|
Communication | |
Standard | |
| Without serial communication or HART as option |
| Prepared for client-mounted add-on modules |
Optional (On MAG 6000 only) | HART, Modbus RTU/RS 485, FOUNDATION Fieldbus H1, DeviceNet, PROFIBUS PA, PROFIBUS DP as add-on modules |
| No communication moduls approved |