| 3-wire version |
Mode of operation | |
Measuring principle | Ultrasonic level measurement |
Input | |
Measuring range | 0.25 ... 5 m (0.8 ... 16.4 ft) |
Frequency | 54 kHz |
Output | |
mA | 4 ... 20 mA |
| Proportional/ inversely proportional |
| 750 О© at 24 V DC |
Relay | For level alarm or fault |
Power supply | |
Supply voltage | 18 ... 30 V DC, max. 0.2 A |
Max. power consumption | 5 W (200 mA at 24 V DC) |
Certificates and approvals | CE, RCM, CSAUS/C, FM |
Accuracy | |
Error in measurement | 0.25 % of measuring range (in air) |
Resolution | 3 mm (0.125 inch) |
Temperature compensation | Built in |
Echo processing | Sonic Intelligence |
Rated operation conditions | |
Beam angle | 12° |
Ambient temperature | |
| -40 ... +60 °C (-40 ... +140 °F) |
| -20 ... +60 °C (-4 ... +140 °F) |
Max. static operating pressure | Normal atmospheric pressure |
Degree of protection | IP65 |
Design | |
Weight | |
| 1.5 kg (3.3 lb) |
| 1.7 kg (3.7 lb) |
Material | |
| PVC |
| PVDF copolymer |
Degree of protection | IP65 |
Process connection | - 2" NPT [(Taper), ANSI/ASME B1.20.1]
- R 2" [(BSPT), EN 10226]
- G 2" [(BSPP), EN ISO 228-1]
- 4" sanitary
|
Flange adapter | 3" Universal (fits DN 65, PN 10 and 3" ASME) |
Cable inlet | 2 inlets for PG 16 or Ѕ" NPT cable glands |