Mode of operation | | |
Measuring principle | Inverse frequency shift capacitive level detection | Inverse frequency shift capacitive level detection |
Input | | |
Measured variable | Change in picoFarad (pF) | Change in picoFarad (pF) |
Output | | |
Output signal | | |
| 4 ... 20/20 ... 4 mA 2-wire loop | 4 ... 20/20 ... 4 mA 2-wire loop |
| Solid-state: 30 V DC/30 V AC, max. 82 mA | Max. switching voltage: 60 V DC/30 V AC Max. switching current: 1 A |
| Min. or max. | Min. or max. |
Accuracy | | |
Repeatability | 2 mm (0.08 inch) | 2 mm (0.08 inch) |
Rated operating conditions2) | | |
Installation conditions | | |
| Indoor/outdoor | Indoor/outdoor |
Ambient conditions | | |
| -30 ... +85 °C (-22 ... +185 °F) | -10 ... +85 °C (14 ... 185 °F) |
| I | I |
| 4 | 4 |
Medium conditions | | |
- Relative dielectric constant Оµr
| Min. 1.5 | Min. 1.5 |
| -30 ... +100 °C (-22 ... +212 °F) | -10 ... +100 °C (14 ... 212 °F) |
| -1 ... +10 bar g (-14.6 ... +146 psi g), nominal2) | -1 ... +10 bar g (-14.6 ... +146 psi g), nominal |
| | |
| IP68/Type 4/NEMA 4 | IP68/Type 4/NEMA 4 |
| IP65/Type 4/NEMA 4 | Not applicable |
| Ѕ" NPT (M20 x 1.5 optional) | Ѕ" NPT (M20 x 1.5 optional) |
Design | | |
| Enclosure/Integral cable version | Fully synthetic version |
Material | | |
| Thermoplastic polyester | Thermoplastic polyester |
| Transparent thermoplastic polycarbonate (PC) | Transparent thermoplastic polycarbonate (PC) |
- Integrated cable body
(Integral cable version)
| 316L stainless steel | Not applicable |
Sensor length (nominal) | 100 mm (4 inch) | 100 mm (4 inch) |
Process connection material of probe/wetted parts3) | Connection: 316L stainless steel; Process seal: FKM (optional FFKM); Sensor: PPS (optional PVDF)4) | PPS process connection and PPS sensor (Uni-Construction) |
Connection (Enclosure version) | Internal 5-point terminal block, Ѕ" NPT wiring entrance, M20 x 1.5 optional | Removable internal 5-point terminal block, Ѕ" NPT wiring entrance, M20 x 1.5 optional |
Connection (Integral cable version) | 4 conductors, 1 m (3.3 ft), 0.5 mmІ (22 AWG), shielded, polyester jacket | Not applicable |
Process connection | ѕ" NPT [(Taper), ANSI/ASME B1.20.1] R 1" [(BSPT), EN 10226/PT (JIS-T), JIS B 0203] G 1" [(BSPP), EN ISO 228-1/PF (JIS-P), JIS B 0202] | ѕ" NPT [(Taper), ANSI/ASME B1.20.1] R 1" [(BSPT), EN 10226/PT (JIS-T), JIS B 0203] |
Power supply | | |
Standard | 12 ... 33 V DC | 12 ... 33 V DC |
Intrinsically Safe | 10 ... 30 V DC (Intrinsically Safe barrier required) | Not applicable |
Certificates and approvals | - General: CE, CSA, FM, RCM
- Marine: Lloyds Register of Shipping, categories ENV1, ENV2, and ENV5
Dust Ignition Proof (barrier required): CSA/FM Class II and III, Div. 1, Groups E, F, G T4 - Intrinsically Safe (barrier required): CSA/FM Class I, II, and III, Div. 1, Groups A, B, C, D, E, F, G T4
ATEX II 1 GD 1/2GD EEx ia IIC T4 to T6 T107 °C - Overfill protection: WHG (Germany)
|
|