Siemens
01 2018
(4872) 700-366
skenergo@mail.ru

Article number

6ES7314-6CH04-0AB0

CPU314C-2DP, 24DI/16DO/5AI/2AO, 192 KB

General information

HW functional status

01

Firmware version

V3.3

Engineering with

  • Programming package

STEP 7 V5.5 + SP1 or higher or STEP 7 V5.3 + SP2 or higher with HSP 203

Supply voltage

Rated value (DC)

  • 24 V DC

Yes

permissible range, lower limit (DC)

19.2V

permissible range, upper limit (DC)

28.8V

external protection for power supply lines (recommendation)

Miniature circuit breaker, type C; min. 2 A; miniature circuit breaker type B, min. 4 A

Mains buffering

  • Mains/voltage failure stored energy time

5ms

  • Repeat rate, min.

1s

Load voltage L+

Digital inputs

  • Rated value (DC)

24V

  • Reverse polarity protection

Yes

Digital outputs

  • Rated value (DC)

24V

  • Reverse polarity protection

No

Input current

Current consumption (rated value)

880mA

Current consumption (in no-load operation), typ.

150mA

Inrush current, typ.

5A

It

0.7As

Digital inputs

  • from load voltage L+ (without load), max.

80mA

Digital outputs

  • from load voltage L+, max.

50mA

Power loss

Power loss, typ.

13W

Memory

Work memory

  • integrated

192kbyte

  • expandable

No

  • Size of retentive memory for retentive data blocks

64kbyte

Load memory

  • Plug-in (MMC)

Yes

  • Plug-in (MMC), max.

8Mbyte

  • Data management on MMC (after last programming), min.

10y

Backup

  • present

Yes; Guaranteed by MMC (maintenance-free)

  • without battery

Yes; Program and data

CPU processing times

for bit operations, typ.

0.06s

for word operations, typ.

0.12s

for fixed point arithmetic, typ.

0.16s

for floating point arithmetic, typ.

0.59s

CPU-blocks

Number of blocks (total)

1024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used.

DB

  • Number, max.

1024; Number range: 1 to 16000

  • Size, max.

64kbyte

FB

  • Number, max.

1024; Number range: 0 to 7999

  • Size, max.

64kbyte

FC

  • Number, max.

1024; Number range: 0 to 7999

  • Size, max.

64kbyte

OB

  • Description

see instruction list

  • Size, max.

64kbyte

  • Number of free cycle OBs

1; OB 1

  • Number of time alarm OBs

1; OB 10

  • Number of delay alarm OBs

2; OB 20, 21

  • Number of cyclic interrupt OBs

4; OB 32, 33, 34, 35

  • Number of process alarm OBs

1; OB 40

  • Number of DPV1 alarm OBs

3; OB 55, 56, 57

  • Number of startup OBs

1; OB 100

  • Number of asynchronous error OBs

5; OB 80, 82, 85, 86, 87

  • Number of synchronous error OBs

2; OB 121, 122

Nesting depth

  • per priority class

16

  • additional within an error OB

4

Counters, timers and their retentivity

S7 counter

  • Number

256

Retentivity

  • adjustable

Yes

  • lower limit

0

  • upper limit

255

  • preset

Z 0 to Z 7

Counting range

  • lower limit

0

  • upper limit

999

IEC counter

  • Number

Unlimited (limited only by RAM capacity)

S7 times

  • Number

256

Retentivity

  • adjustable

Yes

  • lower limit

0

  • upper limit

255

  • preset

No retentivity

Time range

  • lower limit

10ms

  • upper limit

9990s

IEC timer

  • present

Yes

  • Type

SFB

  • Number

Unlimited (limited only by RAM capacity)

Data areas and their retentivity

retentive data area in total

All, max. 64 KB

Flag

  • Number, max.

256byte

  • Retentivity available

Yes; MB 0 to MB 255

  • Retentivity preset

MB 0 to MB 15

  • Number of clock memories

8; 1 memory byte

Data blocks

  • Retentivity adjustable

Yes; via non-retain property on DB

  • Retentivity preset

Yes

Local data

  • per priority class, max.

32kbyte; Max. 2048 bytes per block

Address area

I/O address area

  • Inputs

2048byte

  • Outputs

2048byte

of which distributed

  • Inputs

2003byte

  • Outputs

2010byte

Process image

  • Inputs

2048byte

  • Outputs

2048byte

  • Inputs, adjustable

2048byte

  • Outputs, adjustable

2048byte

  • Inputs, default

128byte

  • Outputs, default

128byte

Default addresses of the integrated channels

  • Digital inputs

124.0 to 126.7

  • Digital outputs

124.0 to 125.7

  • Analog inputs

752 to 761

  • Analog outputs

752 to 755

Digital channels

  • Inputs

16048

  • of which central

1016

  • Outputs

16096

  • of which central

1008

Analog channels

  • Inputs

1006

  • of which central

253

  • Outputs

1007

  • of which central

250

Hardware configuration

Number of expansion units, max.

3

Number of DP masters

  • integrated

1

  • via CP

4

Number of operable FMs and CPs (recommended)

  • FM

8

  • CP, PtP

8

  • CP, LAN

10

Rack

  • Racks, max.

4

  • Modules per rack, max.

8; In rack 3 max. 7

Time of day

Clock

  • Hardware clock (real-time)

Yes

  • retentive and synchronizable

Yes

  • Backup time

6wk; At 40 C ambient temperature

  • Deviation per day, max.

10s; Typ.: 2 s

  • Behavior of the clock following POWER-ON

Clock continues running after POWER OFF

  • Behavior of the clock following expiry of backup period

Clock continues to run with the time at which the power failure occurred

Operating hours counter

  • Number

1

  • Number/Number range

0

  • Range of values

0 to 2^31 hours (when using SFC 101)

  • Granularity

1 hour

  • retentive

Yes; Must be restarted at each restart

Clock synchronization

  • supported

Yes

  • to MPI, master

Yes

  • to MPI, slave

Yes

  • to DP, master

Yes; With DP slave only slave clock

  • to DP, slave

Yes

  • in AS, master

Yes

  • in AS, slave

No

Digital inputs

Number of digital inputs

24

  • of which inputs usable for technological functions

16

integrated channels (DI)

24

Input characteristic curve in accordance with IEC 61131, type 1

Yes

horizontal installation

  • up to 40 C, max.

24

  • up to 60 C, max.

12

vertical installation

  • up to 40 C, max.

12

Input voltage

  • Rated value (DC)

24V

  • for signal "0"

-3 to +5V

  • for signal "1"

+15 to +30V

Input current

  • for signal "1", typ.

8mA

Input delay (for rated value of input voltage)

for standard inputs

  • parameterizable

Yes; 0.1 / 0.3 / 3 / 15 ms (You can reconfigure the input delay of the standard inputs during program runtime. Please note that under certain circumstances your newly set filter time may not be effective until the next filter cycle.)

  • Rated value

3ms

for counter/technological functions

  • at "0" to "1", max.

8s; Minimum pulse width/minimum pause between pulses at maximum counting frequency

Cable length

  • shielded, max.

1000m; 50 m for technological functions

  • unshielded, max.

600m; For technological functions: No

for technological functions

  • shielded, max.

50m; at maximum count frequency

  • unshielded, max.

not allowed

Digital outputs

Number of digital outputs

16

  • of which high-speed outputs

4; Notice: You cannot connect the fast outputs of your CPU in parallel

integrated channels (DO)

16

Short-circuit protection

Yes; Clocked electronically

  • Response threshold, typ.

1A

Limitation of inductive shutdown voltage to

L+ (-48 V)

Controlling a digital input

Yes

Switching capacity of the outputs

  • on lamp load, max.

5W

Load resistance range

  • lower limit

48Ω

  • upper limit

4kΩ

Output voltage

  • for signal "1", min.

L+ (-0.8 V)

Output current

  • for signal "1" rated value

500mA

  • for signal "1" permissible range, min.

5mA

  • for signal "1" permissible range, max.

0.6A

  • for signal "1" minimum load current

5mA

  • for signal "0" residual current, max.

0.5mA

Parallel switching of two outputs

  • for uprating

No

  • for redundant control of a load

Yes

Switching frequency

  • with resistive load, max.

100Hz

  • with inductive load, max.

0.5Hz

  • on lamp load, max.

100Hz

  • of the pulse outputs, with resistive load, max.

2.5kHz

horizontal installation

  • up to 40 C, max.

3A

  • up to 60 C, max.

2A

vertical installation

  • up to 40 C, max.

2A

Cable length

  • shielded, max.

1000m

  • unshielded, max.

600m

Analog inputs

Number of analog inputs

5

  • For voltage/current measurement

4

  • For resistance/resistance thermometer measurement

1

integrated channels (AI)

5; 4 x current/voltage, 1 x resistance

permissible input voltage for current input (destruction limit), max.

5V; Permanent

permissible input voltage for voltage input (destruction limit), max.

30V; Permanent

permissible input current for voltage input (destruction limit), max.

0.5mA; Permanent

permissible input current for current input (destruction limit), max.

50mA; Permanent

No-load voltage, typ.

3.3V

Constant measurement current for resistance-type transmitter, typ.

1.25mA

Technical unit for temperature measurement adjustable

Yes; Degrees Celsius / degrees Fahrenheit / Kelvin

Input ranges

  • Voltage

Yes; 10 V / 100 kΩ; 0 V to 10 V / 100 kΩ

  • Current

Yes; 20 mA / 100 Ω; 0 mA to 20 mA / 100 Ω; 4 mA to 20 mA / 100 Ω

  • Resistance thermometer

Yes; Pt 100 / 10 MΩ

  • Resistance

Yes; 0 Ω to 600 Ω / 10 MΩ

Input ranges (rated values), voltages

  • 0 to +10 V

Yes

  • Input resistance (0 to 10 V)

100kΩ

Input ranges (rated values), currents

  • 0 to 20 mA

Yes

  • Input resistance (0 to 20 mA)

100Ω

  • -20 mA to +20 mA

Yes

  • Input resistance (-20 mA to +20 mA)

100Ω

  • 4 mA to 20 mA

Yes

  • Input resistance (4 mA to 20 mA)

100Ω

Input ranges (rated values), resistance thermometer

  • Pt 100

Yes

  • Input resistance (Pt 100)

10MΩ

Input ranges (rated values), resistors

  • 0 to 600 ohms

Yes

  • Input resistance (0 to 600 ohms)

10MΩ

Thermocouple (TC)

Temperature compensation

  • parameterizable

No

Characteristic linearization

  • parameterizable

Yes; by software

  • for resistance thermometer

Pt 100

Cable length

  • shielded, max.

100m

Analog outputs

Number of analog outputs

2

integrated channels (AO)

2

Voltage output, short-circuit protection

Yes

Voltage output, short-circuit current, max.

55mA

Current output, no-load voltage, max.

14V

Output ranges, voltage

  • 0 to 10 V

Yes

  • -10 V to +10 V

Yes

Output ranges, current

  • 0 to 20 mA

Yes

  • -20 mA to +20 mA

Yes

  • 4 mA to 20 mA

Yes

Connection of actuators

  • for voltage output two-wire connection

Yes; Without compensation of the line resistances

  • for voltage output four-wire connection

No

  • for current output two-wire connection

Yes

Load impedance (in rated range of output)

  • with voltage outputs, min.

1kΩ

  • with voltage outputs, capacitive load, max.

0.1F

  • with current outputs, max.

300Ω

  • with current outputs, inductive load, max.

0.1mH

Destruction limits against externally applied voltages and currents

  • Voltages at the outputs towards MANA

16V; Permanent

  • Current, max.

50mA; Permanent

Cable length

  • shielded, max.

200m

Analog value generation for the inputs

Measurement principle

Actual value encryption (successive approximation)

Integration and conversion time/resolution per channel

  • Resolution with overrange (bit including sign), max.

12bit

  • Integration time, parameterizable

Yes; 16.6 / 20 ms

  • Interference voltage suppression for interference frequency f1 in Hz

50 / 60 Hz

  • permissible input frequency, max.

400Hz

  • Time constant of the input filter

0.38ms

  • Basic execution time of the module (all channels released)

1ms

Analog value generation for the outputs

Integration and conversion time/resolution per channel

  • Resolution with overrange (bit including sign), max.

12bit

  • Conversion time (per channel)

1ms

Settling time

  • for resistive load

0.6ms

  • for capacitive load

1ms

  • for inductive load

0.5ms

Encoder

Connection of signal encoders

  • for voltage measurement

Yes

  • for current measurement as 2-wire transducer

Yes; with external supply

  • for current measurement as 4-wire transducer

Yes

  • for resistance measurement with two-wire connection

Yes; Without compensation of the line resistances

  • for resistance measurement with three-wire connection

No

  • for resistance measurement with four-wire connection

No

Connectable encoders

  • 2-wire sensor

Yes

  • permissible quiescent current (2-wire sensor), max.

1.5mA

Errors/accuracies

Temperature error (relative to input range), (+/-)

0.006%/K

Crosstalk between the inputs, min.

60dB

Repeat accuracy in steady state at 25 C (relative to input range), (+/-)

0.06%

Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-)

0.1%

Linearity error (relative to output range), (+/-)

0.15%

Temperature error (relative to output range), (+/-)

0.01%/K

Crosstalk between the outputs, min.

60dB

Repeat accuracy in steady state at 25 C (relative to output range), (+/-)

0.06%

Operational error limit in overall temperature range

  • Voltage, relative to input range, (+/-)

1%

  • Current, relative to input range, (+/-)

1%

  • Resistance, relative to input range, (+/-)

1%

  • Voltage, relative to output range, (+/-)

1%

  • Current, relative to output range, (+/-)

1%

Basic error limit (operational limit at 25 C)

  • Voltage, relative to input range, (+/-)

0.8%; Linearity error 0.06 %

  • Current, relative to input range, (+/-)

0.8%; Linearity error 0.06 %

  • Resistance, relative to input range, (+/-)

0.8%; Linearity error 0.2 %

  • Resistance thermometer, relative to input range, (+/-)

0.8%

  • Voltage, relative to output range, (+/-)

0.8%

  • Current, relative to output range, (+/-)

0.8%

Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency

  • Series mode interference (peak value of interference < rated value of input range), min.

30dB

  • Common mode interference, min.

40dB

Interfaces

Number of industrial Ethernet interfaces

0

Number of PROFINET interfaces

0

Number of RS 485 interfaces

2; MPI and PROFIBUS DP

Number of RS 422 interfaces

0

1. Interface

Interface type

Integrated RS 485 interface

Physics

RS 485

Isolated

No

Power supply to interface (15 to 30 V DC), max.

200mA

Functionality

  • MPI

Yes

  • PROFIBUS DP master

No

  • PROFIBUS DP slave

No

  • Point-to-point connection

No

MPI

  • Transmission rate, max.

187.5kbit/s

Services

  • PG/OP communication

Yes

  • Routing

Yes

  • Global data communication

Yes

  • S7 basic communication

Yes

  • S7 communication

Yes; Only server, configured on one side

  • S7 communication, as client

No; but via CP and loadable FB

  • S7 communication, as server

Yes

2. Interface

Interface type

Integrated RS 485 interface

Physics

RS 485

Isolated

Yes

Power supply to interface (15 to 30 V DC), max.

200mA

Functionality

  • MPI

No

  • PROFINET IO Controller

No

  • PROFINET IO Device

No

  • PROFINET CBA

No

  • PROFIBUS DP master

Yes

  • PROFIBUS DP slave

Yes

  • Point-to-point connection

No

DP master

  • Transmission rate, max.

12Mbit/s

  • Number of DP slaves, max.

124

Services

  • PG/OP communication

Yes

  • Routing

Yes

  • Global data communication

No

  • S7 basic communication

Yes; I blocks only

  • S7 communication

Yes; Only server, configured on one side

  • S7 communication, as client

No

  • S7 communication, as server

Yes

  • Equidistance

Yes

  • Isochronous mode

No

  • SYNC/FREEZE

Yes

  • Activation/deactivation of DP slaves

Yes

  • Number of DP slaves that can be simultaneously activated/deactivated, max.

8

  • Direct data exchange (slave-to-slave communication)

Yes; As subscriber

  • DPV1

Yes

Address area

  • Inputs, max.

2kbyte

  • Outputs, max.

2kbyte

User data per DP slave

  • Inputs, max.

244byte

  • Outputs, max.

244byte

DP slave

  • GSD file

The latest GSD file is available on the Internet (http://www.siemens.com/profibus-gsd)

  • Transmission rate, max.

12Mbit/s

  • automatic baud rate search

Yes; only with passive interface

  • Address area, max.

32

  • User data per address area, max.

32byte

Services

  • PG/OP communication

Yes

  • Routing

Yes; Only with active interface

  • Global data communication

No

  • S7 basic communication

No

  • S7 communication

Yes; Only server, configured on one side

  • S7 communication, as client

No

  • S7 communication, as server

Yes

  • Direct data exchange (slave-to-slave communication)

Yes

  • DPV1

No

Transfer memory

  • Inputs

244byte

  • Outputs

244byte

Communication functions

PG/OP communication

Yes

Data record routing

Yes

Global data communication

  • supported

Yes

  • Number of GD loops, max.

8

  • Number of GD packets, max.

8

  • Number of GD packets, transmitter, max.

8

  • Number of GD packets, receiver, max.

8

  • Size of GD packets, max.

22byte

  • Size of GD packet (of which consistent), max.

22byte

S7 basic communication

  • supported

Yes

  • User data per job, max.

76byte

  • User data per job (of which consistent), max.

76byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server)

S7 communication

  • supported

Yes

  • as server

Yes

  • as client

Yes; Via CP and loadable FB

  • User data per job, max.

180kbyte; With PUT/GET

  • User data per job (of which consistent), max.

240byte; as server

S5 compatible communication

  • supported

Yes; via CP and loadable FC

Number of connections

  • overall

12

  • usable for PG communication

11

  • reserved for PG communication

1

  • adjustable for PG communication, min.

1

  • adjustable for PG communication, max.

11

  • usable for OP communication

11

  • reserved for OP communication

1

  • adjustable for OP communication, min.

1

  • adjustable for OP communication, max.

11

  • usable for S7 basic communication

8

  • reserved for S7 basic communication

0

  • adjustable for S7 basic communication, min.

0

  • adjustable for S7 basic communication, max.

8

  • usable for routing

4; max.

S7 message functions

Number of login stations for message functions, max.

12; Depending on the configured connections for PG/OP and S7 basic communication

Process diagnostic messages

Yes

simultaneously active Alarm-S blocks, max.

300

Test commissioning functions

Status block

Yes; Up to 2 simultaneously

Single step

Yes

Number of breakpoints

4

Status/control

  • Status/control variable

Yes

  • Variables

Inputs, outputs, memory bits, DB, times, counters

  • Number of variables, max.

30

  • of which status variables, max.

30

  • of which control variables, max.

14

Forcing

  • Forcing

Yes

  • Forcing, variables

Inputs, outputs

  • Number of variables, max.

10

Diagnostic buffer

  • present

Yes

  • Number of entries, max.

500

  • adjustable

No

  • of which powerfail-proof

100; Only the last 100 entries are retained

  • Number of entries readable in RUN, max.

499

  • can be set

Yes; From 10 to 499

  • preset

10

Service data

  • can be read out

Yes

Interrupts/diagnostics/status information

Diagnostics indication LED

  • Status indicator digital input (green)

Yes

  • Status indicator digital output (green)

Yes

Integrated Functions

Number of counters

4; See "Technological Functions" manual

Counting frequency (counter) max.

60kHz

Frequency measurement

Yes

Number of frequency meters

4; up to 60 kHz (see "Technological Functions" manual)

controlled positioning

Yes

integrated function blocks (closed-loop control)

Yes; PID controller (see "Technological Functions" manual)

PID controller

Yes

Number of pulse outputs

4; Pulse width modulation up to 2.5 kHz (see "Technological Functions" Manual)

Limit frequency (pulse)

2.5kHz

Potential separation

Potential separation digital inputs

  • Potential separation digital inputs

Yes

  • between the channels

No

  • between the channels and backplane bus

Yes

Potential separation digital outputs

  • Potential separation digital outputs

Yes

  • between the channels

Yes

  • between the channels, in groups of

8

  • between the channels and backplane bus

Yes

Potential separation analog inputs

  • Potential separation analog inputs

Yes; common for analog I/O

  • between the channels

No

  • between the channels and backplane bus

Yes

Potential separation analog outputs

  • Potential separation analog outputs

Yes; common for analog I/O

  • between the channels

No

  • between the channels and backplane bus

Yes

Permissible potential difference

between different circuits

75 V DC/60 V AC

Between the inputs and MANA (UCM)

8 V DC

between MANA and M internally (UISO)

75 V DC/60 V AC

Isolation

Isolation tested with

600 V DC

Ambient conditions

Ambient temperature during operation

  • min.

0C

  • max.

60C

Configuration

Configuration software

  • STEP 7

Yes; STEP 7 V5.5 + SP1 or higher or STEP 7 V5.3 + SP2 or higher with HSP 203

  • STEP 7 Lite

No

Programming

  • Command set

see instruction list

  • Nesting levels

8

  • System functions (SFC)

see instruction list

  • System function blocks (SFB)

see instruction list

Programming language

  • LAD

Yes

  • FBD

Yes

  • STL

Yes

  • SCL

Yes

  • CFC

Yes

  • GRAPH

Yes

  • HiGraph

Yes

Know-how protection

  • User program protection/password protection

Yes

  • Block encryption

Yes; With S7 block Privacy

Dimensions

Width

120mm

Height

125mm

Depth

130mm

Weights

Weight, approx.

680g


















skener.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
DENDOR

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS -

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK -

  © " " 2007-2022
  (4872) 700-366  skenergo@mail.ru
.