Input | |
Input | 1-phase AC |
Rated voltage value Vin rated | 120 ... 230 V |
Voltage range AC | 93 ... 264 V |
Wide-range input | Yes |
Overvoltage resistance | Surge voltage in accordance with EN 61000-6-2 Table 4 |
Mains buffering at Iout rated, min. | 10 ms; at Vin = 120 V, 40 ms at Vin = 187 V |
Rated line frequency 1 | 50 Hz |
Rated line frequency 2 | 60 Hz |
Rated line range | 47 ... 63 Hz |
Input current | |
| 1.9 A |
| 1.15 A |
Switch-on current limiting (+25 °C), max. | 30 A |
Duration of inrush current limiting at 25 °C | |
| 3 ms |
IІt, max. | 3 AІ·s |
Built-in incoming fuse | T 4 A/250 V (not accessible) |
Protection in the mains power input (IEC 898) | Recommended miniature circuit breaker: from 10 A characteristic C or from 16 A characteristic B |
Output | |
Output | Controlled, isolated DC voltage |
Rated voltage Vout DC | 15 V |
Output voltage | 2 x 15 V DC |
| 15 V |
| 15 V |
Total tolerance, static ± | 2 % |
Static mains compensation, approx. | 0.2 % |
Static load balancing, approx. | 0.2 % |
Residual ripple peak-peak, max. | 50 mV |
Residual ripple peak-peak, typ. | 20 mV |
Spikes peak-peak, max. (bandwidth: 20 MHz) | 150 mV |
Adjustment range | 14.5 ... 17 V |
Product function Output voltage adjustable | Yes |
Output voltage setting | via potentiometer |
Status display | Green LED grГјn for Vout >10 V (summation display) |
Signaling | - |
On/off behavior | Overshoot of Vout < 3 % |
Startup delay, max. | 1 s |
Rated current value Iout rated | 3.5 A |
Output current | |
| 3.5 A |
| 3.5 A |
Current range | 0 ... 3.5 A |
| +45 ... +60 °C: Derating 2%/K |
Supplied active power typical | 105 W |
Parallel switching for enhanced performance | Yes |
Numbers of parallel switchable units for enhanced performance | 2 |
Efficiency | |
Efficiency at Vout rated, Iout rated, approx. | 80 % |
Power loss at Vout rated, Iout rated, approx. | 27 W |
Protection and monitoring | |
Output overvoltage protection | Yes, according to EN 60950-1 |
Current limitation | 4.9 A |
Current limitation | Limit point < 4.9 A; switch-off point < 6 A |
Property of the output Short-circuit proof | Yes |
Short-circuit protection | Electronic shutdown, automatic restart |
Overload/short-circuit indicator | - |
Safety | |
Primary/secondary isolation | Yes |
Galvanic isolation | Safety extra low output voltage Vout according to EN 60950-1 |
Protection class | Class I |
Leakage current | |
| 3.5 mA |
CE mark | Yes |
UL/cUL (CSA) approval | cULus-Listed (UL 508, CSA C22.2 No. 142), File E179336 |
Explosion protection | - |
FM approval | - |
CB approval | No |
Marine approval | - |
Degree of protection (EN 60529) | IP20 |
EMC | |
Emitted interference | EN 55011 Class A |
Supply harmonics limitation | - |
Noise immunity | EN 61000-6-2 |
Operating data | |
Ambient temperature | |
| 0 ... 60 °C |
| with natural convection |
| -40 ... +70 °C |
| -40 ... +70 °C |
Humidity class according to EN 60721 | Climate class 3K3, no condensation |
Mechanics | |
Connection technology | screw-type terminals |
Connections | |
| L1, N, PE: 1 screw terminal each for 0.5 ... 2.5 mmІ single-core/finely stranded |
| P15_1, GND_1, GND_2: 1 screw terminal each for 0.5 ... 2.5 mmІ; P15_2: 2 screw terminals for 0.5 ... 2.5 mmІ |
| - |
Width of the enclosure | 75 mm |
Height of the enclosure | 125 mm |
Depth of the enclosure | 125 mm |
Required spacing | |
| 100 mm |
| 100 mm |
| 0 mm |
| 0 mm |
Weight, approx. | 0.75 kg |
Product feature of the enclosure housing for side-by-side mounting | Yes |
Installation | Snaps onto DIN rail EN 60715 35x7.5/15 |