All racks included: - Mounting rail with threaded bolts for fixing the modules and lateral cutouts for mounting the rack
- Plastic parts serve as guides when swinging the modules into place
- Connection for protective conductors
- Backplane bus with plug-in connections
UR1 for central controllers- 18 single-width slots
- Always required: Power module (PS) and one CPU
- Can be expanded centrally (up to 5 m) and in distributed configuration (up to 600 m)
- The following are required when expanded:
- Interface modules (send IMs); max. 6 interface modules can be plugged in
- Up to 21 expansion units can be connected
UR2 for central controllers- 9 single-width slots
- Always required: Power module (PS) and one CPU
- Can be expanded centrally (up to 5 m) and in distributed configuration (up to 600 m)
- The following are required when expanded:
- Interface modules (send IMs); max. 6 interface modules can be plugged in
- Up to 21 expansion units can be connected
CR2 for central controllers- 18 single-width slots; 2 segments with 8 or 10 slots
- Always required: Power module (PS) und 2 CPUs
- Can be expanded centrally (up to 5 m) and in distributed configuration (up to 600 m)
- The following are required when expanded:
- Interface modules (send IMs). Max. 6 interface modules can be plugged in
- Up to 21 expansion units can be connected.
- 2 CPUs can be operated next to each other, each with its own I/O:
2 P bus segments with 10 or 8 slots for 1 CPU each with its own I/O - C bus throughout: C bus nodes can be addressed from both segments.
CR3 for central controllers- 4 single-width slots
- Always required: Power module (PS) and one CPU
- Can be expanded centrally (up to 5 m) and in distributed configuration (up to 600 m)
- The following are required when expanded:
- Interface modules (send IMs); max. 2 interface modules can be plugged in
- Up to 16 expansion units can be connected
- C bus and P bus throughout
UR2-H- 18 single-width slots; 2 segments with 9 slots each
- Always required: 2 power modules (PS) und 2 CPUs
- Can be expanded centrally (up to 5 m) and in distributed configuration (up to 600 m)
- The following are required when expanded:
- Interface modules (send IMs); max. 6 interface modules can be plugged in
- Up to 21 expansion units can be connected
- 2 CPUs can be operated next to each other, each with its own I/O:
2 P bus segments and 2 C bus segments with 9 slots each for 1 CPU each with its own I/O - C bus throughout: C bus nodes can be addressed from both segments
UR1 for expansion units- 18 single-width slots
- Always required: Interface module (receive IM)
UR2 for expansion units- 9 single-width slots
- Always required: Interface module (receive IM)
ER1 for expansion units- 18 single-width slots
- Always required: Interface module (receive IM)
- P bus with restricted functionality:
- No alarm processing
- No battery backup of the plugged-in modules
- No 24 V DC supply of the modules
- No C bus
- The following can be used:
- SM modules
- Receive IM
- Power supply module
ER2 for expansion units- 9 single-width slots
- Always required: Interface module (receive IM)
- P bus with restricted functionality:
- No alarm processing
- No battery backup of the plugged-in modules
- No 24 V DC supply of the modules
- No C bus
- The following can be used:
- SM modules
- Receive IM
- Power supply module
|
|