Transmission rate | |
Transfer rate | |
| 9.6 kbit/s ... 12 Mbit/s |
Interfaces | |
Number of interfaces acc. to Industrial Ethernet | 0 |
Number of electrical connections | |
| 1 |
Type of electrical connection | |
| 9-pin Sub-D socket (RS485) |
Supply voltage, current consumption, power loss | |
Type of voltage of the supply voltage | DC |
Supply voltage 1 from backplane bus | 5 V |
Relative symmetrical tolerance at DC | |
| 5 % |
Consumed current | |
| 0.6 A |
Power loss [W] | 3 W |
Permitted ambient conditions | |
Ambient temperature | |
| 0 ... 60 °C |
| -40 ... +70 °C |
| -40 ... +70 °C |
Relative humidity at 25 °C without condensation during operation maximum | 95 % |
Protection class IP | IP20 |
Design, dimensions and weight | |
Module format | Compact module S7-400 single width |
Width | 25 mm |
Height | 290 mm |
Depth | 210 mm |
Net weight | 0.65 kg |
Product properties, functions, components general | |
Number of units | |
| 14 |
| The number of CPs that can be operated as DP masters depends on the number of CP 443-1 Advanced processors operating in the S7-400 station as PROFINET IO controllers. Up to 10 CPs can be operated in total: up to 4 as PROFINET IO controllers (CP 443-1 Advanced); up to 10 as DP masters (CP 443-5 Extended) |
Performance data open communication | |
Number of possible connections for open communication by means of SEND/RECEIVE blocks maximum | 32 |
Amount of data | |
| 240 byte |
Performance data PROFIBUS DP | |
Service as DP master | |
| Yes |
Number of DP slaves on DP master usable | 125 |
Amount of data | |
| 4 096 byte |
| 4 096 byte |
| 244 byte |
| 244 byte |
Performance data S7 communication | |
Number of possible connections for S7 communication | |
| 48 |
Performance data multi-protocol mode | |
Number of active connections with multi-protocol mode | |
| 59 |
| 54 |
Configuration software | |
| STEP 7 V5.4 SP4 or higher / STEP 7 Professional V12 (TIA Portal) or higher |