Suitability for use | Easy connection of data terminals to the IE FC cabling system | Easy connection of data terminals to the IE FC cabling system |
Cable designation | LI 02YSCH 4x2x0,15 PIMF GN FRNC | LI 02YSCY 2x2x0,15/0,98 PIMF ICCS GN |
Wire length | 1 m | 1 m |
Electrical data | | |
Damping ratio per length | | |
| 86 dB/km | 85 dB/km |
| 280 dB/km | 278 dB/km |
| 501 dB/km | 500 dB/km |
| 735 dB/km | 733 dB/km |
Impedance | | |
| 100 Ω | 100 Ω |
| 100 Ω | 100 Ω |
Relative symmetrical tolerance | | |
| 15 % | 15 % |
| 10 % | 6 % |
Transfer impedance per length at 10 MHz | 10 mΩ/m | 10 mΩ/m |
Loop resistance per length maximum | 290 mΩ/m | 300 mΩ/m |
Insulation resistance coefficient | 500 GΩ·m | 500 GΩ·m |
Operating voltage | | |
| 80 V | 80 V |
NVP value in percent | 80 % | |
Mechanical data | | |
Number of electrical cores | 8 | 4 |
Design of the shield | Overlapped aluminum-clad foil, sheathed in a braided screen of tin-plated copper wires | Overlapped aluminum-clad foil, sheathed in a braided screen of tin-plated copper wires |
Core diameter | | |
| 0.5 mm | 0.48 m |
Outer diameter | | |
| 0.5 mm | 0.48 mm |
| 1 mm | 0.98 mm |
| 6.2 mm | |
Symmetrical tolerance of the outer diameter of cable sheath | 0.3 mm | |
Width of cable sheath | | 5.8 mm |
Symmetrical tolerance of width of cable sheath | | 0.2 mm |
Thickness of cable sheath | | 3.7 mm |
Symmetrical tolerance of thickness of cable sheath | | 0.2 mm |
Material | | |
| PE | PE |
| FRNC | PVC |
Color | | |
| white/blue, white/orange, white/green, white/brown | white/blue, white/orange |
| green | green |
Bending radius | | |
| 31 mm | 24 mm |
| 43.5 mm | 42 mm |
Weight per length | 50 kg/km | 32 kg/km |
Permitted ambient conditions | | |
Ambient temperature | | |
| -25 ... +80 °C | -40 ... +70 °C |
| -25 ... +80 °C | -40 ... +70 °C |
| -25 ... +80 °C | -40 ... +70 °C |
| -25 ... +80 °C | -40 ... +70 °C |
| In fixed installation -40 °C to 80 °C | |
Burning behavior | flame resistant according to IEC 60332-1 | flame resistant according to IEC 60332-1 |
Chemical resistance | | |
| oil resistant according to IEC 60811-2-1 (4 h / 70°C) | oil resistant according to IEC 60811-2-1 (4 h / 70°C) |
| Conditional resistance | Conditional resistance |
Protection class IP | IP20 | IP20 |
Product properties, functions, components general | | |
Product feature | | |
| Yes | No |
| Yes | Yes |
Standards, specifications, approvals | | |
UL/ETL listing 300 V Rating | No | No |
UL/ETL style 600 V Rating | No | No |
Certificate of suitability | | |
| Yes | Yes |
Standard for structured cabling | Cat6A | Cat6 |
Marine classification association | | |
| No | No |
| No | No |
| No | No |
| No | No |
| No | No |
| No | No |
| No | No |